| 1 | 12.5 MVA Repairing |
| 2 | HV leg coils complete with insulation varnishing by vacuum impregnating (if required as per sample) and baking of coil assembly..(The rate shall be Variable) |
| 3 | LV leg coils complete with insulation varnishing by vacuum impregnating (if required as per sample) and baking of coils assembly.(The rate shall be Variable) |
| 4 | Fresh transformer oil ofapproved quality as per IS: 335/83 and latest amendment thereof.(The rate shall be Variable) |
| 5 | HV bushing 33 KV(The rate shall be Firm) |
| 6 | LV bushing (11 KV)(The rate shall be Firm) |
| 7 | HV bushing Metal parts.(The rate shall be Firm) |
| 8 | LV Bushing Metal parts.(The rate shall be Firm) |
| 9 | Set of gaskets.(The rate shall be Firm) |
| 10 | Silica-gel breather with fresh silica-gel(The rate shall be Firm) |
| 11 | Magnetic type oil level gauge with low level alarm contact.(The rate shall be Firm) |
| 12 | Tapping Switchcomplete with handle. |
| 13 | Oil drain valve incorporating sampling device (with narrow orifice) and having suitable arrangement for locking.(The rate shall be Firm) |
| 14 | Filter valve(The rate shall be Firm) |
| 15 | Dial type thermometer of 150 dia with max. temp. indicator complete with resetting device and alarm contacts etc.(The rate shall be Firm) |
| 16 | Double float bucholz relay complete with resetting device and alarm contacts etc.(The rate shall be Firm) |
| 17 | Air release plug(The rate shall be Firm) |
| 18 | Replacement of damaged core and lamination(The rate shall be Firm) |
| 19 | Pair of arcing horns(The rate shall be Firm) |
| 20 | Radiator valve(The rate shall be Firm) |
| 21 | M.S. clamping rings(The rate shall be Firm) |
| 22 | Winding temperature indicator (complete set)(The rate shall be Firm) |
| 23 | Sundry item viz. cover bolts ,plug caps, screw washers, insulation materials ,minor repairs of tank other parts required if any, Aluminiumname plate etc.(The rate shall be Firm) |
| 24 | LABOUR CHARGES |
| 25 | Labour charges for repairing of T/Fs complete in all respect (including Opening oftransformers cover , draining of oil, de-tanking core and coil assembly, replacement of damaged parts, minor repair of any part including core and tank (if required), cleaning washing of dust & dirt etc. from all parts including core and tank, Cooling tubes of radiators, removal of damaged parts requiring replacement, fitting & fixing of new parts, making new coils, connection & assembly in all respects, re-tanking after repairs, filling fresh transformer oil etc complete in all respect and making transformer ready for tests and testing forall tests etc. (The rate shall be Firm). |
| 26 | Overhauling of OLTC complete in allrespect (including replacement of OLTC contract,replacement of OLTC terminal barrier board, replacement of gasket, lubrication of mechanical system etc.) (The rate shall be Firm) |
| 27 | Painting inside & outside of transformer including radiator tubes conservator with suitable primer and two coats of suitable paint of smoke grey colour and marking etc.(The rate shall be Firm) |
| 28 | Transportation charges from any site in Uttarakhand to contractor works /departmental workshop and contractor works/departmental workshop to UPCL site / Store center including packing forwarding loading unloading stacking and transit cum 30 days storage insurance charges (The rate shall be Firm) |
| 29 | Manual Dragging charges from road side to Plinth / plinth to road side (The rate shall be Firm) |
| 30 | Scrap of HV/LV Copper Leg Coil |
| 31 | Metal Part Scrap |