Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-06-2022 | Corrigendum-02 | Financial Bid | 09-06-2022 |
| 2 | 24-05-2022 | Revised technical specification in BOQ | Financial Bid | 09-06-2022 |
| Sl. No. | Item Description |
| 1 | Design, supply, installation, testing and commissioning , with documentation of Modular Walk -in- Cold-Room (+2 to +8 Deg C) consisting of the following Minimum Technical Specification(from Sl. No. 1.01 to 1.08) (Capacity and quantities are only for approximation ,actual capacities and quantities are to be provided as per design from the contractor) : - (Preferred Makes :Bluestar/Rinac/Rockwell/Emerson) |
| 2 | Refrigeration System: - Refrigeration Unit Type: Air Cooled SplitDX Type ,No. of Refrigeration Unit: 02 No’s (01 No. 100 % working and 01 No. 100 % Standby).Condenser Type: Air Cooled TypeCondenser Material: Aluminum Fin and Copper Tube Type,Compressor Type: Hermetic Scroll,Cooling Capacity: 18000 BTU/Hr for each Refrigeration UnitCooling Capacity based on: -2 Deg C Evaporating Temperature & 50 Deg C Condensing Temperature.The unit shall be capable of operating continuously in ambient temperature of 5 Deg C to 45 Deg C and Relative Humidity of RH 95%.Ambient Temperature: 45 Deg C,Cold Room Temperature: +2 Deg C to + 8 Deg C |
| 3 | Product to be stored:DNA samples, Reagents, Sterile Culture Material, Surgical items,Product incoming Temperature:+25 Deg C,Door openings per Hrs: 1 Time for Three minutes.Pull Down time: 6-8 Hrs,Refrigerant: R 404 A/ R 134 A Eco Friendly Refrigerant,Defrosting Method: Air Defrost/Electric Heater,Power Supply: 440 V,50 HZ, 3 Phase,Control Panel: The box should have visible glass door of size 450mmX600Mmm with the items viz. It Contains MCB, Digital display with Temperature Setting,Contactor for Compressor, Preventer for single phasing, Overload Protector, Micro Processor based digital temperature indicator with controller, Alarm for High and Low temperature,Timer controller for Auto Changeover of the refrigeration system which allows alternate use of refrigeration system during break down. |
| 4 | Outer Panel: Prefabricated sandwich panels with cam toggle-type fastener fitted and self-locking PVC gaskets fitted on all sides of Wall, Ceiling, and Floor Panels. L shaped separate corner fitted with cam toggle-type fastener. All panels fit together by cam toggle-type fastener. Panel with Ribs on both side panel surface materials to increase the strength. Wall, ceiling and floor all get together by the mentioned arrangements. Wall panel having only Cam Toggle Type fastener fitting, No Flashings and Riveting on Panel.Panel Thickness: Minimum 80 mm, PUF Panel with SS 304 inside and outside . Flushing for Wall/ceiling panels with fastners suitable (80 X30) SS 304 .Flushing for wall/Flooring panels with fastners suitable (20 X40) SS 304 .Flushing for Wall/Wall Panels with fastners suitable (30X30) PCGI . Distribution Box ( 3 Phase supply) : consisting of input main switch , MCB for the operation of Rfrigeration unit power supply. Distribution Box (SPN 4 way): For the purpose of control of LED lights , Temperature controller ,Buzzer etc. |
| 5 | Floor Insulation: Pre-Tab modular PUF Panels (ECO- Friendly) Minimum 80mm PUF Panel with outer side 0.7mm PPGI and inner side marine Ply of 9 mm thickness and Aluminum Chequered plate of 2mm.Strip Curtain :01 No. Strip curtain with 50 % overlap to be provided at the door of Cold StoreRefrigerant Piping: Copper piping including insulationof 70 Mtrs for each refrigeration unit excluding Stand by unit (for suction and Liquid line line from outdoor unit placed on terrace at a hieght of 5 mtrs and routed through shaft space and corridor) Total Ref pipeline 550 mtrs ( Approx) for all Units including Stand By Unit . Electrical Cables : Electrical cable of 60 Mtrs ( Between outdoor and Indoor unit ), Armoured copper cable , 4 Sqmm ,4 Core for each refrigeration unit excluding standby unit.) Total Electrical Cable 300 mtrs ( Approx) for al units including Satnd By Unit (Bidders are requested to visit the site for exact measurements before bidding) . Wall mounting bracket for condenser units: Ref unit to be mounted on bracket /Cement pedestal ,Ref Pipe support to be given with cement support . |
| 6 | Lamination of Panels (Wall & Ceiling): 80 mm Thick SS/SS PUF panel,Cam Lock arrangement between the panels,40Kg/CUM density PCGI on both sides for walls &Ceiling ,Manual Swing Door: Flush type Swing Door with Heavy duty Hinges and Handle with Closer for Push type Gasket for easy operation for Long life. Door should have noncorrosive coating,padlock corrosive coating,With aesthetic look,In built anti condensation Door Heater, thermally sealed doors, with internal safety release. With lock & key. Easy opening and closing of the door. Door to be lockable with 100% fail safe provision for opening from inside. Door shall have an incandescent vapor proof light mounted on the interior of the door section. Opening Size: 3\" 6\". 1 No. (as per requirement of particular site.) Door should beSS inside and SS outside 80 mm thick 47-inch X 78-inch clear opening Single leaf Door with Heater Door.Door Accessories: Posi seal closure, Knob -01 No.Extra Accessories: LED Light 2 Nos. with door switch with bulb & bulk heads & appropriate accessories (like sealant & related).Pressure Relief Port: Pressure relief port without heater to balance the pressure within the room & the surrounding to eliminate the deformation of the room due to pressure difference. Kick Plate: Kick Plate is on both side of the Door to protect the door during material handling. |
