| 1 | Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for taking out of unserviceble/laying new LT under ground cable complete all as directed. |
| 2 | Returning filling in, approved soft/loose soil, including spreading , levelling, watering and well ramming in layers each not exceeding 25cm in soft/loose soil complete all as specified and directed by Engineer-in-Charge. |
| 3 | Removal of surplus excavated soil to a distance not exceeding 50metre and depositing where directed at level not exceeding 1.5 metre above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 4 | M & L for local sand cushioning, with dry and clean sand, over and under the under ground cables in trenches, ducts for cable protection including consolidation, 80mm thick to the authorized width as per SSR-Part-1 before laying of cable and 150mm thick after laying of cable and punned down to 180mm after laying complete all as specified and directed by Engineer-in-Charge. Note:- Punned thickness shall be considered for payment purpose. |
| 5 | Supply & laying dry bricks over cable as mechanical protection layed flat with width equal to length of brick with sub class \"B\" bricks complete all as specified. |
| 6 | Taking out serviceable/unserviceable XLPE LT UG cable aluminium conductor of any size 2/3/4 core from excavated trench/pole/over ground etc and retreived material to store kept in safecustody for reuse at site or for taking credit of cable to be replaced with new one all as specified and dirrected. (Excavation, sand and return filling will be paid saperately). |
| 7 | Supply, laying in replacement of unserviciable underground LT cable 1100 Volts grade heavy duty electric cable XLPE insulated & PVC outer sheathing with aluminium stranded conductor, armoured confirming to IS-7098 Part-I (1988) with latest ammendments of sizes 2 core 10 Sqmm Complete all as specified and directed. |
| 8 | All as per ser item No 07 here-in-before but of size 2 core 16 sqmm. |
| 9 | All as per ser item No 07 here-in-before but of size 4 core 10 sqmm. |
| 10 | All as per ser item No 07 here-in-before but of size 4 core 16 sqmm. |
| 11 | All as per ser item No 07 here-in-before but of size 4 core 25 sqmm. |
| 12 | All as per ser item No 07 here-in-before but of size 3.5 core 35 sqmm. |
| 13 | All as per ser item No 07 here-in-before but of size 3.5 core 50 sqmm. |
| 14 | All as per ser item No 07 here-in-before but of size 3.5 core 70 sqmm. |
| 15 | All as per ser item No 07 here-in-before but of size 3.5 core 95 sqmm. |
| 16 | All as per ser item No 07 here-in-before but of size 3.5 core 120 sqmm. |
| 17 | All as per ser item No 07 here-in-before but of size 3.5 core 150 sqmm. |
| 18 | All as per ser item No 07 here-in-before but of size 3.5 core 185 sqmm. |
| 19 | All as per ser item No 07 here-in-before but of size 3.5 core 240 sqmm. |
| 20 | Material and labour in replacement of double compressionbrass cable gland suitable for LT cable of size 10 to 70 sqmm 4 core complete all as specified and directed. |
| 21 | Material and labour in replacement of double compressionbrass cable gland suitable for LT cable of size 95 to 300 sqmm 4 core complete all as specified and directed. |
| 22 | M&L in replacement of LT cable straight through type jointing kit, heat shrinkable including all jointing material & accessories suitable for 1100 Volt grade aluminium conductor cables of size 25 to 50 Sqmm 4/3.5 core cables complete all as specified and directed. |
| 23 | All as per ser item No 22 here-in-before but of size 70 to 120 x 4/3.5 core |
| 24 | All as per ser item No 22 here-in-before but of size 150 to 185 x 4/3.5 core |
| 25 | All as per ser item No 22 here-in-before but of size 240 to 300 x 4/3.5 core |
| 26 | Supply and fixing in replacement of GI steel tubing light grade complete under Road, Path drain, fixed on walls etc of size 100mm bore complete all as specified and directed. |
| 27 | All as per ser item No 26 here-in-beforebut of size 80mm bore |
| 28 | All as per ser item No 26 here-in-beforebut of size 50mm bore |
| 29 | Supply & fixing in replacement of 1100 volt grade heavy duty cable PVC armered insulated aluminium conductor stranded conductor as in service connections suspended by insulated hangers not more than 1.0 mtr apart including 4mm dia GI wire, suspension wire, 2 core flat or circular of sizes 16 Sqmm x 2 core complete all as specified |
| 30 | Supply and fixing in replacement of multi core round PVC insulated copper conductor (flexible) industrial cables PVC sheathed cables, 1100 volts conforming to IS : 694 of size 1.5 Sqmm, single core two run from junction box /overhead conductor to street light inside/outside pole complete all as specified. |
| 31 | Supply and Fixing thermoplastics polystyrene/polycarbonate enclosure, shock proof, IP65( weather proof), rust proof, dust proof, water proof, internally embedded gasket with provision for all side cable entry through glands(IP-65) and/or grommets(IP-55). Size of enclosure: ( 250 x 180 x 110 ) mm With suitable connectors for /1Ph loop in loop out and branch out vibration proof connections and fixing on PCC/ steel poles with 25x3mm thick 02 Nos of clamp with nuts and bolts and washers and proper thimbling incl four nos bus bar of 200 Amps 415 Volts mounting non PVC insulator complete all as specified and directed. |
| 32 | Supply totally enclosed bus bar feeder pillar outdoor type fabricated out of 3.15 mm thick CRCA sheet dust and vermin proof powder coated double door type complete suitable for operating on 415 Volt 50 Hz AC supply having legs 90 cms made out of 50x50x6 mm angle iron grouted on PCC 1:4:8 below the ground 60 cms and above the ground should be 30 cms. Comprising the following:-Note:- (i)01 set of 200 Amps TPN aluminium bus bar of length suitable for fixing minimum 6 cables and of crossection as per design with colour codding. Bus bars shall be designed to with stand a fault level of 36 KA at 415 volts. (ii) Provn of one incoming MCB 100 Amps TPN 16 KA, 50 HZ (iii)The panel shall be front operated with cable entry from the bottom with cable glands. Earth bus shall be part of the main feeder pillar. (iv)Fabrication of feeder pillar box to be approved by CPRI width of the panel not less than 30 cms. (v)Cost for construction of platform for panel work in CM 1:6 with foundation PCC 1:4:8 type D-2 including plaster work, PCC copping 1:2:4 (40 mm thick stone aggerate), deemed to be included in the item rate. No Extra payment will be made.(vi)After fixing the bus bar panel, all electric connections will be made without any extra cost all as specified and directed. |
| 33 | Attending the complaint for LT UG cable any size 1100 Voltsfault locatingby using high POT fault finding Machine vehicle mounting incl T&P and Labour complete with route finder mobile equipment as finding out one fault on one cable route including cutting of road/ plinth/hard standing all as specified & directed by Engr-in-Charge.Note:- (i) Cutting of road/ plinth/ hard standing/Excavation/returning/fillingshall deemed to be included in qouted rates by contractor no extra will be paid.(ii)Cable joints shall be mesured and paid separately.(iii) Vehicle mounted fault finding machine shall be arranged by the contractor, the rates deemed to be included in qouote rates. |