Electro-Mechanical And Civil Works To Be Carried Out At Wadoora ( Stage 1St And Stage 2Nd ) Electro-Mechanical And Civil Works-2 Providing, Fitting, Installation, Testing And Commissioning Of Vt Pumping Unit Of Approved Make Withfollowing Specifications: At Stage 1St Discharge Of The Pump = 15000 Gph Dynamic Head = 48 M Speed = 1450 Rpmworking Voltage = 380 ± 15 V, 03 Phaserating = Corresponding To The Head And Discharge Not Less Than 25 Hp.Rest Of Specification / Details Are As Per Clause 6 Of Annexure C Of Sbd 3 Providing / Supplying And Fitting Ofg.I Flanged Rising Main At Site. The Pipe Shall Be Hot Dip Galvanized, Class-C Confirming To Is 1239. The Job Includes Providing And Fitting Of M.S Flanges Conforming To Bis 6392 / 1997 Table 17 ( Rating Pn16 ) For Y Junction And Washoutsize: 150Class:C ( Heavy ) Rest Of Specification As Per Clause 8 Of Annexure C Of Sbd 4 Cutting Of Hot Dip Galvanized Gi , C-Class Pipe Acoss The Section By Dint Of Pipe Cutter / Gas Cutter. The Job Includes Providing And Welding Of M.S. Flanges To The Two Ends Of Pipe. The Thickness Of Flange Shall Conform To Is 6392 Part 1St Table-17Dia: 150`Rest Of Specification As Per Clause 11 Of Annexure C Of Sbd 5 Fabrication , Providing And Fiting Of Y- Junction Havingminimum 1M Arm Length Of Each Arm To Be Fabricated Out Of G.I C Class Pipe With M.S. Flanges Conforming To Bis 6392 / 1997 Table 17 ( Rating Pn16 ) Fastened With Weld Joints On Three Ends.Dia: 150 Mmrest Of Specification As Per Clause 8 Of Annexure C Of Sbd 6 Providing And Fitting Of, Ductile Iron Double Flanged, Non-Rising Spindle Soft Seatedglandless Gate / Sluice Valves As Per Is14846 For Regulating The Water Supply Outside The Pumping Units .Size: Dn150pn:1.6 / 16 Rest Of Specification / Details Areas Per Clause 12 Of Annexure C Of Sbd 7 Providing And Fitting Ofductile Iron Double Flanged, Slanted Seatswing Check Valve ( Nrv ) As Per Is 5312. Size: 150Mmpn: 1.6 / 16Rest Of Specification / Details Areas Per Clause 13 Of Annexure C Of Sbd 8 Providing And Fitting Of 150 Mm Dia Flanged Flanged Bends / Elbolw To Delivery Mainfold And Washout, Including Nuts And Bolts And Rubber Gaskets As Per Requirement.Rest Of Specification / Details Areas Per Clause 15 Of Annexure C Of Sbd 9 Providing And Fitting Of Flanged Washout Tee 150 Mm , Including Nuts, Bolts And Gasket As Per Site Requirement.Rest Of Specification / Details Areas Per Clause 09 Of Annexure C Of Sbd 10 Supply Installation , Testing And Commissioning Of Level Ii Ht Transfromercapacity: 100 Kvarest Of Specification / Details Areas Per Clause 26 Of Annexure C Of Sbd 11 9 M Long St-410 Sp33 Polerest Details As Per Clause 32 Of Annexure C Of Sbd 12 Cement Bottoming 1:2:4 Mix As Per Rec Standards 0.5 Cum / Pole 13 G.I V Cross With Top Bracket Including Clamps Rest Details As Per Clause 32 Of Annexure C Of Sbd 14 11 Kva Polymeric Insulators12 Kv , 5Kn , Lighting Impulse 75 Kv Positive And 80 Kv Negative With Creepage Distance 320Mmrest Details As Per Clause 31 Of Annexure C Of Sbd 15 Galvanized Nuts And Bolts ( 1Kg / Pole ) Rest Details As Per Clause 33 Of Annexure C Of Sbd 16 Danger Plate With Clampsrest Details As Per Clause 34 Of Annexure C Of Sbd 17 Anti Climbing Device With Clampsrest Details As Per Clause 35 Of Annexure C Of Sbd 18 Earthing Complete By Gi Pipe 40 Mm Or Gi Rod 20 Mm 2.5 Mtr Long Through Gi Strip 19 Red Oxide Coating Rest Details As Per Clause 37 Of Annexure C Of Sbd 20 Alumunium Paint Coating Rest Details As Per Clause 38 Of Annexure C Of Sbd 21 Stone Pad ( 300Mm X300mm X75mm ) Rest Details As Per Clauseof Annexure C Of Sbd 22 Pg Clamps Fo 50 Sqmm Acsr Conductor 23 Acsr Conductor 50 Sqmmrest Details As Per Clause 39 Of Annexure C Of Sbd 24 Gi Channel / Angle / Flat Of Sizes Including Clamps 25 11 Kva Go , Ab Switch 3 Phase, 3 Pole, 200 A, Vertical Typerest Details As Per Clause 28 Of Annexure C Of Sbd 26 11 Kv Polymeric Composite Disc Insulator 12 Kv, Min Failing Load 45Kn, Lighting Impulse 75Kv Positive And 80 Kv Negative, Creepage Distance 320Mm 27 Gapless Surge Arrrestor 9Kv, 10 Ka , La With Polymer Housing, Stn Typerest Details As Per Clause 30 Of Annexure C Of Sbd 28 50 Sq Mm ( 2 Ckt ) 1.1 Kv Grade, Pvc Insulated Stranded Conductor Frls Type 29 Earthing Of Substation- Rest Details As Per Clause 48 Of Annexure C Of Sbd 30 Lt Distribution Box For 100 Kva Dtr With 4 Pole Mccb For Incomer & SfuS For Outgoing Circuitsrest Details As Per Clause 42 Of Annexure C Of Sbd 31 Galvanised Stay Set With 50X8mm Stay Clam, Guy Insulators ( 2NoS ) , Anchor Plate ( 200X200x6mm ) , Nuts And Bolts, 2 Nos; Turn-Buckles, 1.8M Long, 16Mm Dia Meter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Completerest Details As Per Clause 36 Of Annexure C Of Sbd 32 Wedge Connectors / Pg Clampsrest Details As Per Clause 36 Of Annexure C Of Sbd 33 Providing, Installation, Testing And Commissioning Of Outdoor Type Ht Trivectometer As Per Iee Rule. Job Includes Grouting Of Legs In Cement Concrete As Per Site Requirement. All Cabling, Earthing And Allied Accessories Required To Be Provided By The Firm. Moreover Firm Responsible For Completing All Sealing Of Pdddepartment And Testing On Load And Noload At Site 34 Sundry Items Like Alumunium Lugs , Jumprs, Binding Tape 35 35 Sq Mm Ab ( Ht ) Cable ( 3X35+1X70 Sqmm ) Xlpe ( 11 Kv , 3C+Earth ) Rest Details As Per Clause 41 Of Annexure C Of Sbd 36 Heat Shrinkable Outdoor Cable Termination Kitrest Details As Per Clause 73 Of Annexure C Of Sbd 37 Providing & Fitting Of35 Sq Mm Single Core Copper Conductor ( Flexible ) Pvc Insulated Heavy Duty Industrial Cables ( Unsheathed ) , 1100 Volts Conforming To Is: 694- For Connecting Motors From Panel , Stabilizers In Rubber Conduit . Job Includes Providing& Laying Of Flexible Conduit For Cu Cable With Lugs As Per Requirement Heat Shrinkable Outdoor Cable Termination Kitrest Details As Per Clause 73 Of Annexure C Of Sbd 38 Providing, Installation , Testing Of Power Service Cablefor Workingvoltage Up To And Including 1100 Volts; 70 Sq Mm Armored Aluminum 3.5 Core Cable As Service Line From Output Terminals Of Ht / Lt Transformerto Cubical Panel. Cost Includes Laying Of Cable In Trenches In Pvc Conduit Where Ever Itis To Be Laid Underground As Per Site Requirement Included Is Termination Of Ends With Suitable Aluminum Tube Terminals Dully Crimpled & Taped. Rest Specifications As Per Clause 68 Of Annexure C Of Sbd 39 Providing And Fitting Of 3-Core Flat Submersible Copper Cable Conforming To Is: 694 ( Part 1St ) – 1964 & Is: 694 ( Part 2Nd ) - 1964 For Submersible Pumping Unit And Other Electrical Equipment. The Cable Connections Terminal Shall Be Fitted With Copper Thimbles Of Required Size. The Main Specification Of The Cable Is Given Below:Size: 16 Sq Mmrest Specification As Per Cluase 47Of Annexure C Of Sbd. 40 Providing , Fitting, Testing And Commission Of Heavy Duty De-Silting Pumping Unit Complete Unit Of Capacity 25000 Gph Head 25 M And Motor Including Compete Cabling, Starter- 2Nos ( One As Standby ) , Sluice Valves , Agitator Function, Delivery Pipe Minimum 50 M With Ms Supports With All Joints And Accessories. Complete Jobjob Includes Fabrication , Providing , Fitting And Testing Of Gantry System For Fabricated Out Of Iscm / Ismbbelow Machine Floor Of Circular Shape Approx. 7 M Dia.The Gantry System Should Be Fabricate In Such A Way That Desilting Pumping Unit Should Move In All Directions. Job Includes Providing And Fitting Of 2 Mt Chain Pulley Block ( Chain Lift 10 M ) And Monorail Of Induff / Globe Make. The De-Silting Pumping Have. . Job Also Includes Making Of Hole And Covering Of The Same With 8 Mm Thick Ms Sheet & Isa.Job Also Includes Fabrication Of Ladder And Plate Form At Middle In Isa, Ismc For Handling Of The System 41 Providing, Installation, Testing And Commissioning Of 100 Kva Voltage Stabilizer Rest Details & Specification As Per Clause 44 Of Annexure C Of Sbd 42 Fabrication Providing And Fitting Of 3 Phase Modular Control Panel. The Technical Details / Ratings Of Various Components Of Modular Control Panel Are Given Below B. Main Circuit Breaker = 250 Ac. Changeover Switch = 200 Ad. Motor Breakup Protectionmccb= 200 Ae. Fasdstarter - 2 Units With Rating Line Contactor _Ac3 110 A , Delta Contactor- Ac3 110 Astar Contractor- Ac3 90Atimer- Star Delta Electronicthermal Overload Relay- With Relay Range 35-75 Direct / Ct Operated Suitable-Rangeaux Coil Voltage Wide Band Fitted With Seperate Stabilization Unit Min 1Kw Aux Wiringf ) . Auxillary Mccb =63 Ampwith S.C. Breaking Capacity Of36kag ) . Motor Protection Relay Suitablei ) M-Power Module For Mobile Starter & Earth Fault Relay J ) Water Level Controller Rest Of Deatils / Technical Specification Are As Per Clause 43 Ofannexure C Of Sbd 43 Providing, Installation And Testing Ofheavy Duty Manual Type Triple Spur Gear Chainpulley Block Along With Monorail Geared Travelling Trolley Having Followingfeaturesmake = Reputed Make Capacity = 3 Ton ( P ) No. Of Load Chain Falls = 2 Or Above Min. Height Of Lift = 6 Mrest Details / Specification As Per Clause 24 Of Annexure C Of Sbd 44 Illumination Of Premises:Providing And Erection Of 9 Mtr Long Hot Dip Galvanized Octagonal Pole Rest Of Deatils / Technical Specification Are As Per Clause 50 Ofannexure C Of Sbd 45 Providing, Installation, Testing And Commissioning Of Area Lighting 120 Watt Led ( Street Light Type ) On Top Of Octagonal Pole , Including Mcb Fiited In Box 10Arest Details / Specification As Per Clause 51 Of Annexure C Of Sbd 46 Providing And Installation Of Junction Box With Dp 32Amp Mcb To Serve As Amin Switch For Led Lighting Including Complete Wiring Min 20-30 M From Panel Board.Rest Details / Specification As Per Clause 52 Of Annexure C Of Sbd 47 Providing, Installation And Testing Of 2Kva Fully Automatic Voltage Stabilizer , Including Wiringrest Details / Specification As Per Clause 53 Of Annexure C Of Sbd 48 Providing & Fitting Oflighting Points For ( Machine Room , Operators Room, ) As Per Site Requirement In 1.5 Mm² Multistranded Single Core 1100 Volts, Pvc Insulatedcopper Conductor Through Pvcconduit Pipe By Way, Switches, Socket Modules , Regulators , Indicators, 08 / 10 Watt Led Lamps Surface Light Make. .Included Is Cost On Account Of Modular Switch Boards With The Wooden Frames As Per Site Requirements 49 Providing Fitting Of Heating Points In 2.5Mm² Multistranded Single Core 1100 Volts, Pvc Insulated Copper Conductor Through Pvc Conduit By Way Of P / F Of 15 Amp Switches, 6 Pin Socketon Modularfittingas Per Site Requirements. Heating