Name of Work:Rate Contract for Supply and Installation of HEPA Filters and Validation of 25 Nos. Modular Operation Theatre (MOT) at AIIMS Rishikesh
Sl. No.
Item Description
1
Supply and Installation of Mini pleat HEPA Filter flange type with media packing of 2 inch, H 14 Grade, Efficiency 99.999% down to 0.3µ, IPD 160Pa +- 10% & FDP 500Pa, MOC: - Aluminium anodized extrusion Filter media: - Glass fiber with hot melt separator with both side GI faceguard, Neoprene Gasket 5 mm, Operating temperature 70°C Size -305(mm)X610(mm)X69(mm), 250 CFM
2
Supply and Installation of Mini pleat HEPA Filter flange type with media packing of 2 inch, H 14 Grade, Efficiency 99.999% down to 0.3µ, IPD 160Pa +- 10% & FDP 500Pa, MOC: - Aluminium anodized extrusion Filter media: - Glass fiber with hot melt separator with both side GI faceguard, Neoprene Gasket 5 mm, Operating temperature 70°C. Size -610(mm)X915(mm)X69(mm), 750 CFM
3
Supply and Installation of Mini pleat HEPA Filter flange type with media packing of 2 inch, H 14 Grade, Efficiency 99.999% down to 0.3µ, IPD 160Pa +- 10% & FDP 500Pa, MOC: - Aluminium anodized extrusion Filter media: - Glass fiber with hot melt separator with both side GI faceguard, Neoprene Gasket 5 mm, Operating temperature 70°C. Size -610(mm)X760(mm)X69(mm), 625 CFM
4
Supply and Installation of Mini pleat HEPA Filter flange type with media packing of 2 inch, H 14 Grade, Efficiency 99.999% down to 0.3µ, IPD 160Pa +- 10% & FDP 500Pa, MOC: - Aluminium anodized extrusion Filter media: - Glass fiber with hot melt separator with both side GI faceguard, Neoprene Gasket 5 mm, Operating temperature 70°C. Size -610(mm)X610(mm)X69(mm), 500 CFM
5
Validation of 25 Nos. MOT (Each MOT with HEPA filter – 6 Nos of above-mentioned size) as per ISO 14644 standards. Following tests to be done: - 1. Temperature and Humidity check 2. Non-Viable particle count 3. Air Change Rate Calculation 4. Air velocity at outlet of terminal filtration unit /filters 5. Pressure Differential levels of the OT with respect to ambient / adjoining areas 6. HEPA Filter Integrity Test (using PAO) 7.Recovery Test 8. Air flow pattern test with videography (using water fogger) 9.Light Intensity Measurement10. Sound Level Measurement