| 7 | Minimum Technical Specification consisting of :- Door Accessories: View Plates,Posi seal closure, Knob -01 No.Extra Accessories: LED Light 4 Nos. 40 W lights with door switch with bulb & bulk heads & appropriate accessories (like sealant & related) including operating switchesfor lightson the outside of the cold room .Pressure Relief Port: Pressure relief port without heater to balance the pressure within the room & the surrounding to eliminate the deformation of the room due to pressure difference. Kick Plate: Kick Plate is on both side of the Door to protect the door during material handling.Safety Release Knob: Safety release knob with buzzer placed at the inner side of the door for safety precautions.Shelving: Stainless Steel fully adjustable racks for stacking or storage fitted on all walls up to 6 ft. height. Each rack size (Approx.): - 3700mm(W) x 500mm (D) x 2100mm(H). The material of the shelves should be non-corrosive 316 grade stainless steel to take load of at least 0.075kg/cm2. ISO 9001 certification. |
| 8 | Indoor Unit : SS Ceiling suspended evaporator with all fitting ans SS Drain Tray . Outdoor Unit : Powder coated/wather Protected factory fitted and tested ,outdoor unit, Hermatically sealed & discharge valves. Data Logger Display : LED Display • Output module: Relay alarm output (Max. 8 output), RS-485, RS-232 and USB port (CFR 21) • Record time: Flexible setting interval time: 1s, 2s, 3s, 4s, 3600s • Power-off protection Time O/P: The setting parameters and history data can be kept by FLASH MEMORY, Memorized forever if power off Hardware clock built in for still accuracy running • Calibration Certificate of Data Logger at the time of supply and in every 6 (six) months.Input regulation voltage: the equipment shouold be able to operate within the range of 340V-480V,input operating Low Cut- High Cut outside the range, 3 digit 7-segment.Installation & Commissioning works: The installation commissioning is requiring complete in all respect. The supplier may be required to undertake minor civil works at site viz., minor repair, dismantling a wall etc.Manufacturer Certification: Manufacturer should have ISO-9001 Certification.Warranty: The supplier will provide 6-year warranty from the date of installation and commissioning that will include comprehensive annual maintenance contract “CAMC” including all spare parts and repair. Site Certification: Installation Qualification (IQ), Operational Qualification (OQ), and Performance Qualification (PQ) at site in original.Onsite Comprehensive Training: The bidder should provide on site comprehensive training of Lab Staff on Operation of Equipment, support services till services satisfaction. The Dimensions of the room are as mentioned below:- |
| 9 | Civil Works:- Construction & Finishing of RCC pedestal :- The vendor has to make the 3” Reinforced cement concrete platform on the existing flooring and finished with Kota stone for to install the PUF Slabs for flooring.Drainage ystem:- The vendor has to connect the drainage of the cold room to the nearest drain point. The Scope also includes the necessary civil works like chipping of existing tile flooring, False Ceiling removing & Modification etc. in all respects for commissioning of cold rooms is inclusive and department will not pay any amount for such works. |
| 10 | Hospital Block ,First Floor Haematology Lab with cold room outerSize 3 Mtr (L) X 3 Mtr ( W) X 2.6Mtr (H) , Quantity of product to be stored : 300 Kgs with 04 No\"s Racks |
| 11 | Hospital Block ,First Floor Molecular DiagnosisLab of internal Room Size 2.8 Mtr (L) X 3.0 Mtr (W) X 2.6 Mtr (H) ,Quantity of product to be stored :300 Kgs with 04 No\"s Racks |
| 12 | Hospital Block ,First Floor Micro Biology Lab of internal Room Size 3 Mtr (L) X 3 Mtr ( W) X 2.6 Mtr (H),Quantity of product to be stored :350 Kgswith 04 No\"s Racks |
| 13 | Hospital Block ,First Floor Pharmacy Roomof internal Room Size 3 Mtr (L) X 3 Mtr ( W) X 3 Mtr (H),Quantity of product to be stored : 350 Kgs with 04 No\"s Racks |
| 14 | Supply and Transportation of XLPE/PVC insulated & PVC sheathed armoured cables of 1.1 KV grade with copper conductor |
| 15 | 4C x 6 sq.mm |
| 16 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 17 | Upto 35 sq. mm (clamped with 1mm thick saddle |
| 18 | Supply,transporatation & installation of following sizes of Hot Dipped Galvanized Iron perforated cable trays with cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete |
| 19 | 100mm x 50mm x 1.6mm |
| 20 | Supply and laying of following sizes Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required |
| 21 | 8 SWG GI wire(0.104Kgs/1Mtr) |
| 22 | Supply and making end termination with heavy copper lugs (pin/ ring type) including Cable Glandingas per IS specification, duly crimped with crimping tool, PVC tape etc of followingsize Makes : As per list of recommendedbrands. |