Points Are To Be Connected From Main Control Panel. All Accessories Required Is To Be Provided By The Firm 50 Providing And Fitting Of 9” X 9”Exhaust Fan With Complete Wiring In 1.5 Mm Cu Wire Through Conduit And 6 A Modular Controlcomplete Job. Make Providing And Fitting Of 9” X 9”Exhaust Fan With Complete Wiring In 1.5 Mm Cu Wire Through Conduit And 6 A Modular Controlcomplete Job. 51 Providing, Fitting Of Distribution Board Of Reputed Make 4 Way S P N Single Door Powder Coated Sheet Steel Enclosure For Surface Mounting Fitted With Bus Bar, Din Channel, Neutral Link And Incoming Contact. The Above Db Is To Be Provided / Fitted With Double Pole 40 Amp Mcb For Main. 32 A For Heating Circuit & Rest 3 Of 16 / 6 Amps Each For Premises Luminary, Auxiliary Circuit Of Reputed Make. Further Job Includes Providing / Fitting 4 Mm² Multistranded Single Core 1100 Volts, Pvc Insulated Copper Conductor Through Pvc Conduit As Service Line From Main Panel As Per Site Requirements. Connections Should Be Made In Such A Way Lighting Pointsis To Be Connected Via Automatic Transformer By Way Of P / F Switch Socket Arrangement With Allied Fixtures & And Heating Points To Main Panel. Job Includes Dismantling Of Existing Damaged Conduit , Wires, Conduit And Cleaning The Surface Properly 52 Earthing Of Panel Boad, Stabilizer, Motors, Heating Points, Lighting Points, D.G Setsrest Details As Per Clause 48 Of Annexure C Of Sbd 53 Painting On Steel Structure / Pipe With Synthetic Enamel Paint Of Approved Brand And Maufacturer Of Required Colour To Give An Even Shade On New Work ( Two Or More Coats ) Including A Coat Of Approved Steel Primer But Excluding A Coat Of Mordant Solution. ( Ref 13.61 ) Schedule2021 54 Providing , Installation, Testing And Commissioning Of 415+-10 V ( Out Put ) , 3 Phase Dg Set Of Specification Of Approved Make As Per Latest Guide Linecapacity =62.5 Kvarest Details / Specifications Are As Per Clause 66 Of Annexure C Of Sbd 55 Providing, Installation , Testing Of Power Service Cablefor Workingvoltage Up To And Including 1100 Volts; 95 Sq Mm Armored Aluminum 3.5 Core Cable As Service Line From Output Terminals Of Ht / Lt Transformerto Cubical Panel. Cost Includes Laying Of Cable In Trenches In Pvc Conduit Where Ever Itis To Be Laid Underground As Per Site Requirement Included Is Termination Of Ends With Suitable Aluminum Tube Terminals Dully Crimpled & Taped. Rest Specifications As Per Clause 67 Of Annexure C Of Sbd 56 Fabrication, Providing, Fitting Of Base Framefor Pumping Units , Covering Of Holes , Fabrication Of Gantry, Ladder , Dg Set Covering, Ht / Lt Transformer Bed With Gantry Fabricated Out Of Ismc / Ismb / Isa / Bars / Ms Pipe / Ms Plain-Chequrred Sheets. Including Making Of Holes In Concrete, Including Metal Primer 1 Coat And Two Coats Of Approved Shade . The Works Is To Be Executed As Per Site Requirement And As Per Dimentions Of Pumping Unit And As Per Directions Of Site Engineer.Rest Of Specification / Details Are As Per Clause 21 Of Annexure C Of Sbd 57 Providing And Laying In Position Cement Concrete Of Specified Grade Including Curing But Excluding The Cost Of Centring And Shuttering. All Work Upto Plinth Level 1:2:4 With Stone Aggregrate 20 Mm Nominal Size. For Dg Set Foundatioin / Concrete Beds For Rising-Main As Per Requirement 58 Centering And Shuttering Including Strutting, Propping Etc And Removal Of Form Work For Foundation, Footing , Base 59 Earth Work In Excavation By Manualmeans In Trenches For Foundations, Drains , Pipes , Cables Etc ( Not Exceeding 1.5 M In Width ) Andramming Of Bottoms Lift 1.5 M , Including Getting Out Excavated Earth And Disposal Of Surplus Exacavated Earth As Directed ( All Kinds Of Soil ) ( 2.81 Schedule ) 60 Providing And Laying Of Soling Stone 61 Cement Plaster In Find Sand In 1:3 Mix Finished With A Coat Of Neat Cement And Curing Complete 18 Mm Thick. ( S-11.8 ) 62 Supply, Installation, Testing & Commissioning Of 1000Va Full Sine Wave Power Inverter With 12V, 180Ah Tubular Inverter Batteryrest Details / Specification As Per Clause 54 Of Annexure C Of Sbd 63 Providing, Laying & Fixing With Adhesive / Bonding Material Of Insulation Rubber Mats On The Floor Of The Pump House, Covering Area Around Electro-Mechanical Machinery For Safeguarding The Life & Limb Of The Workmen . Rest Details / Specification As Per Clause 55Of Annexure C Of Sbd 64 Tool Kit For Maintenance: -The Tool Kit For Maintenance As Per Detailed Specification In Clause 56 Of Annexure C Of Sbd 65 Providing Of Good Quality Conveinence And Utility Items As Per Details In Clause57 Of Annexure C Of Sbd 66 Fabricationof6’ X 6’ Angle Iron Bedfor Operators. Rest Details / Specification As Per Clause 58 Of Annexure C Of Sbd 67 Providing And Fitting Of 19 Mm Thick Multilayered Ply Sheet Of Size 6 X 3 Feet , 2 Nos. Rest Details / Specification As Per Clause 59 Of Annexure C Of Sbd 68 Providing Of Solar / Electrical Lantern Chargeable On Both Solar & Electrical 220V Supply.Rest Details / Specification As Per Clause 60 Of Annexure C Of Sbd 69 Providing Of Bamboo Ladder 18 Feet Long With 15 Feet Long Link Rods And Ht Gloves Pair ( 01 Each ) Rest Details / Specification As Per Clause 61 Of Annexure C Of Sbd 70 Providing Of 1 Kw Heat Convector For Operators For Winter