| 1 | Design, Supply, Installation, testing and Commissioning of WQM (Water Quality Monitoring System) with real time online monitoring all the specified parameters as per BSI std for drinking water and have a check on the given parameters. WQM should be a skid mounted system comprising of SS storage Sampling tank of 60 Ltr Capacity, circulation pump, Control panel, interconnecting piping with all valves & Fittings. System should be installed in parallel to the existing water supply line, it should take bleed from the water supply line and should reconnect to same line. Sampling tank should have all the sensors attached to it to monitor the real time parameters. The sensors should be compatible to the Local BMS. The entire system of pump, tank and fittings shall be mounted on base plate and shall have structure frame to strengthen/balance the entire skid. The supplier shall comply all the specification. The system should be ISO 9001:2015 and CE Marked. The system shall be equipped with following feature and specification as under. |
| 2 | a) SYSTEM OPERATIONi) Sampling Tank: - SS 316 mirror finished 60 L hold up volumeii) Valves: - UPVC Manual valves and check valve to isolate the system from the main stream during maintenance.iii) Piping: - Food grade UPVC piping of size 25mm.iv) Pump: - 0.5 HP 10mtr head 30 lpm at the inlet of WQM for sucking water from main line,passing through sampling tank and then sending it back to main line.v) All Component of tank shall be of SS316 L or higher grade material |
| 3 | b) ELECTRICAL CONTROL SYSTEMi) Electrical connection required: - 3-Phase, 415 Volt and 50 Hzii) Single point termination should be required, all internal wiring shallbe strictly factory fitted. MONITORING AND CONTROL FACILITYi) The system shall have separate indicators for each parameter in the control panel.ii) System should have Water\"s pH value, TDS (Total Dissolved solids) Temperature sensor, ORP (Oxygen reduction potential) sensor.iii) Control panel should have pump ON /Off Status. |
| 4 | c) MONITORING SENSORS FEATURESi) PH sensor –Resolution: 0.01 Range : 0 to 14pH pH Accuracy: ± 0.01pH Calibration: 2 Point ( Manual) Retransmission Output : 4 to 20 mA Isolated.ii) TDS transmitter-Range : 0 to 2000 ppm Resolution : 1 ppmMeasuring Accuracy : ±1%FSIndication : 3.5 digit LED displayRetransmission Output : 4 to 20 mA Isolated.iii) ORP Indicating Controller Cum Transmitter systemRange : ± 2000 mVResolution : 1 mVAccuracy : ± 0.2% of Full ScaleCalibration : Soft Key calibration – 1 Point |
| 5 | d) ACCESSORIES AND PARTSi) SS tank 60 L -1 Noii) Local control panel all indicatorsiii) Water pump 0.5 HP 10mtr head 30 lpm - 1 noiv) UPVC sluice valve-2 Nos.v) UPVC Check valve- 2 Nos.vi) PH sensor -1 Novii) ORP transmitter- 1 Noviii) Total Suspended solid transmitter-1Noix) Temperature sensor-1 no |
| 6 | Fabricating, supplying and fixing of wire mesh protection frame work fabricating with 40 x 40 x 6 mm thick angle iron/Tee iron having intermediate members of size 25mm x 6 mm (GI wire should be 6SWG) flat strip welded at 30 cm in each sections & duly welded with hard drawn wire fabric mesh of size 25 mm X 75 mm having weight not less than 7.5 Kg/Sqmtr.and making main door gate provided with two nos. sliding bolt with godown locks with operating hadle welded from inside of the door i/c providing and fixing of four no. legs of same angle size of 90 cm length duly grouted in foundation (30 x 30 x 45) cm (deep) in 1:2:3 cement concrete & painting with one coat of red oxide & two coat of super synthetic luminous paint of approved colour and quality etc. complete as complete as reqd. {Area of hard drawn wire fabric with angle (Except legs) shall be measured for payment} |
| 7 | Providing & fixing UV stabilised fiberglass reinforced plastic sheet roofing up to any pitch, including fixing with polymer coated \"J\" or \"L\" hooks, bolts & nuts 8mm dia. G.I plain/bitumen washers complete but excluding the cost of purlins, rafters, trusses etc. The sheets shall be manufactured out of 2400 TEX panel rovigs incorporating minimum 0.3% ultra-violet stabiliser in resin system under approximately 2400 psi and hot cured. They shall be of uniform pigmentation and thickness without air pockets and shall conform to IS 10192 and IS 12866.The sheets shall be opaque or translucent, clear or pigmented, textured or smooth as specified.a) 2 mm thick flat |
| 8 | Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 9 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 10 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 11 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |