| 1 | Taking down copper/ aluminium point wiring (light,fan, socket or power) complete, including fixture and fittings such as switches, sockets complete removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls complete all as specified and as directed by Engr-in-charge. |
| 2 | Disconnecting and taking down carefully split /window type air conditioning unit of capacity 1.5 Ton /2 Ton, electrically/ mechanically lowering to the ground from any position and transporting to AGE E/M-II store yard for safe custody complete all as specified and as directed by Engr-in-charge. |
| 3 | Disconnecting carefully water cooler and refrigerator of any type /size electrically/ mechanically and transporting to AGE E/M-II store yard for safe custody complete all as specified and as directed by Engr-in-charge. |
| 4 | Supply, install, testing and commissioning of air cooled invertor split type air conditioner minimum 3 star rating of capacity 1.5 /1.6 ton, electric driven (230 volts, 50 Hz, single phase supply), comprising of indoor unit, wall mounted, material of construction of indoor unit ABS, outdoor unit material of cabinet GI sheet 1 mm thick, powder coated, condensor copper tubing type including copper tubing and connection cable complete between indoor and outdoor with the following specification complete all as specified and as directed by Engr-in-charge.(a) Rated cooling capacity (Min-Max) (Watts) - 5010 (1296-5158)(b) Air flow Volume (Wet CFM) (High/ Medium/ Low) - 400/318/250(c) Noise level Indoor (High/Medium/Low) dB(A) - 42.7/36.8/31.6(d) Compressor type - Inverter Rotary with 10 year warranty(e) Refrigerant type - R-32 (Eco Friendly)(f) Remote type - Cardless LCD Display |
| 5 | Supply, install, testing and commissioning of air cooled invertor split type air conditioner minimum 3 star rating of capacity 2.0 ton, electric driven (230 volts, 50 Hz, single phase supply), comprising of indoor unit, wall mounted, material of construction of indoor unit ABS, outdoor unit material of cabinet GI sheet 1 mm thick, powder coated, copper tubing condensor type including copper tubing and connection cable complete between indoor and outdoor with the following specification complete all as specified and as directed by Engr-in-charge.(a) Rated cooling capacity Watts (Min-Max) - 6350 (1772 -6624)(b) Air flow Volume (Wet CFM) (High /Medium /Low) - 576/501/399(c) Noise level Indoor (High /Medium/ Low) dB(A) - 46.63/43.7/37.7(d) Compressor type - Inverter Rotary with 10 year warranty(e) Refrigerant type - R-32 (Eco Friendly)(f) Remote type - Cardless LCD DisplayNote for Item Nos. 4 & 5: Copper cable, copper tubing of dia 1/2\" for suction line and 1/4\" discharge line including thermal insulation and other brass fitting (between indoor and out door unit minimum distance 3m and condensed water drainage pipe system is inclusive of quoted rate and more than 3m will be measured and paid separetely under relevent item of schedule. |
| 6 | Supply and fix for copper tubing of dia 1/2\" for suction line including thermal insulation and other brass fitting, fixing into wall etc., complete all as specified and as directed by Engr-in-charge. |
| 7 | Supply and fix for copper tubing of dia 1/4\" for discharge line including thermal insulation and other brass fitting, fixing into wall etc., complete all as specified and as directed by Engr-in-charge. |
| 8 | Supply and fix for powder coated iron stand for supporting the outer unit set of two of split air conditioning including all accessories required for fitting /hanging the stand into the wall complete all as specified and as directed by Engr-in-charge. |
| 9 | Supply, installation, commissioning of Energy efficient water cooler fully stainless steel, electric driven, single phase, having approx storage capacity 80 ltrs and nominal cooling capacity of 40 liters per hour with RECIP compressor working on R-134 (a) refrigerant complete all as specified and as directed by Engr-in-charge. |
| 10 | Supply, installation, commissioning of Energy efficient water cooler fully stainless steel, electric driven, single phase, having approx storage capacity 120 ltrs and nominal cooling capacity of 60 to 80 liters per hour with RECIP compressor working on R-134 (a) refrigerant complete all as specified and as directed by Engr-in-charge. |
| 11 | Supply and install Refrigerator, electric driven (Single phase) of capacity 198 Ltrs or near higher size, single door, minimum 4 star invertor direct cool working with latest Eco friendly refrigerant complete all as specified and as directed by Engr-in-charge. |
| 12 | Supply and install Refrigerator, electric driven (Single phase) of capacity 280 Ltrs or near higher size, single door, minimum 4 star invertor direct cool working with latest Eco friendly refrigerant complete all as specified and as directed by Engr-in-charge. |
| 13 | Supply and install Refrigerator, electric driven (Single phase) of capacity 310 Ltrs or near higher size, double door, minimum 4 star frost free, double door convertible refrigerator working with latest Eco friendly refrigerant complete all as specified and as directed by Engr-in-charge. |
| 14 | Material and labour for point wiring with1100 Volts, grade 2.5 Sqmm (nominal area) wire /cable for phase and neutral for 3 Pin 5, 3 pin 15 Amp socket on independent board including PVC caping casing (medium duty) 20mm complete with all accessories with concealed pressed iron/ steel suction box of thickness 1.2mm for mounting of switch socket combination with 3 mm thick plastic laminated sheet as top cover including one 2.5 sqmm PVC insulated unsheathed multi stranded copper conductor cable, FRLS 1100 volts grade as earth continuity conductor upto common earth and connected to earth dolly complete all as specified and as directed by Engr-in-charge. |
| 15 | Supply and fix for switch socket combination 2 in 1, 3 pin, 6 and 16 Amp flush type universal SP 250 Volt AC complete all as specified and as directed by Engr-in-charge. |
| 16 | Supply and fix in replacement switch socket combination 2 in 1, 3 pin, 6 and 16 Amp flush type universal SP 250 Volt AC complete all as specified and as directed by Engr-in-charge. |
| 17 | Material and labour for sub main wiring with 2 single core PVC insulated unsheathed cable 1100 Volts grade heavy duty copper conductor multistranded of size 4 sqmm (nominal area) drawing in and including 20mm dia PVC capping casing including one single core green colour PVC insulated unsheathed cable copper conductor multistranded of size 4 sqmm as earth wire upto common earth and connected to earth dolly including taking out old unserviceable submain complete all as specified and as directed by Engr-in-charge. |
| 18 | Supply and fix in replacement sheet metal enclosure SPN with a two pin and earth plug and socket complete with one single pole MCB 20 Amp 10 KA \"C\" series complete all as specified and as directed by Engr-in-charge. |
| 19 | Supply and fix in replacement PVC insulated unsheathed copper conductor 3 core 2.5 sqmm round sheathed multicore industrial cable for voltage grade upto 1100 complete all as specified and as directed by Engr-in-charge. |