| 23 | up to 16 sqmm |
| 24 | Shed for Cold Room Condenser Units and Cafeteria Dry Scrubber unit |
| 25 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin- charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 26 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer and two coats of syntheticenamel paint of approved colour in all complete |
| 27 | Cafeteria Ventillation System: Design, Supply, installation, testing and commissioningincluding documentationfor exhaust system in First & Second Floor of Cafeteria Block at HBCH&RC ( Floor plan for the First & Second Floor of Cafeteria Block will be provided , Contractor has to visit the site for the feasibility of execution & Design the Ventillation system as per site ) |
| 28 | Cafeteria Ventillation System : Design, Supply, installation, testing and commissioning and documentation of Cabinet Ducted-in-Line Ventilation fans consists of GSS rectangular cabinet double skin construction (Kitchen Exhaust), centrifugal blower with backward/forward and SISW type curved blades, fan motor, removable access door for easy accessibility to motor and fan, flanged inlet and outlet for easy duct work connection, thermally protected motor and necessary supports. Fire retardant canvass connections, Internal power and control wiring, suitable starter panels with isolator, indication lamps, ON/OFF push buttons, GI base frame complete as per specifications as required. Fan motor shall be suitable for 415±10% volts, 50Hz, 3 phase AC supply & high efficiency (IE2)(Makes: Kruger / Nicotra / Greenheck) |
| 29 | Air Qty: 15000 CFM, ESP: 50mmWC, Max Motor Rating: 5.5 kW (3 Phase) -Weatherproof Construction, Maximum permissible noise level- 65 Db |
| 30 | Cafeteria Ventillation System :Design, Supply, installation, testing and commissioning of Ventilation Fan Units with EU-4 Filter for fresh air supply. The unit shall be single skin, belt driven centrifugal fan, High efficiency motor, spring vibration isolator for fan and motor, Fire retardant canvass connections, internal power and control wiring,suitable starter panels with isolator, GI base frame complete as per specifications as required. Fan motor shall be suitable for 415±10% volts, 50Hz, 3 phase AC supply & high efficiency (IE2).(Makes: Kruger / Nicotra / Greenheck) |
| 31 | Air Qty: 8000 CFM, ESP: 20mmWC, Max Motor Rating: 3.7 kW (3 Phase) - Ground Floor kitchen ,Maximum permissible noise level- 55 Db |
| 32 | Air Qty: 6000 CFM, ESP: 20mmWC, Max Motor Rating: 3.7 kW (3 Phase) - First Floor,Maximum permissible noise level- 55 Db |
| 33 | Cafeteria Ventillation System : Supply, installation, testing and balancing of Air Distribution System consists of factory fabricated Galvanized Iron sheet metal ducting with TDF/TDC flanges complete with supports (anchor fasteners and tie-rods, cradles, angle iron supports, GI bolts and nuts, 4mm thick self-adhesive neoprene rubber gasket, stiffeners, zinc chromate painted angle iron flanges, chipping and plastering of openings made for duct supports etc., filling the gap with fibre glass wool and with fire sealant complete as per specification. The rates quoted shall include turning vanes, straightening vanes, splitters, inspection doors probe, inlets with test openings enclosures complete with locking caps, chain, gaskets, insulating plugs, and extension for insulated ductwork etc. The rates should include placing of suitable sound attenuators in supply and exhaust ventillation system so as to limit the maximum permissible noise level to 55Db to 60 Db for the complete cafetretia ventillation system.(Makes: TATA / Jindal / Sail ) |
| 34 | 1.2mm thick GSS ducting |
| 35 | 1.0mm thick GSS ducting |
| 36 | 0.8mm thick GSS ducting |
| 37 | 0.63mm thick GSS ducting |
| 38 | Cafeteria Ventillation System : Supply and installation of Sound Attenuators in existing ventillation ducting in CSSDRoom consist of outer ,casing with 1.2m Long, sound absorbing material and internal baffles, splitters and supports as required. Casing shall be of 18G thick GI sheet. Sound absorbing material shall be high density fibre glass held in place with at least 5% compression to prevent voids due to settling.Absorption material density shall be minimum 48 kg/cum. Fibreglass faced with minimum 24G perforated GI sheet of minimum 40% open area. |
| 39 | Cafeteria Ventillation System : Supply, installation, testing and commissioning of Dry Scrubber Units (Electrostatic Air Cleaners) for Kitchen Exhaust System. The casing shall be made up of powder coated, 16 Gauge Hot-dip Galvanized steel. The Units shall be provided with pre-filters, post filters, indicator LEDs, short circuit protection, auto power cut-off when door is open, alarm indicator. The unit shall be suitable for Ceiling Suspended / Wall or Frame Mounted and the necessary supporting arrangements shall be included.The Scrubber unit capacity is 7000 CFM ( Area Available for installaing the unit is (Makes: Rydair ,Rieco ) |
| 40 | Cafeteria Ventillation System : Supply and installation of Powder coated extruded aluminium continuous linear 1 way or 2 way grilles with 15 degree deflection and aluminium volume control damperas per drawing & specifications.(Makes : Caryaire / Air master / Systemair / Cosmic ) |