Season.Rest Details / Specification As Per Clause 62 Of Annexure C Of Sbd 71 Providing And Fitting Of 01 No. Led ( Scroll Type ) Sign Board Fabricated Out Of Stainless Steel And Metalrest Of Deatils / Technical Specification Are As Per Clause 63 Of Annexure C Of Sbd 72 Providing And Fitting Of 01 No. Angle Iron / Sheet Metal Board Duly Painted Showing Various Specifications Of The Mechanical And Electrical Equipments Installed At Site. The Legs Are To Be Grouted In Cement Concrete.Rest Of Deatils / Technical Specification Are As Per Clause 64 Of Annexure C Of Sbd 73 Providing Corrugated G.S Sheet Roofing Including Vertical / Curved Surface Fixed With Polymer Coated J Or L Hooks , Bolts And Nuts For Dg Set And Overhead Gantryrest Of Deatils / Technical Specification Are As Per Clause 68 Of Annexure C Of Sbd 74 Stage 2Nd 75 Providing, Fitting, Installation, Testing And Commissioning Of Hz Pumping Unit Of Approved Make Withfollowing Specifications: At Stage 2Nddischarge Of The Pump = 14000 Gph Dynamic Head = 40 M , With Head Range 25-50Speed = 1450 Rpmworking Voltage = 380 ± 15 V, 03 Phaserating = Corresponding To The Head And Discharge Not Less Than 20 Hp.Rest Of Specification / Details Are As Per Clause 5 Of Annexure C Of Sbd 76 Providing / Supplying And Fitting Ofg.I Flanged Rising Main At Site. The Pipe Shall Be Hot Dip Galvanized, Class-C Confirming To Is 1239. The Job Includes Providing And Fitting Of M.S Flanges Conforming To Bis 6392 / 1997 Table 17 ( Rating Pn16 ) For Y Junction And Washoutsize: 150Class:C ( Heavy ) Rest Of Specification As Per Clause 8 Of Annexure C Of Sbd 77 Cutting Of Hot Dip Galvanized Gi , C-Class Pipe Acoss The Section By Dint Of Pipe Cutter / Gas Cutter. The Job Includes Providing And Welding Of M.S. Flanges To The Two Ends Of Pipe. The Thickness Of Flange Shall Conform To Is 6392 Part 1St Table-17Dia: 150`Rest Of Specification As Per Clause 11 Of Annexure C Of Sbd 78 Providing And Fitting Of, Ductile Iron Double Flanged, Non-Rising Spindle Soft Seatedglandless Gate / Sluice Valves As Per Is14846 For Regulating The Water Supply Outside The Pumping Units .Size: Dn150pn:1.6 / 16 Rest Of Specification / Details Areas Per Clause 12 Of Annexure C Of Sbd 79 Providing And Fitting Ofductile Iron Double Flanged, Slanted Seatswing Check Valve ( Nrv ) As Per Is 5312. Size: 150Mmpn: 1.6 / 16Rest Of Specification / Details Areas Per Clause 13 Of Annexure C Of Sbd 80 Providing And Fitting Of 150 Mm Dia Flanged Flanged Bends / Elbolw To Delivery Mainfold And Washout, Including Nuts And Bolts And Rubber Gaskets As Per Requirement.Rest Of Specification / Details Areas Per Clause 15 Of Annexure C Of Sbd 81 Providing And Fitting Of Flanged Washout Tee 150 Mm , Including Nuts, Bolts And Gasket As Per Site Requirement.Rest Of Specification / Details Areas Per Clause 09 Of Annexure C Of Sbd 82 Providing / Supplying And Fitting Ofg.I Flanged Pipe At Site. The Pipe Shall Be Hot Dip Galvanized, Class-C Confirming To Is 1239. The Job Includes Providing And Fitting Of M.S Flanges Conforming To Bis 6392 / 1997 Table 17 ( Rating Pn16 ) For Suctionsize: 100Class:C ( Heavy ) Rest Of Specification As Per Clause 8 Of Annexure C Of Sbd 83 Cutting Of Hot Dip Galvanized Gi , C-Class Pipe Acoss The Section By Dint Of Pipe Cutter / Gas Cutter. The Job Includes Providing And Welding Of M.S. Flanges To The Two Ends Of Pipe. The Thickness Of Flange Shall Conform To Is 6392 Part 1St Table-17Dia: 100`Rest Of Specification As Per Clause 11 Of Annexure C Of Sbd 84 Providing And Fitting Of 100 Mm Dia Flanged Flanged Bends / Elbolw To Suction Side / At Site, Including Nuts And Bolts And Rubber Gaskets As Per Requirement.Rest Of Specification / Details Areas Per Clause 15 Of Annexure C Of Sbd 85 Providing And Fitting Ofductile Iron Double Flanged, Slanted Seatswing Check Valve ( Nrv ) As Per Is 5312. Size: 100Mmpn: 1.6 / 16Rest Of Specification / Details Areas Per Clause 13 Of Annexure C Of Sbd 86 Supply Installation , Testing And Commissioning Of Level Ii Ht Transfromercapacity: 100 Kvarest Of Specification / Details Areas Per Clause 26 Of Annexure C Of Sbd 87 9 M Long St-410 Sp33 Polerest Details As Per Clause 32 Of Annexure C Of Sbd 88 Cement Bottoming 1:2:4 Mix As Per Rec Standards 0.5 Cum / Pole 89 G.I V Cross With Top Bracket Including Clamps Rest Details As Per Clause 32 Of Annexure C Of Sbd 90 11 Kva Polymeric Insulators12 Kv , 5Kn , Lighting Impulse 75 Kv Positive And 80 Kv Negative With Creepage Distance 320Mmrest Details As Per Clause 31 Of Annexure C Of Sbd 91 Galvanized Nuts And Bolts ( 1Kg / Pole ) Rest Details As Per Clause 33 Of Annexure C Of Sbd 92 Danger Plate With Clampsrest Details As Per Clause 34 Of Annexure C Of Sbd 93 Anti Climbing Device With Clampsrest Details As Per Clause 35 Of Annexure C Of Sbd 94 Earthing Complete By Gi Pipe 40 Mm Or Gi Rod 20 Mm 2.5 Mtr Long Through Gi Strip 95 Red Oxide Coating Rest Details As Per Clause 37 Of Annexure C Of Sbd 96 Alumunium Paint Coating Rest Details As Per Clause 38 Of Annexure C Of Sbd 97 Stone Pad ( 300Mm X300mm X75mm ) Rest Details As Per Clauseof Annexure C Of Sbd 98 Pg Clamps Fo 50 Sqmm Acsr Conductor 99 Acsr Conductor 50 Sqmmrest Details As Per Clause 39 Of Annexure C Of Sbd 100 Gi Channel / Angle / Flat Of Sizes