| 1 | Supplying and fixing testing, connecting and commissioning of 16 gauge powder coated LT Panel out door mountable (IP-65),lockable door, of suitablecomplete with bus bars , Ampmeter, Ampmeter selector switch , voltmeter , Voltmeter selector switch ,Digital meter, indicating lamps, CT\"s , Interconnection with suitable capacity aluminium strips / rods, connection of incoming and outgoing cables with thimbles , stove enamelled painted and having following incoming and outgoingMCCB, switch MBC with complete all as required. |
| 2 | Main LT Distribution Panel |
| 3 | INCOMING: |
| 4 | 1 Nos. of400 A 415V, 4 Pole MCCB 50kA MP Based Release (O/C &S/C protection), with Rotary Operated Handle Mechanism, Pole spreader for MCCB 400A, 1 nos. Digital type Multifunction Meter, Digital type Voltmeter CL-1.0 with selector switch.1 nos. Digital type Ammeter CL-1.0 with selector switch with CT\"s 400/5A CL-1.0, 15VA Cast Resin for metering, ON, OFF & RYB phase indicating lamps , 6 no. 5A SP MCB 10 kA for Cont. Ckt. complete as reqiured. |
| 5 | BUSBARS: |
| 6 | 1 Set. 400A 50Hz four pole AL. Busbar. |
| 7 | OUTGOING: |
| 8 | 2 Nos. 200A 415V, FP MCCB of 36kA with TM Based Release (O/C &S/C protection), 2 no. Rotary Operated Handle Mechanism, 2 no. 4 Pole spreader for MCCB 200Awith Digital type Multifunction Meter at each outgoing etc complete as required. |
| 9 | 2 Nos. 100A 415V, FP MCCB of 25kA with TM Based Release (O/C &S/C protection), 2 no. Rotary Operated Handle Mechanism, 2 no. 4 Pole spreader for MCCB 100Awith Digital type Multifunction Meter at each outgoing etc complete as required. |
| 10 | Cost of LT panel |
| 11 | Supply of one no.XLPE cable aluminum conductor steel armoured power cable of 1.1kV grade of size3-1/2x 300 sq.mm. complete as required and as instructed by Engineer in charge. |
| 12 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 13 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 14 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 15 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 16 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. |
| 17 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 18 | Above 185 sq. mm and upto 400 sq. mm |
| 19 | Laying ofonenumberadditionalPVCinsulatedandPVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 20 | Above 185 sq. mm and upto 400 sq. mm |
| 21 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL pipe as required. |
| 22 | Above 185 sq. mm and upto 400 sq. mm |
| 23 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 24 | Above 185 sq. mm and upto 400 sq. mm |
| 25 | Laying andfixingofonenumberPVCinsulatedandPVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 26 | Above 185 sq. mm and upto 400 sq. mm |
| 27 | Laying andfixingofonenumberPVCinsulatedandPVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 28 | Above 185 sq. mm and upto 400 sq. mm |
| 29 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 30 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 31 | 3½ X 300 sq. mm (70mm) |
| 32 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc as required |
| 33 | 100 mm dia |