| 1 | Contract Details |
| 2 | Disconnecting, dismantling,and taking out of unserviceable Indicator lamp assembly LED(RYB) type from HT/ LT panel/ LT distribution panel and supply and fixing new Indicator lamp assembly LED type including making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 3 | Disconnecting, dismantling,and taking out of unserviceable start push button( green colour) assembly LED type fromStarter panel/ LT distribution panel and supply and fixing new push buttonassembly LED(green colur) type including making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 4 | Disconnecting, dismantling,and taking out of unserviceable stop push button( Red colour) assembly LED type fromStarter/ LT distribution panel and supply and fixing new push buttonassembly LED(Red colur) type including making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 5 | Disconnecting, dismantling,and taking out of unserviceable thermal over load relay 3 pole assembly (8.9 A to 13.5 A)fromStarter panel / LT distribution panel and supply and fixing newthermal over load relay 3 pole assemblyincluding making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 6 | Disconnecting, dismantling,and taking out of unserviceable thermal over load relay 3 pole assembly (13.2 A to 20 A)fromStarter panel / LT distribution panel and supply and fixing newthermal over load relay 3 pole assemblyincluding making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 7 | Disconnecting, dismantling,and taking out of unserviceablephase preventor (SPP) for starterassembly fromStarter panel / LT distribution panel and supply and fixing new Single phase preventor (SPP) assemblyincluding making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 8 | Disconnecting, dismantling,and taking out of unserviceable Timer assembly fromStarter panel / LT distribution panel and supply and fixing new timer assemblyincluding making connections withsingle core PVC insulated cable and necessary thimbles nut bolts etc complete all as specified and directed. |
| 9 | Disconnecting, dismantling,and taking out of unserviceable MCCB 250 A any type any descriptionand Supply and fixed new MCCB Triple pole neutral TPN/ 4P, 250 Amps 415 volts, 50 Hz having breaking capacity 35 KA , with fixed thermal and fixed magnetic setting and testing Complete all as specified and directed. |
| 10 | Disconnecting, dismantling,and taking out of unserviceable MCCB 160 A any type any descriptionand Supply and fixed new MCCB Triple pole, 160 Amps 415 volts, 50 Hz having breaking capacity 36 KA , with fixed thermal and fixed magnetic setting and testing Complete all as specified and directed. |
| 11 | Disconnecting, dismantling,and taking out of unserviceable MCCB 100 A any type any descriptionand Supply and fixed new MCCB Triple pole, 100 Amps 415 volts, 50 Hz having breaking capacity 25 KA , with fixed thermal and fixed magnetic setting and testing Complete all as specified and directed. |
| 12 | Disconnecting, dismantling,and taking out of unserviceable MCCB 63 A any type any descriptionand Supply and fixed new MCCB Triple pole,63 Amps 415 volts, 50 Hz having breaking capacity 16 KA , with fixed thermal and fixed magnetic setting and testing Complete all as specified and directed. |
| 13 | Labour only for checking the serviceablity of the different spares/components/parts of security light/ Garden light/Pole light/ Security light on bldg and pole/Post top lantern light fittings (LED fittings , flood light fittings e.t.c , any wattage/capacity) of any description from skilled electrician and replacement of unservicable/damaged/loose wiring/broken parts either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in position connecting to electric supply and its testing on installation complete all as specified and directed. NOTE:- (i) Replacement of parts i.e lamps, led blub ,Holder, covers, driver, etc for Led Flood light fittings/ led securityany wattage & capacity, if any required at site, shall be measured and paid for separately under appropriate item of Schedule `A\" as ‘supply only’ (i) Necessary T&P i.e. ladder, tools etc required for checking and making the light fittings in serviceable conditions, its fixing in position and testing shall be arranged by the contractor at his own cost for checking and fixing of street light fittings/security light fittings of any description on poles / on walls / on pillars etc i.e. in any position at site. |
| 14 | S&F Lamp holder, PVC/Polycarbonate type with cord grip cap suitable for garden light/pole light fittings. |
| 15 | S&F LEDdriver for Ledfittings from 8 watt to 24 watt 300 mA. |
| 16 | S&F LEDdriver for Ledfittings from 30 watt to 70 watt for street/ security light/flood light. |
| 17 | Disconnecting and taking out existing light fitting of any description and in any position on walls including rusted brackets complete and Supply, fixing & testing 45 W LED street light fitting mounting type made out of one piece in pressure die-cast aluminium, alloy powder coated housing enclosed with glass cover in frame fitted luminaries complete with all accessories. The fitting shall IP 65 protection, duly prewired suitable for and including mounting bracket made of MS Angle Iron 40x40x5mm , 900mm long, bent to shape cutting,drilling of holes & welding as required & directed etc fixed/grouted on wall with fastner\"s nut,bolt washers as required and including painted with two coat of aluminium paint over a coat of red oxide primer with and including connecting the fitting to bus bar box/Main switch with using 2.5 Sqmm two single core PVC insulated and unsheathed copper conductor copper conductor cable complete all as specified and directedCat Part No: ENDURA PERL NEO 45W LED757PASYTOPC IP65 of Make Havells or equivalent model of specified make as approved by AGE. |
| 18 | Disconnecting and taking out existing light fitting of any description and in any position on walls including rusted brackets complete and Supply, fixing & testing 85 W LED high light intensity impowered color changing and monochromatic compact led projector with polorized light designmade out of one piece in pressure die-cast aluminium, alloy powder coated housing enclosed with glass cover in frame fitted luminaries complete with electronic driver and all accessories suitable for & including lamp 85 W with suitable No\"s of LEDs . The fitting shall IP 66 protection, duly prewired complete with and including connecting the fitting to bus bar box/Main switch with usingtwo core PVC insulated and unsheathed copper conductor cable complete all as specified and directed Make- Havells/L&T/Bajaj or equivalent model of specified make as approved by AGE. |
| 19 | Disconnecting and taking out existing light fitting of any description and in any position on walls including rusted brackets complete and Supply, fixing & testing 70 W LED Flood light fitting mounting type made out of one piece in pressure die-cast aluminium, alloy powder coated housing enclosed with glass cover in frame fitted luminaries complete with electronic driver and all accessories suitable for & including lamp 70 W with suitable No\"s of LEDs . The fitting shall IP 66 protection, duly prewired complete with and including connecting the fitting to bus bar box/Main switch with using 2.5 Sqmm two single core PVC insulated and unsheathed copper conductor cable complete all as specified and directedCat Part No: FL70WLED757LTG of model JETA PRO 70 of Make- Havells or equivalent model of specified make as approved by AGE. Note : GI pipe bracket and clamps if required shall be measured and paid separately. |
| 20 | Disconnecting and taking out existing light fitting of any description and in any position on walls including rusted brackets complete and Supply, fixing surface mounted LED down lighter fitting with white powder coated aluminium housing enclosed with glass cover in frame fitted luminaries complete with electronic driver and all accessories suitable for & including lamp 15 Watt duly prewired complete with and including connecting the fitting to junction box/Main switch with using suitable wiretwo core PVC insulated and unsheathed copper conductor cable/wire complete all as specified and directedCat Part No: ENDURA NEO HE DL SURFACE of model (ENDURANEOHESURFACEDLS15WLED857S) of Make- Havellsequivalent model of specified make as approved by AGE. |
| 21 | Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep in any type of soil including forming sides and bottom surface to required levels/slopes/gradients etc. complete all as specified and directed at site. |
| 22 | M&L for Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed. |
| 23 | M&L for Removal of surplus excavated soil to a distance not exceeding 50 Mtr distance and depositing as directed at a level not exceeding 1.5 mtr above starting point complete all as specified and directed. |
| 24 | Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches/ducts for cable protection complete all as specified and directed . |
| 25 | M&L for old size sub class `B` bricks, kiln burnt, as in cable protection laid flat with axis of brick perpendicular to the axis of the cable complete all as specified and directed . |
| 26 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable of size 70 Sqmm 3.5 core of any description and in any position complete and Supplying, laying, jointing & testing XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 70 Square mm,3.5 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed. |
| 27 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable of size 50 Sqmm 3.5 core of any description and in any position complete and Supplying, laying, jointing & testing XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 50 square mm, 3.5 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed. |
| 28 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable of size 25 Sqmm 4 core of any description and in any position complete and Supplying, laying, jointing & testing XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 25 square mm,3.5 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed. |
| 29 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable of size 16 Sqmm 4 core of any description and in any position complete and Supplying, laying, jointing & testing XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 16 Sq mm, 2 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed. |
| 30 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable of size 10 Sqmm 2 core of any description and in any position complete and Supplying, laying, jointing & testing XLPE insulated PVC sheathed (heavy duty) armoured cable with aluminium conductor for working voltage upto 1100 volts size 10 square mm, 4 core conforming to IS 7098 Part-I or IS 1554 Part-I. complete all as specified and directed. |
| 31 | Disconnecting and taking out old unserviceable GI pipe and Supplying, laying & jointing GItubing, 50 mm bore, light grade as in sleeving etc laid in trenches / pole post etc. complete all as specified and directed . |