Including Clamps 101 11 Kva Go , Ab Switch 3 Phase, 3 Pole, 200 A, Vertical Typerest Details As Per Clause 28 Of Annexure C Of Sbd 102 11 Kv Polymeric Composite Disc Insulator 12 Kv, Min Failing Load 45Kn, Lighting Impulse 75Kv Positive And 80 Kv Negative, Creepage Distance 320Mm 103 Gapless Surge Arrrestor 9Kv, 10 Ka , La With Polymer Housing, Stn Typerest Details As Per Clause 30 Of Annexure C Of Sbd 104 50 Sq Mm ( 2 Ckt ) 1.1 Kv Grade, Pvc Insulated Stranded Conductor Frls Type 105 Earthing Of Substation- Rest Details As Per Clause 48 Of Annexure C Of Sbd 106 Lt Distribution Box For 100 Kva Dtr With 4 Pole Mccb For Incomer & SfuS For Outgoing Circuitsrest Details As Per Clause 42 Of Annexure C Of Sbd 107 Galvanised Stay Set With 50X8mm Stay Clam, Guy Insulators ( 2NoS ) , Anchor Plate ( 200X200x6mm ) , Nuts And Bolts, 2 Nos; Turn-Buckles, 1.8M Long, 16Mm Dia Meter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Completerest Details As Per Clause 36 Of Annexure C Of Sbd 108 Wedge Connectors / Pg Clampsrest Details As Per Clause 36 Of Annexure C Of Sbd 109 Providing, Installation, Testing And Commissioning Of Outdoor Type Ht Trivectometer As Per Iee Rule. Job Includes Grouting Of Legs In Cement Concrete As Per Site Requirement. All Cabling, Earthing And Allied Accessories Required To Be Provided By The Firm. Moreover Firm Responsible For Completing All Sealing Of Pdddepartment And Testing On Load And Noload At Site 110 Sundry Items Like Alumunium Lugs , Jumprs, Binding Tape 111 35 Sq Mm Ab ( Ht ) Cable ( 3X35+1X70 Sqmm ) Xlpe ( 11 Kv , 3C+Earth ) Rest Details As Per Clause 41 Of Annexure C Of Sbd 112 Heat Shrinkable Outdoor Cable Termination Kitrest Details As Per Clause 73 Of Annexure C Of Sbd 113 Providing & Fitting Of35 Sq Mm Single Core Copper Conductor ( Flexible ) Pvc Insulated Heavy Duty Industrial Cables ( Unsheathed ) , 1100 Volts Conforming To Is: 694- For Connecting Motors From Panel , Stabilizers In Rubber Conduit . Job Includes Providing& Laying Of Flexible Conduit For Cu Cable With Lugs As Per Requirement Heat Shrinkable Outdoor Cable Termination Kitrest Details As Per Clause 73 Of Annexure C Of Sbd 114 Providing, Installation , Testing Of Power Service Cablefor Workingvoltage Up To And Including 1100 Volts; 70 Sq Mm Armored Aluminum 3.5 Core Cable As Service Line From Output Terminals Of Ht / Lt Transformerto Cubical Panel. Cost Includes Laying Of Cable In Trenches In Pvc Conduit Where Ever Itis To Be Laid Underground As Per Site Requirement Included Is Termination Of Ends With Suitable Aluminum Tube Terminals Dully Crimpled & Taped. Rest Specifications As Per Clause 68 Of Annexure C Of Sbd 115 Providing, Installation, Testing And Commissioning Of 75 Kva Voltage Stabilizer Rest Details & Specification As Per Clause 44 Of Annexure C Of Sbd 116 Fabrication Providing And Fitting Of 3 Phase Modular Control Panel. The Technical Details / Ratings Of Various Components Of Modular Control Panel Are Given Below B. Main Circuit Breaker = 250 Ac. Changeover Switch = 200 Ad. Motor Breakup Protectionmccb= 160 Ae. Fasdstarter - 2 Units With Rating Line Contactor _Ac3 90 A , Delta Contactor- Ac3 90 Astar Contractor- Ac3 70Atimer- Star Delta Electronicthermal Overload Relay- With Relay Range 20-50 Direct / Ct Operated Suitable-Rangeaux Coil Voltage Wide Band Fitted With Seperate Stabilization Unit Min 1Kw Aux Wiringf ) . Auxillary Mccb =63 Ampwith S.C. Breaking Capacity Of36kag ) . Motor Protection Relay Suitablei ) M-Power Module For Mobile Starter & Earth Fault Relay J ) Water Level Controller Rest Of Deatils / Technical Specification Are As Per Clause 43 Ofannexure C Of Sbd 117 Providing, Installation And Testing Ofheavy Duty Manual Type Triple Spur Gear Chainpulley Block Along With Monorail Geared Travelling Trolley Having Followingfeaturesmake = Reputed Make Capacity = 3 Ton ( P ) No. Of Load Chain Falls = 2 Or Above Min. Height Of Lift = 6 Mrest Details / Specification As Per Clause 24 Of Annexure C Of Sbd 118 Illumination Of Premises:Providing And Erection Of 9 Mtr Long Hot Dip Galvanized Octagonal Pole Rest Of Deatils / Technical Specification Are As Per Clause 50 Ofannexure C Of Sbd 119 Providing, Installation, Testing And Commissioning Of Area Lighting 120 Watt Led ( Street Light Type ) On Top Of Octagonal Pole , Including Mcb Fiited In Box 10Arest Details / Specification As Per Clause 51 Of Annexure C Of Sbd 120 Providing And Installation Of Junction Box With Dp 32Amp Mcb To Serve As Amin Switch For Led Lighting Including Complete Wiring Min 20-30 M From Panel Board.Rest Details / Specification As Per Clause 52 Of Annexure C Of Sbd 121 Providing, Installation And Testing Of 2Kva Fully Automatic Voltage Stabilizer , Including Wiringrest Details / Specification As Per Clause 53 Of Annexure C Of Sbd 122 Providing & Fitting Oflighting Points For ( Machine Room , Operators Room, ) As Per Site Requirement In 1.5 Mm² Multistranded Single Core 1100 Volts, Pvc Insulatedcopper Conductor Through Pvcconduit Pipe By Way, Switches, Socket Modules , Regulators , Indicators, 08 / 10 Watt Led Lamps Surface Light Make. .Included Is Cost On Account Of Modular Switch Boards With The Wooden Frames As Per Site Requirements 123 Providing Fitting Of Heating Points In 2.5Mm² Multistranded