| 41 | Cafeteria Ventillation System :Supply and installation of Powder coated extruded aluminium continuous linear grilles with 0 degree deflection without volume control damper as per drawing & specifications.(Makes : Caryaire / Air master / Systemair / Cosmic ) |
| 42 | Cafeteria Ventillation System : Supply, installation, testing and balancing of GI louver volume controldamper (low leakage) made out of 16G thick galvanized sheet steel frame and blades of 18G galvanized steel with suitable links, handles, levers and quadrants for manual control of volume of air flow and for proper balancing of air distribution system. |
| 43 | Cafeteria Ventillation System : Design, Supply, installation, testing and commissioning of motorized Fire damper in supply air/return air/exhaust air streams. The damper shall be made out of 16G thick galvanized sheet steel frame and blades of 18G galvanized steel with air tight arrangement. The damper shall be provided with control panel, actuator, combined smoke and heat sensor and transmitters, control / communication cables, etc. The control panel shall be suitable for receive/send signal from the Fire Alarm System and status shall be monitored thru BAS. |
| 44 | Smoke & Fire Dampers. ( Makes: Dynacraft / Ravi-Star /Caryaire) |
| 45 | BMS compatible Actuators with Control Panel & Wiring |
| 46 | Cafeteria Ventillation System :Supply and installation of Extruded Aluminium powder coated fresh air intake / outlet louver with vermin netting and 45 deg angle suitable for protection against splashing rain water fixed in a powder coated Aluminium angle mount frames. (Makes : Caryaire / Air master / Systemair / Cosmic ) |
| 47 | Supply and installation of Fire Retardant Canvass connections with GI matching flanges on both sides with a provision of openable zip. The entire assembly shall be factory fabricated. |
| 48 | Design, Supply, installation, testing and commissioning of Air Curtain for Cafeteria: The body shall be made up of corrosion resistant hot zinc plate and powder enamel steel plate. The air curtain shall have less noise and suitable for wall mounting / ceiling suspension. The grille shall be adjustable to direct the air flow. The air curtain shall be suitable for 230V, 50Hz, 1 phase supply and max motor rating shall be 1.0 kW. The rate shall be inclusive of required ceiling suspension bracket and supporting arrangement. The width of the air curtain shall be 1500mm and suitable to fix above 3000mm level. (Makes : Rust Air/Rusell AIr / Equivalent approved by EIC ) |
| 49 | CSU Unit for Record Room in Hospital Block : Design, Supply, installation, testing and commissioning of Double Skin Air Handling Units of Ceiling Suspended type, 25±3mm thick panel with PUF insulation, filter sections, min 4 row deepwater coil of copper tube & aluminium fins, copper header, single / multiple forward curved DIDW centrifugal fan, High efficiency motor, vibration isolator for fan and motor, factory assembled volume control damper, Fire ratardant canvass connections, internal power and control wiring, complete as per specifications as required. Fan motor shall be suitable for 415±10% volts, 50 cycles, 3 phase AC upply & high efficiency (EFF-1)and suitable for VFD operation. VCD Size 400 X400 (Makes: Systemair/Zeco/Edgetech/Saiver) Desired Room Temperature : 23 ± 1 Deg C |
| 50 | Capacity:8 TR, Dehumidified Air: 4000 CFM |
| 51 | PIPES AND VALVES ( for CSU Unit) :Supply, erection, testing and commissioning of following chilled water water pipes. inside the building (with necessary clamps, vibration isolatorsand fittings but excluding valves, strainers, gauges etc.) duly insulated with 32 mmclosed cell elastometric nitrile rubber of minimum 45 Kg / cu m density,thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘O’ insulation applied by suitable rubber based adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Pipes will be of Mild Steel - Class C’. The thickness of the pipes up to 150mm Dia as per IS 1239. Rate shall inclusive of all necessary fittings like bends, elbows, Tee, etc and inclusive ofmaking hole in the wall, chasing, chipping, making good with plastering after completion of work, pipe sleeve of suitable higher size, sealing the sleeves with glass wool & 2 hour fire sealant, and provisions for BAS sensors. Cost of supports for piping like clamps,anchor fasteners, tie rods, brackets, nuts and bolts, etc as shallalso be included in the quoted rate. Cost of dismantling the required spaces in Connecting bridge and making good in all respects is also included in the cost.(Tata/Jindal -Star). |
| 52 | 65 NB - MS Class C |
| 53 | 50 NB - MS Class C |
| 54 | 40 NB - MS Class C |
| 55 | CSU Unitdrain line :-Supply , erection and insulation with 19 mm thick Class \"O\" nitrile Rubberof the following GI Class B pipe for CSU Drain line with all screw joints, reducer, necessary elbows and tees, supporting arrangements, etc. ( (Tata/Jindal -Star).) |
| 56 | 25 NB- GI Class B |
