| 1 | Supplying and Fixing following sizes of FRLS PVC insulatedcopper conductor, single core cable in recessed steel/ PVC existing /fresh conduit or PVC Channel as required. (Excluding cost of PVC Conduit/Channel) |
| 2 | 3 x 2.5 sq. mm |
| 3 | P/F PVC Channel 2 mm thick 25mm wide with accessories forabove mentioned single core cable wherever necessary. |
| 4 | P/F piano type switch15/ 16 A Switch |
| 5 | P/F of piano typer switch6 pin 15/16 A Socket outlet |
| 6 | P/F of Bakelite Sheet/Phenolic Sheet 3mm thick(6\"\"x9\"\")= 20Nosfor abovementioned switch and sockets. The job includes the cost of cutting required for fixing switch sockets. |
| 7 | Supply, installation testing and commissioning of following sizes shutter type exhaust fans 900/1600 RPM, the job includes cost of wall opening complete as required at site .(a) 250mm Dia |
| 8 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 9 | Providing and laying of following sizes 3 ½ core/PE Al. cable Armored as fresh ones. 1.1KV grade. The job includes cost of excavation and suitable size iron clampscomplete as required at site. |
| 10 | a) 50 mmsq( for OT Lift and from Service Block ) |
| 11 | b) 95 mmsq( for OTfrom 1st floor and from Service Block ) |
| 12 | Supplying and making end termination and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 13 | a) 50 mmsq |
| 14 | b) 95 mmsq |
| 15 | Supplying and fixing of following ways surface/ recessmounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 160 A tinned copper bus bar, common neutral link, earth bar,din bar for mounting MCBs (but without MCBs and incomer ) asrequired . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 16 | a) 8 way (4 + 24), Double door |
| 17 | Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories, and providing masonry enclosurewith cover plate having locking arrangement and watering pipeof 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 18 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metrebelow ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 19 | Providing and fixing 100A 4 pole MCCB30KA adjustable with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 21 | a) Single pole |
| 22 | b) Triple pole |
| 23 | SITC of Bus Bar Chanmber, TPN, Factory fabicated, complete with Lock, Hinged Type Door, with Al. Bus Bar, Earthing Nut Bolt and Painting Powder coated, Heay Duty: |
| 24 | i. 400A (8 Way, 1 In, 8 Out) |
| 25 | ii. 200A (8 Way, 1 In, 8 Out) |
| 26 | Supply Installation testing & Commissioning of MS Class \"C\" ERW pipescovered with the glass wool of 48 kg/³ density duly sealed with UV film or aluminium cladding of following dia\"s complete with all acessories & fittigs like tees, elbows, bends, junctions, unions, flanges etc.clamps structural supports as required/directed at site including painting the pipes with anti-corrosive paint over a coat of primer |
| 27 | a) 50 mm dia |
| 28 | b) 32 mm dia |
| 29 | Providing and fixing of ball Valve (ISI marked) of following size |
| 30 | a) 50 mm dia |
| 31 | b) 32 mm dia |
| 32 | Supply fixing testing & commissioning of Submersible sewerpump for sucking out the water from the cable Trench between transformers/ DG sets and electric sub/stn of below mentioned specifications & complete with all accessories including valves, strainer other fitting . The job also includes the base frame of required dimensions of gear pump with DOL starter and electric cable wiring of 2.5 mm² FRLS single core copper flexible type through MS conduit of suitable size from main electrical source to starter and starter to pump Specification Motor rating :3/4 HP |
| 33 | Providing and fitting of corrugated galvanized iron sheet of 24 SWG having uniform 120 gsm zinc coatedof dimension 6\" x 2.5\"alongwith G.I hooks and appropriate fitting arrangement complete as required at site. |
| 34 | Supply and erectionof frame out of ISA 50 x 50 x 6 mm alongwith G.I hooks and appropriate fitting arrangement for above mentioned iron sheets |
| 35 | Supply and erection 75 x 40x4.8 mm MS channelofmain supports for above mentioned frame. |
| 36 | CEMENT CONCRETE (CAST-IN-SITU) Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with(1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) |