Single Core 1100 Volts, Pvc Insulated Copper Conductor Through Pvc Conduit By Way Of P / F Of 15 Amp Switches, 6 Pin Socketon Modularfittingas Per Site Requirements. Heating Points Are To Be Connected From Main Control Panel. All Accessories Required Is To Be Provided By The Firm 124 Providing And Fitting Of 9” X 9”Exhaust Fan With Complete Wiring In 1.5 Mm Cu Wire Through Conduit And 6 A Modular Controlcomplete Job. Make Providing And Fitting Of 9” X 9”Exhaust Fan With Complete Wiring In 1.5 Mm Cu Wire Through Conduit And 6 A Modular Controlcomplete Job. 125 Providing, Fitting Of Distribution Board Of Reputed Make 4 Way S P N Single Door Powder Coated Sheet Steel Enclosure For Surface Mounting Fitted With Bus Bar, Din Channel, Neutral Link And Incoming Contact. The Above Db Is To Be Provided / Fitted With Double Pole 40 Amp Mcb For Main. 32 A For Heating Circuit & Rest 3 Of 16 / 6 Amps Each For Premises Luminary, Auxiliary Circuit Of Reputed Make. Further Job Includes Providing / Fitting 4 Mm² Multistranded Single Core 1100 Volts, Pvc Insulated Copper Conductor Through Pvc Conduit As Service Line From Main Panel As Per Site Requirements. Connections Should Be Made In Such A Way Lighting Pointsis To Be Connected Via Automatic Transformer By Way Of P / F Switch Socket Arrangement With Allied Fixtures & And Heating Points To Main Panel. Job Includes Dismantling Of Existing Damaged Conduit , Wires, Conduit And Cleaning The Surface Properly 126 Earthing Of Panel Boad, Stabilizer, Motors, Heating Points, Lighting Points, D.G Setsrest Details As Per Clause 48 Of Annexure C Of Sbd 127 Painting On Steel Structure / Pipe With Synthetic Enamel Paint Of Approved Brand And Maufacturer Of Required Colour To Give An Even Shade On New Work ( Two Or More Coats ) Including A Coat Of Approved Steel Primer But Excluding A Coat Of Mordant Solution. ( Ref 13.61 ) Schedule2021 128 Providing , Installation, Testing And Commissioning Of 415+-10 V ( Out Put ) , 3 Phase Dg Set Of Specification Of Approved Make As Per Latest Guide Linecapacity =40 Kvarest Details / Specifications Are As Per Clause 66 Of Annexure C Of Sbd 129 Providing, Installation , Testing Of Power Service Cablefor Workingvoltage Up To And Including 1100 Volts; 70 Sq Mm Armored Aluminum 3.5 Core Cable As Service Line From Output Terminals Of Ht / Lt Transformerto Cubical Panel. Cost Includes Laying Of Cable In Trenches In Pvc Conduit Where Ever Itis To Be Laid Underground As Per Site Requirement Included Is Termination Of Ends With Suitable Aluminum Tube Terminals Dully Crimpled & Taped. Rest Specifications As Per Clause 67 Of Annexure C Of Sbd 130 Fabrication, Providing, Fitting Of Base Framefor Pumping Units , Covering Of Holes , Fabrication Of Gantry, Ladder , Dg Set Covering, Ht / Lt Transformer Bed With Gantry Fabricated Out Of Ismc / Ismb / Isa / Bars / Ms Pipe / Ms Plain-Chequrred Sheets. Including Making Of Holes In Concrete, Including Metal Primer 1 Coat And Two Coats Of Approved Shade . The Works Is To Be Executed As Per Site Requirement And As Per Dimentions Of Pumping Unit And As Per Directions Of Site Engineer.Rest Of Specification / Details Are As Per Clause 21 Of Annexure C Of Sbd 131 Providing And Laying In Position Cement Concrete Of Specified Grade Including Curing But Excluding The Cost Of Centring And Shuttering. All Work Upto Plinth Level 1:2:4 With Stone Aggregrate 20 Mm Nominal Size. For Dg Set Foundatioin / Concrete Beds For Rising-Main As Per Requirement 132 Centering And Shuttering Including Strutting, Propping Etc And Removal Of Form Work For Foundation, Footing , Base 133 Earth Work In Excavation By Manualmeans In Trenches For Foundations, Drains , Pipes , Cables Etc ( Not Exceeding 1.5 M In Width ) Andramming Of Bottoms Lift 1.5 M , Including Getting Out Excavated Earth And Disposal Of Surplus Exacavated Earth As Directed ( All Kinds Of Soil ) ( 2.81 Schedule ) 134 Providing And Laying Of Soling Stone 135 Cement Plaster In Find Sand In 1:3 Mix Finished With A Coat Of Neat Cement And Curing Complete 18 Mm Thick. ( S-11.8 ) 136 Supply, Installation, Testing & Commissioning Of 1000Va Full Sine Wave Power Inverter With 12V, 180Ah Tubular Inverter Batteryrest Details / Specification As Per Clause 54 Of Annexure C Of Sbd 137 Providing, Laying & Fixing With Adhesive / Bonding Material Of Insulation Rubber Mats On The Floor Of The Pump House, Covering Area Around Electro-Mechanical Machinery For Safeguarding The Life & Limb Of The Workmen . Rest Details / Specification As Per Clause 55Of Annexure C Of Sbd 138 Tool Kit For Maintenance: -The Tool Kit For Maintenance As Per Detailed Specification In Clause 56 Of Annexure C Of Sbd 139 Providing Of Good Quality Conveinence And Utility Items As Per Details In Clause57 Of Annexure C Of Sbd 140 Fabricationof6’ X 6’ Angle Iron Bedfor Operators. Rest Details / Specification As Per Clause 58 Of Annexure C Of Sbd 141 Providing And Fitting Of 19 Mm Thick Multilayered Ply Sheet Of Size 6 X 3 Feet , 2 Nos. Rest Details / Specification As Per Clause 59 Of Annexure C Of Sbd 142 Providing Of Solar / Electrical Lantern Chargeable On Both Solar & Electrical 220V Supply.Rest Details / Specification As Per Clause 60 Of Annexure C Of Sbd 143 Providing Of Bamboo Ladder 18 