| 57 | CSU Unit Control valve arrangement : : Supplying, fixing, testing and commissioning , insulation of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.16.7.1 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O Ring PN 16 pressure rating for chilled water/hot eater circulation as specified (Crawly &Ray /Advance / C&R / CIM / Danfoss / Balimo) |
| 58 | 50 NB - Lever operated |
| 59 | Supply and erection of Forged Brass Ball valves as per specification complete with end flanges/matching flanges, additional supports,fixing accessories, thermal insulation, etc. (Crawly &Ray /Advance / C&R / CIM / Danfoss / Balimo) |
| 60 | 40 NB - Lever operated |
| 61 | Supply and erection of ‘Y’ type strainer with removable stainless steel screen with 3mm perforation and permanent magnet, drain piping. Rate shall inclusive of end flanges/matching flanges,additional supports, fixing accessories, thermal insulation, etc (Crawly &Ray/ Sant/Rapid control/Emerald) ( for CSU Unit) |
| 62 | 40 NB |
| 63 | CSU Unit Chilled water Piping and insulation : Supply and erection of Thermal insulation of chilled water piping ,with FM approved closed cell nitrile rubber insulation covering with,fire resistant fibre cloth fabric as a resistant to Scratch &Mechanical Impact. The thickness of the insulation for various pipe sizes are as below. The rate shall inclusive of adhesive as recommended by the manufacturers.( Makes for insulation :Beardsell/Styrene packaging/LLyods) ( Makes for Adhesives : Fevicol/superlon/pidilite) |
| 64 | 38mm thick insulation for 65 NB pipe |
| 65 | 38mm thick insulation for 50 NB pipe |
| 66 | 32mm thick insulation for 40 NB pipe |
| 67 | 19mm thick insulation for 25 NB pipe |
| 68 | Supply and erection of SS Bourdon Type Pressure gauges complete with ball valve, mounting well, fittings and copper tubing extension where required .( Makes : H.Guru/Taylor/Emerald.) |
| 69 | Supply and erection of SS Bourdon Type Thermometers with copper separable well complete with guard mounted on water lines, etc. (Makes: H.Guru/Taylor/Emerald/Jaspin) |
| 70 | AIR DISTRIBUTION SYSTEM for CSU Unit & CSSD Room Ducting : Supply, installation, testing and balancing of Air Distribution System ( having a maximum noise level of 60 DB within the Kitchen Area) consists of factory fabricated Rectangular duct Galvanized Iron sheet metal ducting (Zinc coating 180GSM) with TDF/TDC flanges complete with supports (anchor fasteners and tie-rods, cradles, angle iron supports, bolts and nuts, 4mm thick self-adhesive neoprene rubber gasket, stiffeners, zinc chromate painted angle iron flanges, chipping and plastering of openings made for duct supports etc., filling the gap with fibre glass wool and with fire sealant complete as per specification. The rates quoted shall include turning vanes, straightening vanes, splitters, inspection doors probe, provisions for BAS sensors, inlets with test openings enclosures complete with locking caps, chain, gaskets, insulating plugs, and extension for insulated ductwork etc. |
| 71 | 0.8mm thick GSS ducting (Plenum box) ( Makes Edgetech/ Saiver/ZECO / Ravi-aircon/ Wave) |
| 72 | 0.63mm thick GSS ducting( Makes: Sail / Tata/Jindal.) |
| 73 | Duct accoustic for CSU Unit & CSSD Room ducting:Supply and installing of Acoustic insulation,Material shall be processed Nitrile Rubber foam with anti-microbial protection. The material should be fibre free. The density of the same shall be within 140-180 Kg/m3.The material should have a thermal conductivity not exceeding 0.038 W/mK. The maximum surface temperature the material should withstand is 105º C and minimum temperature should be -20ºC. The Thickness of the material shallbe 15mm. The material should conform to Class 1 rating for surface spread of Flame as per BS 476 Part 7. |
| 74 | Supply and fixing of Spigot damper shall be installed from take off collar to diffuser plenum boxes and at plenum boxes (low leakage) made out of 16G galvanized sheet steel frame and blades of 18Ggalvanized steel with suitable links.( Makes: Sail / Tata/Jindal.)( for CSU Unit & CSSD Room Ducting |
| 75 | 250mm Dia |
| 76 | For CSU Unit & CSSD Room Ducting :Supply and fixing of 10mm thick open cell nitrile rubber acoustic lining for supply air plenum box (Supreme/Trocellene/Armacel/Paramount) |
| 77 | For CSU Unit & CSSD Room Ducting :Supply and fixing of08 No\"s Supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core Powder coated Extruded Aluminium Supply air diffusers with 600 x 600mm size. (Dynacraft / Ravi star/caryaire) |
| 78 | For CSU Unit & CSSD Room Ducting :Manufacturing of 08 No\"s24G (0.63 mm) GI sheet pre-fabricated plenum box. The plenum shall be of 450mm height and Length X Width of 450 mm X450mm The plenum box shall be supported at the four corners with adjustable hanger / chain support. 375 x 375mm neck size (Sail / Tata/Jindal) |
| 79 | For CSU Unit & CSSD Room Ducting:Supply and fixing of08 No\"s Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.Extruded Aluminium, powder Coated return air diffusers with removable centre core overall size 600 x 600mm without volume control dampers . (Dynacraft / Ravi star/caryaire) |
| 80 | For CSU Unit & CSSD Room Ducting: Supply and installation of 04 No\"s Powder coated extruded aluminium,continuous linear 2 way grilles in gypsum board false ceiling(Size 2000mmX150mm) for return air as per specifications,The rate shall inclusive of necessary fixing and supporting,arrangement for the grilles.( Dynacraft / Ravi star/caryaire) |