| 32 | Earthing of machinary/ equipment Complete with galvanised steel earth plate electrode 600 mmx600 mmx 6mm thick burrieddirectly in groundverticallyto a depth not less than 2.25 metrebelowgroundlevelwith topedgeof theearth plate at a depth not less than 1.5 mtr belowgroundlevelearth platesurrounded from all sides by 15cmthickpacked layer ofcharcoal dust and common saltfillinginalternate layers andelectrodeconnectionby using32x6mm glavanised MS strip by meansof bolts, nuts, check nutsand washersmade of galvanised ironand thimbles and other endof theearth wire connectedto mainswitch boardprotected by galvanised iron light grade pipe 15 mm borein wall/floor/andGI Pipe 20mm borelight grade forwatering with funnel and wiremesh PCC chamber in cementconcrete 1:3:6 typeC-2 and RCC pitcover includingnecessaryexcavation andearth work in anytype ofsoil, returningslurry approved soil and disposed of surplussoilto adistancenotexceeding 50 Mtraway all as shown inelectrical plateNo 5ofSSR 2009( Part-I). |
| 33 | Supply and fixing cable lugs Aluminium of size 25 sq mm. |
| 34 | -do- but size 35 sq mm. |
| 35 | -do- but size 50 sq mm. |
| 36 | -do- but size 70 sq mm. |
| 37 | Supply and fixing cable jointing kit heat shrink type and complete acessories straight thru joint suitable for 3.5 /4 core XLPE ofsize 25 sqmm to 50 sq mm of 1.1 KV, low voltage,for indoor/ outdoor of material aluminium or copper all as specified and as directed at site by Engr-in-charge. |
| 38 | Supply and laying Rubber insulating mats for11 KV electrical safety floor coverings in areas 1 mtr x 2 mtr 2.5 mm thicksize. |
| 39 | S&F in replacement capicitor metalized poly propylene type S(MPP - S) for three phase 440 Volt 50 Hz for permissible non linear load of 15 % of capacity 25 KVAR |
| 40 | M&L for reparing of old out door LT Panels/feeder piller such as alingment of both doors , repair / replacement of locking arrangement, door hinges, welding at cracks , uprighting and fixing properly all as directed at site. |
| 41 | S&F in repalcement GI pipe bracket make of 40 mm bore light grade pipe made to shape of overall length of 1.2 mtr for fixing of street light fitting including MS clamps, nuts & bolts of required size complete all as specified and directed . |
| 42 | S&F in repair poly carbonate Sintexcable junction box (IP-66) weather proof outdoor type of size 200 mm x 200 mm x 100 mm with terminals suitable for entry of cable size 10 to 25 Sqmm including and fixing arrangement for 1 No. MCB SPN, 6 to 32 amps, 250 Volts with \"B\" curve, fixed on pole with clamp including connecting complete. Make : Sintex or equivalent |
| 43 | Material & labour for top up of transformer oil as per manufacturer specification all as specified and as directed at site requirement. |
| 44 | Material & Labour for preparation of old painted surface of steel tubular pole (09 meter long) with one coat of aluminium paint complete including marking of strip of 20 cm each (Black and white) upto 1400 mm height with enameled paints with scrubbing of old paint on the existing pole including painting the existing brackets & clamp fixed on pole by silver paint and also putnumber in polesall as specified and directed. |
| 45 | M&L for servicing of Air circuit breaker (1000 Amp) by taking out rack, measuring insulation of all wires,power cables, measuringcontinuty by meter, and meggaring all cables, greasing mechanical parts, checking allinsulators and checking all nuts /bolt. In ON/OFF position complete all as specified and directed at site. Note. All preventive measure before opening the rack should be strictly followed by the authrosied machanic in contractor supervision . |
| 46 | M&L for servicing of capacitor panel (4x25 KVAR) air blower, dusting all internal partsby machine, greasing where necessary, checking all parts , if some minor parts like nuts , bolts, washer, fuse, wire, if necessary should be replaced in the quated rate only, any other major parts if found unserviceable will be paid seprate and the fitting charges of that particular item will be quated under servicing item only. Note. All preventive measure before opening the rack should be strictly followed by the authrosied machanic in contractor supervision . |
| 47 | Supply and fix in repair TNC Switch gear to main VCB Panel after taking out the old one carefully and fix the new one as specified and as directed by Engr-in-Charge. Make- AREVA |
| 48 | Supply and fix silica gel in the transformer . |
| 49 | M&L for servicing of Vaccum circuit breaker by taking out rack, measuring insulation of all wires,power cables, measuringcontinuty by meter, and meggaring all cables, oiling/greasing mechanical parts, checking allinsulators and checking all nuts /bolt. In ON/OFF position complete all as specified and directed at site. Note. All preventive measure before opening the rack should be strictly followed by the authrosied machanic in contractor supervision . |
| 50 | S&F in repair MCB single pole, 6 to 32 Amps (`C’ series ) having current rating 10 KA complete all asspecified and directed.Make : L&Tand equivalent |
| 51 | Supply and fixing in repair 415V 10KA \"C\" curve miniature circuit breaker (MCB) ofSPN (40-63 amp) poles and current carrying capacity in the DB complete with connection testing and commissioning |
| 52 | Supply and fixing in repair 415V 10KA \"C\" curve miniature circuit breaker (MCB) TPN/4 P (16-32 amp) poles and current carrying capacity in the DB complete with connection testing and commissioning |
| 53 | S&F in repair PVC flat twin core cable 4 Sqmm complete all asspecified and directed.Make :Havells/ polycab/ L&Tand equivalent. |
| 54 | S&F in repair Solar LEDstreet light 50 watt automatic sensor for outdoor purpose ,water proof, whitein coloraluminium die cast housing with tempered glass protection including complete rewiring fixing with copper wire and connected to all acessories asspecified and directed at site .Make :Tata/ BP/ Dmak/Usha/BAJAJ |
| 55 | Note :-Tenderers may be noted that amount of credit will be deducted from the total amount arrived, at the time of Acceptance of contract. |