Feet Long With 15 Feet Long Link Rods And Ht Gloves Pair ( 01 Each ) Rest Details / Specification As Per Clause 61 Of Annexure C Of Sbd 144 Providing Of 1 Kw Heat Convector For Operators For Winter Season.Rest Details / Specification As Per Clause 62 Of Annexure C Of Sbd 145 Providing And Fitting Of 01 No. Led ( Scroll Type ) Sign Board Fabricated Out Of Stainless Steel And Metalrest Of Deatils / Technical Specification Are As Per Clause 63 Of Annexure C Of Sbd 146 Providing And Fitting Of 01 No. Angle Iron / Sheet Metal Board Duly Painted Showing Various Specifications Of The Mechanical And Electrical Equipments Installed At Site. The Legs Are To Be Grouted In Cement Concrete.Rest Of Deatils / Technical Specification Are As Per Clause 64 Of Annexure C Of Sbd 147 Providing Corrugated G.S Sheet Roofing Including Vertical / Curved Surface Fixed With Polymer Coated J Or L Hooks , Bolts And Nuts For Dg Set And Overhead Gantryrest Of Deatils / Technical Specification Are As Per Clause 68 Of Annexure C Of Sbd 148 Intake Sump Cum Pump House ( Sinking Well Type ) At Nallah Pohru At Wadoora ( Civil Works ) 149 Earth Work In Excavation By Mechanical Means Over Areas ( Exceeding 30Cm And Up [ To 1.5Mtr In Depth, 1.5Mtr In Width As Well As 10 Sqm On Plan ) Including Disposal Of Excavated Earth Upto 50M From Cutting Edge Disposal Earth To Be Levelled And Neatly Dressed .All Kinds Of Soil 150 Filling Available Excavated Earth ( Excluding Rock ) In Trenches, Plinth, Sides Of Foundation Etc Layers Not Exceeding 20Cm In Depth, Consolidating Each Deposited Layer By Ramming And Watering Lead Upto 50M And Lift Upto 1.5M 151 Providing And Laying Of Dry Stone Solling Tightly Hand Packed. 152 Providing And Laying In Position Specified Grade Of Cement Concrete In 1:4:8 Nominal Mix. 153 Providing And Laying In Position Specified Grade Of Reinforced Cement Concrete Excluding The Cost Of Centering, Shuttering, Finishing And Reinforcement. All Work Upto Plinth Level. 1 : 1.5 : 3 ( 1 Cement : 1.5 Coarse Sand : 3 Graded Stone Aggregate 20Mm Nominal Size ) 154 Reinforced Cement Concrete Work In Chimneys, Shafts Upto Floor Five Level Including Curing Complete But Excluding The Cost Of Centering, Shuttering, Finishing And Reinforcement With:5.6.1 1:1½:3 ( 1 Cement : 1½ Coarse Sand : 3 Graded Stone Aggregate 20 Mm Nominal Size ) 155 Reinforced Cement Concrete Work In Beams, Suspended Floors, Roofs Having Slope Upto 15°, Landings, Balconies, Shelves, Chajjas, Lintels, Bands, Plain Window Sills, Staircases And Spiral Stair Cases Upto Five Level Including Curing But Excluding The Cost Of Centring, Shuttering, Finishing And Reinforcement With 5.3.1 1:1½:3 ( 1 Cement : 1½ Coarse Sand : 3 Graded Stone Aggregate 20 Mm Nominal Size ) 156 Reinforcement To Rcc Works Including Bending , Binding , Cuttingstraighteningand Placing In Position Complete Tmt Bars. 157 Structural Steel Work In Built Up Sections, Trusses And Framed Work, Including Cutting, Hoisting, Fixing In Position And Applying A Priming Coat Of Approved Steel Primer All Complete.10.2.2 Welded 158 Steel Work Welded In Built Up Sections / Framed Work, Including Cutting, Hoisting, Fixing In Position And Applying A Priming Coat Of Approved Steel Primer Using Structural Steel Etc. As Required.10.25.1 In Stringers, Treads, Landings Etc. Of Stair Cases, Including Use Ofchequered Plate, Railings Wherever Required, All Complete.Similar Works. 159 Centering And Shuttering Including Straightening Propping Etc, And Removal Of Form Work For: Foundations, Footing, Bases Of Columns Etc For Mass Concrete 160 Centering And Shuttering Including Straightening Propping Etc, And Removal Of Form Work For: Walls ( Any Thickness ) Including Attached Pilasters, Buttresses, Plinth And String Courses 161 Centering And Shuttering Including Straightening Propping Etc, And Removal Of Form Work For: Lintels, Beams, Plinth Beams, Girders, Bressumers And Cantilevers 162 Centering And Shuttering Including Straightening Propping Etc, And Removal Of Form Work For: Suspended Floors 163 Extra For Shuttering In Circuilar Work ( 20 % Of Respective Centring And Shuttering Items ) :Foundation 164 Extra For Shuttering In Circuilar Work ( 20 % Of Respective Centring And Shuttering Items ) : Walls ( Any Thickness ) Including Attached Pilasters, Buttresses, Plinth And String Courses 165 15Mm Thick Cement Plaster Finished With Floating Coat Of Cement Of Mix 1 : 3 ( 1 Cement : 3 Fine Sand ) 166 Supply , Fabrication And Fixing In Position Ms Edge Cutter With Proper Anchorage Incl All Welding And As Per Directions Of Engineer Incharge 167 Sinking Of Well Through All Type Of Soil Complete As Per Specificatons And Directions Of Engineer Incharge 168 Pumping Out Water Caused By Springs, Tidal Or River Seepage, Broken Water Mains Or Drains And The Like ( Tobe Paid As Per Actual ) 169 Providing, Placing Earth Filled Bags Incl Excavating Earth From Borrow Pits , Filing Of Bags, Sewing, Stitching , Stacking And Placing In Position As Per The Diractions Of Engineer Incharge Incl All Sorts Of Carriagecomplete Job . The Job Includes Demolishing Of Same After Successful Commissioning Of The Job 170 Providing And Fixing Tie Bolt, Spring Coil And Plastic Cone In Wall Shuttering Complete As Per The Direction Of Engineer-In-Charge 171 20 Mm Dia And 350 Mm Length 172 Brick Masonary With Common Burnt Clay F.P.S ( Non-Modualar ) Bricks Of Class Designation 75 In Foundation And Plinth In : Cement Mortar 1 : 4 ( 1 Cement : 4 Coarse Sand ) 173 Extra For Brick Work In Super Structure Above Plinth Level Upto Floor V Level ( By Manual Means ) 174 Providing Corrugated G.S Sheet Roofing Including Vertical / Curved Surface Fixed With Polymer Coated J Or L Hooks, Bolts And Nuts 8Mm Diameter With Bitumen And G.I Limpet Washers Or With G.I Limpet Washers Filled With White Lead And Including A Coat Of Approved Steel Primer And Two Coats Of Approved Paint On Overlapping Of Sheets Complete ( Upto Any Pitch In Horizontal / Vertical Or Curved Surface ) Excluding The Cost Of Purlins, Rafters And Trusses And Including Cutting To Size And Shape Wherever Required. 0.50Mm Thick With Zinc Coating Not Less Than 275Gm / M2 175 Providing And Fixing Hand Rail Of Approved Size By Welding Etc To Steel Ladder Railing, Balcony Railing And Stair Case Railing And Similar Work Including Applying A Priming Coat Of Approved Steel Primer. M.S Tube ( Medium ) 40Mmm Nominal Bore 176 Finishing Walls With Water Proofing Cement Paint Of Approved Brand And Manufactured Of Required Shade To Give An Even Shade New Work ( Two Or More Coats ) Applied @3.84Kg / 10Sqm 177 Providing Ridges Or Hips Of Width 60Cm Over All Width Plain G.S Sheets With Polymer Coated J Or L Hooks, Bolts And Nuts 80Mm Dia G.I Limpet And Bitumen Washers Complete Job 178 Providing And Fixing At Site Eaves Boarding Of 200Mmwide Colouredncluding Cost Of Holders, Angle Supports Complete Job 179 Providing And Fixing Of 2Mm Ms Sheetsoffit Boardingincl Supports Etc Complete Job 180 Supplying And Fixing Rolling Shutters Of Approved Make, Made Of Required Size M.S Laths Interlocked Together Through Their Entire Length And Jointed Together At The End By End Locks Mounted On Specially Designed Pipe Shaft With Brackets, Side Guides And Arrangements For Inside And Outside Locking With Push And Pull Operation Complete Including The Cost Of Providing And Fixing Necessary 27.50Cm Long Wire Springs Manufacture From High Tensile Steel Wire Of Adequate Strength Confirming To Is 4454 Part 1 And M.S Top Cover Of Required Thickness For Rolling Shutters. 80X1.25Mm M.S Laths With 1.25Mm Thick Top Cover 181 Providing And Fixing Ball Bearing For Rolling Shutters 182 Providing Wood Work In Frames Of Doors, Windows, Clerestory Windows And Other Frames, Wrought Framed And Fixed In Position With Hold Fast Lugs Or With Dash Fasteners Of Required Dia And Length ( Hold Fast Lugs Or With Dash Fasteners Shall Be Paid For Separately ) : Second Class Kail Wood 183 Providing And Fixing Glazed Shutters For Doors, Windows And Clerestory Windows Using 10Kg / Sqm ( 4Mm Thick ) Float Glass Panes Including Isi Marked M.S Pressed Butt Hinges Bright Finished Of Required Size With Necessary Screws. Second Class Kail Wood 184 Providing And Fixing 30Mm Thick Wire Gauze Shutters Using Galvanized M.S Wire Gauze Of Average Width For Aperture 1.4Mm In Both Direction With Wire Of Dia 0.63Mm For Doors, Windows And Clerestory Windows With Hinges And Necessary Screws. Isi Marked M.S Pressed Bright Finished Butt Hinges With Necessary Screws Of Required Size. Second Class Kail Wood 185 Providing And Fixing Of 5Mm Thick Glass Sheets In Windows Incld. Cost Of All Complete Job As Directed By Site Engineer 186 Painting With Synthetic Enamel Paint Of Approved Brand And Manufacture To Give An Even Shade. Two Or More Coats On New Work Over An Under Coat Ofsuitable Shade With Ordinary Paint Of Approved Brand And Manufacture. 187 Providing And Fixing 12Mm Thick Plyboard For Covering Yhe Ceiling Area Incl C / O Frames, Supports , Battens Inclallosorts Of Screws Etc Complete Job 188 Providing And Fixing Aluminium Handles Isi Marked Anodized ( Anodic Coating Not Less Than Grade Ac 10 As Per Is : 1868 ) Transparent Or Dyed To Required Colour And Shade With Necessary Screws Etc Complete 100 Mm 189 Providing And Fixing Aluminium Tower Bolts Isi Marked Anodized ( Anodic Coating Not Less Than Grade Ac 10 As Per Is : 1868 ) Transparent Or Dyed To Required Colour Or Shade With Necessary Screws Etc Complete 100 X 10Mm 190 Carriage Of Materials By Mechanical Transport From Source To Actual Site Of Work Including Loading, Unloading And Stacking Of Material: Cemenet / Steel For Avg. Lead 12Kms 191 Carriage Of Materials By Mechanical Transport From Source To Actual Site Of Work Including Loading, Unloading And Stacking Of Material: Sand For Avg. Lead 20Kms 192 Carriage Of Materials By Mechanical Transport From Source To Actual Site Of Work Including Loading, Unloading And Stacking Of Material: Stone Agg. 40Mmfor Avg. Lead 20Kms 193 Carriage Of Materials By Mechanical Transport From Source To Actual Site Of Work Including Loading, Unloading And Stacking Of Material: Stone Agg. 20Mmfor Avg. Lead 20Kms 194 Carriage Of Materials By Mechanical Transport From Source To Actual Site Of Work Including Loading, Unloading And Stacking Of Material: Stone Soling For Avg. Lead 10Kms 195 Carriage Of Materials By Mechanical Transport From Source To Actual Site Of Work Including Loading, Unloading And Stacking Of Material: Bricks For Avg. Lead 75Kms