| 81 | For CSU Unit & CSSD Room Ducting :Supply, installation, testing and balancing of GI louver volume controldamper (low leakage) made out of 16G thick galvanized sheet steel frame and blades of 18G galvanized steel with suitable links, handles, levers and quadrants for manual control of volume of air flow and for proper balancing of air distribution system. |
| 82 | For CSU Unit & CSSD Room Ducting :Supply, installation, testing and balancing of High Air Flow HEPA filters (efficiency 99.99% down to 0.3microns) and suitable plenum box housing in HVAC ducting of CSSD room . The overall height of the housing to be limited to 400mm. Suitable opening provision for pendant lighting and supporting arrangement shall be considered. The belew specified sizes are minimum recommended sizes and Vendor to upgrade the sizes to meet the Filteration level of Class 1,00,000 for OT and Class 10,000 for CSSD as per ISO-14644.HEPA Filters size 600 x 600mm. |
| 83 | Exhaust ductingwith blower and Inline Heater for Bio Safety Cabinet in Lab areas. |
| 84 | :Supply ,Installation ,Testing and Commissioning of 1.5 KWIn Line Duct Heaters withduct blower ( with Minimum200 CFM) for Bio Safety Cabinet ,installing the duct heater betweenventillation ducts with suitable clamping and electrical connection for heater with auto cut off mechanism , auto temperatre cut off ( Make : M/s RICKARD in line heaters ) |
| 85 | Supply, installation, testing and balancing of Air Distribution System consists of factory fabricated Galvanized Iron sheet metal ducting with TDF/TDC flanges complete with supports (anchor fasteners and tie-rods, cradles, angle iron supports, GI bolts and nuts, 4mm thick self-adhesive neoprene rubber gasket, stiffeners, Exhaust air Valve, zinc chromate painted angle iron flanges, chipping and plastering of openings made for duct supports etc., filling the gap with fibre glass wool and with fire sealant complete as per specification. The rates quoted shall include turning vanes, straightening vanes, splitters, inspection doors probe, inlets with test openings enclosures complete with locking caps, chain, gaskets, insulating plugs, and extension for insulated ductwork etc. (Makes: TATA / Jindal / Sail ) |
| 86 | 0.8mm thick GSS ducting |
| 87 | 0.63mm thick GSS ducting |
| 88 | VENTILATION SYSTEM ( for Lab Areas) :Design, Supply, installation, testing and commissioning of Cabinet / Ducted-in-Line Ventilation fans consists of GSS rectangular/circularcabinet double skin construction, centrifugal blower with backward/forward curved blades, fan motor, removable access door for easy accessibility to motor and fan, flanged inlet and outlet for easy duct work connection, thermally protected motor and necessary supports. Motors shall be suitable for 3 Phase(EFF-1) or 1 Phase AC supply, and the capacity are as follows. (Weather proof fan and motor for outdoor type fans - IP65) |
| 89 | Outdoor Type :Air Qty: 700 CFM, ESP: 30mmWC, Max Motor Rating: 0.35 kW (1Phase) |
| 90 | For Lab Areas :Supply, Installation, Testing & Commissioning of 6-32 A ,DP, MCB for the purpose of ON/OFF of Exhaust fans . The MCB should be installed in Terrace HVAC Panel boardd with inclusive of all supporting accessories and mountings |
| 91 | For Lab Areas : Design, Supply, installation and commissioning of the following capacity Ceiling mount type Fans for blood bank washing room and culture room bio safety cabinet. The fan shall be of noiseless operation and having good aesthetic. The fan motor shall be suitable for operating on 230V, 1 phase, 50Hz AC supply. The body shall be made up of impact resistance ABS plastic. The casing shall be air tight and have non return damper to prevent back flow and spigot damper for flexible duct connections.The cost shall include the price steel supports required for mounting the fan and bird screen, wire mess and storm proof louvers as required. The fan shall have min ESP of 10mmWC |
| 92 | Air flow rate: 250CFM |
| 93 | For Lab Areas : Supply, Installation, Testing & Commissioning of 6-32 A ,DP, MCB for the purpose of ON/OFF of Exhaust fans . The MCB should be installed in nearestPanel board with inclusive of all supporting accessories and mountings |
| 94 | Electrical Items forCafteria Ventillation and Point Wiring for kitchen equipments, CSU Unit , Lab Area Bio safey cabinet. |
| 95 | KITCHEN-VTPN DB-8WAY : READYMADE DISTRIBUTION BOARDS Supply, installation, testing &commissioning of following ready made distribution boards, double door, IP 42degree protection complete withnecessary, MCB isolators , MCBs, earthleakage circuit breaker (ELCB) etcincluding interconnections with appropriate capacity size of PVCinsulated copper conductor wires (ISImarked),suitable for concealed mounting/wall mounting with MS frame work of 40 x40 x 5 mm MS angle iron, with M.S.enclosure fabricated out of min 18 SWG/20SWG thick M.S. CRCA sheet as permanufacturers standard, with concealedhinged door, locking arrangement etc.including earthing clamps for bothincoming & outgoing circuits,interconnections, per phase isolation kitas required,cable end box & wire way boxif required, continuous copper earth wirein the wire way box with single/duplicatebrass earthing terminals, danger board,name plate, flexible earthing for the door,metal treatment & powder coatedpainting, Phase Distribution drawing etc.all as per drawings (G.A. & fabricationdrawing to be got approved), etc. relevantIS & instruction of Engineer-in-charge.The powder coating colour shade forDB\"s shall be as follows:-1. DB\"s fed from normal / DG powersupply - RAL 7032Note:1.MCBs (Type –C) shall be minimum 10 KA /25 KA breaking capacity, as specified.2. Blanking Plates shall be included inscope of work. 3. DB shall be of standard readymadetype from approved manufacturers asindicated in preferred makes of material.4. Routine tests will be conducted atfactory as per relevant IS.5. The DB shall be complete withnecessary tinned Copper busbars,interconnections, separate earth bus &separate neutral bus for each phases.6. All Distribution boards doors arelockable with master sets of key eachseparate block |
| 96 | Supply, fixing, testing and commissioning of the Double door type VTPN 8 way MCCB DB IP-42 comprising of the following :(Fabricated DB),125A FPMCCB 16 KA – 1No. as incomer with ELM,32A TP MCB 10kA (C-Curve) – 8 Nos. as outgoings.With necessary tinned copper busbars, interconnections,earth bus, neutral bus. The board shall be powder coated type fixed with concealed system in wall/ fixed in column. The rate shall include necessary connected civil works like chipping, rough plastering etc. |
| 97 | PDB (7 segment DB)-8WAY-GF-1,GF-2,FF-1,FF2 : Supply, fixing, testing and commissioning of the double door type compartmental Phase segregated 8 way MCB DB meeting IP-42 comprising of the following :63A FP MCB 16kA with all necessary connected accessories – 1No.as incomer, 63 A DP 100 mA RCBO – 3 Nos. as outgoings.Each 63 A DP MCB outgoing consist of 8nos.20 A 10KASP MCB (C-Curve) in a separate compartment with necessary phase segregation as required by the Electrical Inspectorate.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases.The board shall be powder coated type fixed with concealed system in wall/ fixed in column.The rate shall include necessary connected civil works like chipping, rough plastering etc. |
| 98 | Wiring in PVC conduit/GI conduit :Power Wiring for 6A/ 16A/ socket outlet /6A outlet for exhaust fanetc. with 1.1 KV grade FRLSPVC insulated multistranded copperconductor wire(ISI marked), in G.I conduiton surface /25 to 40 mm dia rigid concealedPVC conduit having ISI marked IS 9537Part - 3 , including fixing accessories &hardware. The GI conduits shall be mounted on 5mm. thick G.I. spacers fixedwith no. 10 nettle fold wood screws withnylon plug complete with all conduitaccessories 20 SWGG.I. Saddles. Thescope shall include providing ready madeMS switchboxes, socket outlet boxes ofmin 18 SWG / 20 SWG thickness , brassearthing stud 1/2 nos, controlling modularswitches, sockets with moulded front plateand inner plate etc. includingappropriate size of FRLS PVC insulatedcopper earth wire , brass/bakelite(straight / angular) lamp holders, 3 plateceiling rose,16 A, connectors, paintingetc. as per specifications and drawingsand as per instructions of E-I-C and asdetailed below : (sample switch Box etc. to be got approved before fabrication) |
| 99 | 6 A 3 pin socket outlet point with 2R of 2.5sq.mm wires alongwith 1 no of 1.5 sq.mm FRLS insulatedwire complete with16A switch in one box. Note: One circuit main connected to max.2 nos. sockets. |
| 100 | 16 A 3 pin socket outlet point with 2R of 4sq.mm wires alongwith 1 no of 2.5 sq.mm FRLS insulatedwire complete with 16 Aswitch in one boxNote: One circuit main connected to 1 nos. sockets. |
| 101 | Power wiring with 2 nos of 4 sq.mm wire and 1 no.of4 sq.mm FRLS insulated wire complete with 20 A DP MCB & 20 A 3pin socket outlet with plug (IndustrialType Weather proof-IP65) in readymade Poly Carbonate box and interconnections earthing stud etc.MCB shall be with 10 KA breaking capacity. Note: One circuit main connected to max.1 no. set. |
| 102 | Supply,Testing and commissioning of 32A 4P MCB & 32 A ,3 Phase, 5 pin socket outlet with plug(Industrial Type-Weather Proof-IP 65) in readymade Poly Corbonate box and necessary cutouts,interconnections earthing stud etc. MCBshall be with 10 KA breaking capacity. Note:One circuit main connected to max.1 no. set. |
| 103 | Supply,erection,testing and commissioning of starter comprising of the following 1No. 32A TP&N MPCB with adjustable variable settings 16 KA with all connected accessories.1 No. Star Delta starter (3 Phase) suitable for 5.5 KW for with Ammeter, selector switch, suitable ratio of CTs,control fuses, Auto/Manual selector switch, on/off/trip indication lamp with necessary power and control wiring interconnections etc.,with suitable provision to link with IBMS and all connected necessary accessories in a suitable MS enclosure with painting , earthling and suitable fixing arrangement as required and Panel should have IP55 Protection.The rate shall be including necessary interlocking, control wiring, interconnection & termination etc., |
| 104 | Supply,erection,testing and commissioning of starter comprising of the following :1No. 16A TP&N MPCB with adjustable variable settings 16 KA with all connected accessories.1 No. Direct Online starter (3 Phase) suitable for 3.7 KW for with Ammeter, selector switch, suitable ratio of CTs,control fuses, Auto/Manual selector switch, on/off/trip indication lamp with necessary power and control wiring interconnections etc.,with suitable provision to link with IBMS and all connected necessary accessories in a suitable MS enclosure with painting , earthling and suitable fixing arrangement as required and Panel should have IP55 Protection.The rate shall be including necessary interlocking, control wiring, interconnection & termination etc., |
| 105 | CABLES AND TERMINATION For all items in section-E, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same. |
| 106 | L.T Cables:Supply, installation, testing &commissioning of 1.1 KV gradealuminium/ Cu stranded circular/ sectorshape core conductor withPVC/XLPEinsulation, extruded PVC innersheathed, G.I flat strip/wire armoured,extruded FRLS grade antirodent & antitermite PVC (ST-2)outer sheathedcable conforming to IS : 1554 Part I / IS7098 Part-I with latest amendments, fixed on wall/column/slab/false ceiling/ existing cable tray /existing humepipe/trench/ shaft/pit/ on 5mm thickM.S. flat /GI spacer/angle/ support fixedwith coach screws/grouted inwall/anchor fasteners 2mm. thick G.I.fabricated saddle, all fixingaccessories, etc complete includingpainting of M.S spacers/angles andsaddles or in ground at a - depth of900 mm below ground level (cost ofexcavation shall be measuredseperately under item no. 4.0 ofSection-XXIII ) , sand bedding, laying ofbaked bricks on side & top-, temporaryreinstatement, back filling, dewatering,consolidation, disposal of excess earthwithin the radius of 500 m and makinggood to the original finish etc providingbrass cable number tag as perenclosed detailed specifications,drawings & as per instructions ofthe E-I-C & of the following sizes. NOTE: 1) Sealing of hume pipes with woodenbushes after cable laying shall beincluded in the scope of work.2)Clamping of cables on trays includingsupply of clamping materials as perinstruction of EIC shall be included in thescope of work.3) Colour coding shall be used for 1 core PVC Copper unarmoured cableto differentiate phase, neutral and earthing of UPS system. |
| 107 | 4 Core 50 Sq.mm XLPE Aluminium armoured Cable for VTPN DB |
| 108 | 4 Core 25 Sq.mm XLPE Aluminium armoured Cable for PDB |
| 109 | 4 Core 6 Sq.mm XLPE Copper armoured Cable for ceiling mounted exhaust fans and outdoor Type exhaust fan used for ventillation in Labs bio safety cabinet. |
| 110 | 4 Core 6 Sq.mm XLPE Copper armoured Cable for Kitchen 3ph Isolator/Equipments |
| 111 | 4 Core 10 Sq.mm XLPE Copper armoured Cable forPharmacy (CSU unit and Cold Room)from HVAC Room |
| 112 | LT Cables End Joints :End jointing of following sizes of cable bycrimping with supply of all jointingmaterials like solderless tinned coppercable socket,double compression brasscable glands, gland earthing, insulationtape, flux, duplicate interconnectionbetween gland earthing strip & to thenearest earthing bus terminals as per thedrawings, specifications and as per theinstructions of the Engineer-in-charge. |
| 113 | 4 Core 50 Sq.mm XLPE Aluminium armoured Cable |
| 114 | 4 Core 25 Sq.mm XLPE Aluminium armoured Cable |
| 115 | 4 Core 6 Sq.mm XLPE Copper armoured Cable |
| 116 | SECTION –E : TRAYS AND EARTHINGS Supply and installation of prefabricated hot dip galvanised sheet perforated/ ladder type cable trays of following sizes including horizontal and vertical bends, reducers, tees, cross members, coupler plates and other accessories as required and duly suspended from the ceiling/wall with hangers, threaded rods, supports etc., as required. |
| 117 | 100mm WideLadder X 50mm Height X 2.5mm Thick |
| 118 | EARTHING SYSTEM Supply, installation, testing &commissioning of earthing system &associated accessories, etc. complete allas per layout drawing, specifications & asper the instructions of E.I.C. |
| 119 | 25 X 3 mm GI strip |
| 120 | 8 SWG tinned Cuearth wire |
| 121 | False Ceiling |
| 122 | Providing and fixing Gl Clip in Metal Ceiling System of 600x600 mm module which includes providing and fixing \"C\" wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of Gl steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into spring T with GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending. |
| 123 | PART -BComrehensive Maintenance Charges for maintenance of complete walk -in- cold room facility( OEMproviding 1 year warranty after which CMC charges for the 05 years follows ) |
| 124 | Second Year CMC |
| 125 | Third Year CMC |
| 126 | Fourth Year CMC |
| 127 | Fifth year CMC |
| 128 | Sixthyear CMC |
| 129 | Comprehensive Maintenanc Charges for Total value of work for Installaing CSU Unit in Pharmacy Block( OEMproviding 1 year warranty after which CMC charges for the 05 years follows ) |
| 130 | Second Year CMC |
| 131 | Third Year CMC |
| 132 | Fourth Year CMC |
| 133 | Fifth year CMC |
| 134 | Sixthyear CMC |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy