Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Part A - Hydrant Pipeline Revamp & Addition |
| 2 | Supply, Installation & Commissioning of 100mm dia. CS Gate Valve Hand wheel Operated of approved make (WCB-216) Bolted Bonet OS&Y Type Rising Stem SS 410 Trim Flanged End to ANSI-B16.5, 125-250 Ra Finish, Class 150 as per API 600 A216 Gr. WCB Trim 1 to API 600, 602 (13% Cr) OS&Y, PTFE Gland Packing API 598. Flexible Wedge with with nuts,bolts, gaskets etc complete as per specifications in tender documents. |
| 3 | Supply of Butterfly Valve of approved make as per below specifications |
| 4 | 100 mm Dia Water Butterfly Valve API 609 Cat. A CL 150 RFTBE Lever Operated DI GGG40 Trim 1 to API 600 602 (13% Cr) EPDM Lining PN 16 API598. |
| 5 | 150 mm Dia Water Butterfly Valve API 609 Cat. A CL 150 RFTBE Lever Operated DI GGG40 Trim 1 to API 600 602 (13% Cr) EPDM Lining PN 16 API 598. |
| 6 | 200 mm Dia Water Butterfly Valve API 609 Cat. A CL 150 RFTBE Lever Operated DI GGG40 Trim 1 to API 600 602 (13% Cr) EPDM Lining PN 16 API598. |
| 7 | Fixing & commissioning of the supplied butterfly valves of the following sizes on the pipeline including supplying and fixing new 3 mm thick non metalic gaskets, studs / nuts etc. of approved make for the following sizes as per specifications and site instructions, complete in all respect. |
| 8 | 100mm dia. Butterfly valve |
| 9 | 150mm dia. Butterfly valve |
| 10 | 200mm dia. Butterfly valve |
| 11 | \"UNDERGROUND PIPELINE : Underground pipelines of 200mm dia. pipes to be laid at a depth as per site condition (upto 3m) including excavation in all types of soil, Pipe to be hydro tested at 16 Kg / Sq. cm before laying. 100% radiography of welded product pipeline joints to be done. Cost under this item includes excavation in all types of soil including asphalted driveways, WBM, Stone Boulders etc. except RCC driveway which shall be paid separately under concerned item of Schedule. The job also includes required test & back filling of earth after laying pipeline complete in all respect. Note: The pipeline laid under culvert or Hume pipe coating shall be measured and paid as Above Ground pipeline. Item includes painting of pipeline as per enclosed technical specifications. |
| 12 | Supply of pipeline 200mm dia. Heavy Duty, IS 3589/2001 , ERW Straight Seam with all the fittings like Tees, Elbows, bends, reducers, spools etc. |
| 13 | ABOVE GROUND PIPELINE: Handling, Laying, Aligning, Cutting and Welding (3 runs min.) above ground / below ground pipelines from IOCL supplied old/new MS pipes (pipes to be supplied anywhere within the Location / Terminal / Depot and the contractor shall shift the same to the site of work at no extra cost to IOCL with all leads and lifts) of 200mm dia. as described below including cutting, beveling, fixing & welding the specials such as elbows, bends, tees, reducers, spools etc. complete and hydro testing the pipelines segments at 10.5 Kg / Sq. cm for a minimum period of 4 Hrs. The job also includes carrying out required repairs of pipe defects occurred during transportation, handling, testing etc. Item also includes supply, cutting, welding of Mild Steel required size & thickness of pad plate on pipeline at each support as per specifications/drg. In case of product pipeline, the job also includes D.P. test of the weld joints root run& 10% radiography of welded product pipeline joints to be done. Item also includes painting of pipeline as perpainting specification provided in scope of work of tender documents.Note: a)Welding & installation of supplied elbows, bends, reducers, tees, spools etc. shall be in the scope of the contractor andpayment shall be made as per running meter of pipeline only. b) For the sizes of piping of 100 mm and below, direct stub connection shall be made on the headers with suitable pad plates and the rate quoted should include the same. c).All hot/cold work shall be carried out with all required safety precautions as per OISD with required work permit & providing required temp. GI sheet fire screen at welding area. Before start of work required protective equipment, DCP, running fire water hoses with nozzles, sand scoop etc. to be positioned at work site issued by Terminal & required trained manpower to be positioned to run the same in case of any emergency. |
| 14 | Dismantling of existing MS piping by hacksaw cutting including fittingsand disposal of same at a preferred location as instructed by site engineer. Product evacuation if any, will be in IOCL\"s Scope, however flushing to make pipelines gas free shall be done by Contractor (water for flushing will be provided by IOCL).Pipeline to be cut and to be stacked properly in a length of 6.0 M. |
| 15 | 100 mm dia Pipe |
| 16 | 150 mm dia Pipe |
| 17 | 200 mm dia Pipe |
| 18 | Dismantling of existing valves and mating flanges, gaskets and stud / bolts and disposal of same at a prefered location as instructed by site engineer. |
| 19 | 100 mm dia Pipe |
| 20 | 150 mm dia Pipe |
| 21 | 200 mm dia Pipe |
| 22 | Fixing & commissioning of the supplied valves of the following sizes on the pipeline including supplying and fixing new 3 mm thick non metalic gaskets, studs / nuts etc. of approved make for the following sizes as per specifications and site instructions, complete in all respect. |
| 23 | 100mm dia. Butterfly valve |
| 24 | 150mm dia. Butterfly valve |
| 25 | 200mm dia. Butterfly valve |
| 26 | Supply of SORF flanges as per below |
| 27 | 25/32 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 28 | 40/50 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 29 | 80 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 30 | 100 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 31 | 150 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 32 | 200 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 33 | Supply of 200 mm Dia Blind Flange FCS BLRF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 34 | Welding of the supplied flanges on the pipelines with required 2-3 run, complete as per specification enclosed and direction of site engineer. |
| 35 | 100 mm dia Pipe |
| 36 | 150 mm dia Pipe |
| 37 | 200 mm dia Pipe |
| 38 | 25/32 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 39 | 40/50 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 40 | 80 mm Dia Flange CS SORF, B16.5 Class 150 RF ASTM 105, 125-250 RA Finish |
| 41 | Making flanged joints for both slip on and blind flanges including supplying and fixing 3 mm thick SW SS gaskets with graphite filler, studs / nuts etc. of approved make for the following sizes as per IOC specifications and site instructions. The rate quoted for the above items also include mechanical cleaning of the face. The flange joint shall also includes providing and fixing mukti strand copper strip/flat for bonding of product pipeline including provision of lugs. |
| 42 | 25/32 mm dia Pipe |
| 43 | 40/50 mm dia Pipe |
| 44 | 80 mm dia Pipe |
| 45 | 100 mm dia Pipe |
| 46 | 100 mm dia Pipe |
| 47 | 100 mm dia Pipe |
| 48 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets,depth upto 3m including getting out excavated material & returning the soil as required in not exceeding 20cm depth including consolidating each deposited layer by ramming,watering etc. & stacking serviceable material, disposing unserviceable material as directed, within or outside site at unobjectionable place IN ALL KIND OF SOILS, for Pipes,Cables etc. upto 80mm dia. |
| 49 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets,depth upto 3m including getting out excavated material & returning the soil as required in not exceeding 20cm depth including consolidating each deposited layer by ramming,watering etc. & stacking serviceable material, disposing unserviceable material as directed, within or outside site at unobjectionable place IN ALL KIND OF SOILS, forPipes, Cable etc. > 80mm < 300m dia |
| 50 | Excavation & Backfilling in All Types of Ordinary soil including filled soil, clay, Hard basalt bedrock etc upto 1.5 m depth below FGL/NGL: Excavation and backfilling around foundation and trenches/pits in all types of soil viz. earth, sand, gravel, clay, soft & hard murum, Asphalt, WBM etc. (excluding soft/hard rock) for footings, steps, plinth beams, equipment foundations, drains, trenches, manholes, underground tanks/pits, etc including shoring strutting, dewatering wherever required (until foundation work is complete). Item also includes carting, stacking if required, filling, Spreading, levelling and compacting / consolidating, disposal of surplus materials outside IOCL premises to an unobjectionable place following local rules or as per instructions of CONSULTANT/IOCL Engineer In Charge (Rate includes removal of any vegetation, small shrubs etc.). All Excavation Work has to be carried out Strictly as per Specification for Earthwork in Excavation. All kinds of soil upto depth of 1.5m. |
| 51 | Demolishing PCC / R.C.C. work in existing building structures at all heights and depths using pnuematic tools or chemicals or core cutter as approved by Engineer-in- charge including following all safety requirements, ensuring adequate precaution to the neighbourhood structures & equipment, putting necessary cover , stacking of reinforcement bars and disposal ofunserviceable material upto a lead of 1000 metres all complete as directed by Site Engineer. Note:- 1. Dismantling shall be allowed during day shift only & prior permission for the same shall be obtained. 2. Providing of necessary covers/barricades around the work area is to be done prior to dismantling operations. 3. Cutting of all reinforcement shall be done using hack saw or chisiel or any other method as approved byEngineer-in-charge. |
| 52 | Demolishing plastered/unplastered brick work in cement mortar at all heights and depths including following all safety requirements, ensuring adequate precaution to the neighbourhood structures & equipment, putting necessary cover, stacking of serviceable materials and disposal of unserviceable material up to a lead of 1000 metres all completed as directed by Site Engineer. Note:- 1. Dismantling shall be allowed during day shift only & prior permission for the same shall be obtained. 2. Providing of necessary covers/barricades around the work area is to be done prior to dismantling operations. |
| 53 | Dry stone pitching 22.5 cm thick including supply of stones and preparing surface, handset vertically in rectangular lines, interstices filled in with smaller stone chips including watering, compacting/consolidating & finishing to the required levels and lines etc with manual compaction etc complete as directed by Site Engineer. |
| 54 | HYSD Bars of Grade Fe 415 /500 TMT for reinforcement Supplying and placing in position High Yield Strength deformed TMT Bars conforming to IS: 1786, Fe415/500 for beams, slabs, columns, etc at all levels and locations of RCC work with all leads & lifts. including transporting the steel, straightening, cleaning, decoiling, cutting, bending to required shapes and lengths as per specifications, binding with Contractor\"s own 16 gauge SWG binding wire at every intersection, supplying and placing with proper cover blocks, supports, chairs, overlaps, spacers, etc. all complete as per Bar bending schedule approved by CONSULTANT/IOCL Engineer-in-Charge. Separate measurement will be made under this item for authorised laps only as per approval of IOCL/Consultant.All Reinforcement Work shall be carriedout Strictly as per Specification for Plain & Reinforced Cement Concrete. The weight of reinforcement shall be calculated as per theoretical weight given in standard steel table and wastage/ unauthorized overlaps/binding wires shall not be payable extra.Note: No extra payment towards the laps will be made and the rates quoted should include the same. |
| 55 | Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns, drains etc. for concrete. |
| 56 | Providing and laying inposition RCC 1 Cement :1½ Coarse Sand: 3 Graded Stone Aggregate 20mm ofreinforced concrete excluding thecostof centering,shuttering, finishing and reinforcement |
| 57 | Providing and laying inposition 1:3:6 (1 Cement : 3 fine sand : 6 graded stone aggregate 20 mm nominal size). ofplain cement concrete excludingthecostof centering,shuttering, finishing and reinforcement |
| 58 | Providing and laying cement concrete, grade of mix 1:2:4 (1 cement :2 coarsesand : 4 graded stone aggregate 20 mm nominal size), infoundation, floors, bed of drains, including ramming, de-watering, shuttering, shoring, strutting, curingetc. complete in all respects inclusive of cost of all labour, materials, tools, tackles etc. as per drawings, specifications and direction of Site Engineer. |
| 59 | 230 thk Brick Masonry in CM 1:4 Supplying & constructing 230 thk brick masonary walls using bricks of first class burnt clay (class 5.0 as per IS:1077, Compressive strength of Brick 50 kg/cm2) of approved source at all locations and levels with cement mortar (1:4) including scaffolding, racking of joints, watering, but excluding cement plaster finish complete as directed and instructed by IOCL/Consultant Engineer incharge. Brickwork shall be carried out strictly as per Specification for Brick Masonry Work. |
| 60 | Providing and applying external sand faced plaster 20mm thk consists of 12 mm thk in C.M. 1:4 first coat and 8 mm thk in CM 1 : 2 second coat to all RCC and masonry works at all locations and levels including required grain finishing, curing etc. complete as per specification and as directed and instructed by CONSULTANT / IOCL Engineer in charge. NOTE: The rates includes the cost of the base coat of not less than 12mm thk., external patta, drip moulds, curing and providing and fixing 200mm wide G.I. chicken mesh 26g thk. & 15mm mesh size at junctions of brick and RCC/PCC work etc. as well as providing and mixing waterproofing compound of approved make in both coats as per manufacturers specifications.Note: a) Hacking of RCC surfaces shall be done when the concrete is green in order to provide key to plaster.b) Plastering shall be done using 1 Kg of water proofing compound to every bag of cement used. c) The above cost includes the rates for making grooves, Plaster Band, Elevation Plaster Treatment & Etc in any shape & size in plaster or as directed by EIC. |
| 61 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 300 mm dia. R.C.C. pipe |
| 62 | Providing and laying non-pressure NP3 class R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc.complete: Medium Duty, Laying Mechanically/manual, 600 mm dia. RCC pipe |
| 63 | Providing and fixing double scaffolding system (cup lock type) on the exterior side, up to seven story height made with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineer- in-charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment will be made once irrespective of duration of scaffolding. |
| 64 | Supply & providing wrapping-coating of approved make on pipelines of various sizes, in underground excavated sections, inside culverts/RCC pipes, aboveground etc. as per site conditions and instructions of site-engineer. |
| 65 | Structural steel work inbuilt up sections/ framed workin gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cutting,hoisting,fixing in position & applying a priming coat of approved steel primer etc. as required. |
| 66 | Supply, cutting, Welding, Installation, Testing & Commissioning of class ‘C’ heavy duty MS pipe conforming to IS 1239 including fittings like elbows, tees, flanges, tapers, nuts bolts, gasket etc. and painting with two or more coats of synthetic enamel paint (after applying a coat of primer as per specifications) of required shade of Fire Red complete as required. The item also includes fully welded 200 mm saddle/pad plate of same pipe in 1/4th perimeter at bottom over supports. Structural steel required for pipeline support or laying on wall / ceiling or columns etc shall be paid under separate item. The connection/welding job of Sprinkler system with main hydrant line will also be part of this item, including required fittings, consumable, labour, materials etc. complete. |
| 67 | 100 mm Dia Pipe, Heavy Duty,IS 1239 Part 1/1990 , ERW Straight Seam |
| 68 | 150 mm Dia Pipe,Heavy Duty,IS 1239 Part 1/1990 , ERW Straight Seam |
| 69 | 200 mm DiaPipe Heavy Duty,IS 3589/2001 , ERW Straight Seam |
| 70 | Supplying ofbucket type strainers 500 mm dia pipeline Bucket Type Strainer as per enclosed specifications, including installation with required fittings, consumable, labour, materials etc. complete. |
| 71 | Supply & Installation of 150 mm dia Check Valve Dual Plate API 594 A 216 Gr. WCB CL 150 RFTBE Wafer Type between Flanges Trim 1 to API 594 602 ( 13 % Cr) AISI 410 Pin Inconel X750 Spmg 125-250 Ra Finish API 598. Confirming to BS 1868 including required fittings, consumable, labour, materials etc. complete. |
| 72 | Supply & Installation of 200 mm dia Check Valve Dual Plate API 594 A 216 Gr. WCB CL 150 RFTBE Wafer Type between Flanges Trim 1 to API 594 602 ( 13 % Cr) AISI 410 Pin Inconel X750 Spmg 125-250 Ra Finish API 598. Confirming to BS 1868 including required fittings, consumable, labour, materials etc. complete. |
| 73 | Supply of 25mm dia. thermal relief valve as perenclosed technical specifications including required fittings, consumable, labour, materials etc. complete. |
| 74 | CS Pipe Line Painting - Pipeline painting shall be with surface preparation SA-2½ by grit/slag blasting applying primer one coat of Zinc Ethyl Slicate (P1) (70-80 µ), undercoat one coat of 2 Pack Epoxy Polyamide MIO (U1)(120 µ) & finish coat two coat of 2 Pack Aliphatic Acrylic Polyurethane (F1) (40-50 µ each) total DFT to be 275 µ complete in all respect with required colour coding with synthetic enamel paint as directed by Site Engineer as per the specifications enclosed. The make and shade of paint shall be decided in consultation with IOC prior to use. Painting of all pipeline fittings shall be in the scope of the contractor andpayment of the same shall be made as per running meter of pipeline only. |
| 75 | 100 mm Dia Pipe, Heavy Duty,IS 1239 Part 1/1990 , ERW Straight Seam |
| 76 | 150 mm Dia Pipe,Heavy Duty,IS 1239 Part 1/1990 , ERW Straight Seam |
| 77 | 200 mm DiaPipe Heavy Duty,IS 3589/2001 , ERW Straight Seam |
| 78 | Part B - Fire Extinguishers |
| 79 | Supplying & commissioning of 75 Kg DCP trolley mounted Fire extinguisher of approved make,Conforming to IS15658, Body Carbon Steel as per IS:513, EDD grade with no vertical weld joint on the body Neck ring of seamless mild steel tube conforming to IS 1239 part-1, Valve assembly conforming to SS 316 grade or forged brass as per IS 6912 grade FLB, Inlet and outlet siphon tubes of SS 316 grade or of brass as per IS 407. Discharge nozzle of SS 316 grade of forged brass as per IS 6912, 5m long discharge hose of EDPM rubber, stainless steel safety Pin of SS 316 grade, Dry Chemical powder (potassium bi-carbonate & Minimum 90% of the total chemical), ISI marked CO2 Gas cylinder of 2 Kg. Min. jet length shall be 10m, dischanrge percentage of min.85% having min. discharge time of 50 seconds. Extinguisher shall have anticorrosive treatment of phosphating by hot dipping process to thickness not less than 0.012mm both internally & externally. Epoxy polyester powder coating of minimum 50 micron to all metallic external parts with two bands of yellow colored fluorescent adhesive tape of minimum 20mm thickness on body. Finish of the paint to be PO red as per shade 538 ofIS:5. Fire extinguisher shall be hydro tested at 30 Kgf/Sq.cm, test certificate shall be provided. |
| 80 | Supplying and fixing of 9kg DCP portable,cartridge type Fire extinguisher of approved make,Conforming to IS15683:2006, Body Carbon Steel as per IS:513, EDD grade with no vertical weld joint on the body Neck ring of seamless mild steel tube conforming to IS 1239 part-1, Valve assembly conforming to SS 316 grade or forged brass as per IS 6912 grade FLB, Inlet and outlet siphon tubes of SS 316 grade or of brass as per IS 407, Discharge nozzle of SS 316 grade of forged brass as per IS 6912, 500mm long discharge hose of EDPM rubber, powder coated wall mounting mild steel bracket,stainless steel safety Pin of SS 316 grade, Dry Chemical powder (potassium bi-carbonate & Minimum 90% of the total chemical), ISI marked CO2 Gas cartridge of 200 gms, dia of the body 175mm +/- 10mm & overall height less than 650mm.Extinguisher shall have anticorrosive treatment of phosphating by hot dipping process to thickness not less than 0.012mm both internally & externally. Epoxy polyester powder coating of minimum 50 micron to all metallic external parts with two bands of yellow colored fluorescent adhesive tape of minimum 20mm thickness of body.Finish of the paint to be PO red as per shade 538 ofIS:5. Fire extinguisher shall be hydro tested at 35 Kgf/Sq.cm, test certificate shall be provided. |
| 81 | Supply, installation & commissioning of UL listed Fire Hoses, 63mm dia. of approved make,both end GunMetal (1 male, 1 female) couplings for connection to hydrant valves and nozzle. Reinforced rubber lined canvas or Non-percolating synthetic fire hoses conforming to IS- 636/ UL 19 (Type A or B) UL listed. The length and diameter of the hoses should be 15 m and 63 mm respectively fitted with instantaneous type male and female couplings of material as specified in IS 636/UL 19. |
| 82 | Supply & Installation of double door type Mild Steel Hose Boxes with locking arrangement with key having glass on front doors, with provision to hold 2 no. hoses and 1 no. Jet nozzle in each box.Hose box shall have arrangement for mounting on steel strutucre / wall. 1 no. Jet nozzles to be supplied, shall be UL marked, painted with one coat of primer and two coats of syntheric enamel paint. Rate shall be inclusive of all labour, materials, consumables required for installation of Hose Box at designated place/ as per instruction of IOCL. |
| 83 | Supply & installation of pressure gauges of 150mm dial of approved make, 0-21 Kg/Sq. cm., Stainless steel body, ½” BSP, bottom entry. |
| 84 | Supply, installation & commissioning of UL / FM listed Water Monitors - including supplying and fixing 3mm thick gaskets/nuts/ studs, SS304 4mm thk Orifice plate to reduce the pressure as per design requirment and all other materials as per enclosed specifications and, as directed at site. Note: The fittings shall be cleaned by hand cleaning or wire brushing and painted as per IOCL painting Specification.The rates quoted should include the same. |
| 85 | Supply, installation & commissioning of UL / FM listed Double Headed Hydrant Valves having inlet 100mm with 2no. 63mm female outlets. Material shall be leaded tin bronze of IS:318 and SS as per IS: 3444 - including supplying and fixing 3mm thick gaskets/nuts/ studs, SS304 4mm thk Orifice plate to reduce the pressure as per design requirment and all other materials as per enclosed specifications and, as directed at site. Note: The fittings shall be cleaned by hand cleaning or wire brushing and painted as per IOCL painting Specification.The rates quoted should include the same. |
| 86 | Part C - Addressable Smoke detection with Fire alarm panel Work under Part C may required to be carried out from the Approved Licensed Agencies of Haryana Fire Services Department, having license for that work. |
| 87 | ADDRESSABLE 4 LOOP FIRE DETECTION ALARM PANEL - Supply, installation, testing & commissioning of Microprocessor based Intelligent and electronically addressable, modular,expandable, networkable, fire Alarm system panel for combined smoke detection system at Warehouse as well as office buildings. The panel shall have 4 loop capacity having distributed memory, the panel shall have LCD display unit, The panel shall have 240 volts AC power supply, automatic battery charger, 24 volts, sealed lead acid maintenance free batteries sufficient for 48 hours normal working and then be capable of operating the system for 15 minutes during emergency condition, capacity to store minimum 1000 history events. Panel shall have minimum 32 bit micro-processor; each loop should support at least 99 detectors & 99 devices. (Make : Morley Honeywell, Schrack,or equivalent) |
| 88 | Active Repeater -Supply, Installation, Testing and Commissioning of Active Repeaters at three positions – Location In Charge Cabin, warehouse office and Security cabin. Functions – Silence, Mute, reset, Accept, Evacuate and test controls. Should be compatible with the main Fire Alarm panel. The repeater panel shall duplicate all the audio-visual annunciations initiated at the main panel.Battery back up along with the charging facility as that of main panel shall be provided for uninterrupted operation for atleast 8 hours. (Make : Morley Honeywell, Schrack,or equivalent) |
| 89 | Supply, Installation, testing & commissioning of Intelligent Analogue Addressable optical smoke Detector with floating sensitivitycomplete with all accessories like base, base box, etc. to be installed in Office, warehouse. interconnecting to loop cable complete as required. (Make : Morley Honeywell, Schrack, or equivalent) |
| 90 | Multi sensor type Smoke Detectors - Supply, Installation, Testing and Commissioning of Addressable intelligent Multi sensor type smoke detectors along with mounting base for panel and electric room. (Make : Morley Honeywell, Schrack, or equivalent) |
| 91 | Heat Detectors - Supply, Installation, Testing and Commissioning of Addressable Heat detectors along with mounting base (Make : Morley Honeywell, Schrack, or equivalent) |
| 92 | Supply, Installation, testing & commissioning of Intelligent Analogue Addressable optical Beam Smoke Detector with Transmitter-Receiver & Reflectorcomplete with all accessories like base, base box, etc. to be installed under roof and concealed space, etc. interconnecting to loop cable complete as required. (Make : Morley Honeywell, Beam LRK, or equivalent) |
| 93 | Supply, Installation, testing & commissioning of Analogue Addressable strobes cum hoooters (conventional hooters + control module ) (Specification :- 110 cd light & 85 dB with adjustable DB)at different locations complete with all fixing accessories, etc under false ceiling roof, wall etc. interconnecting to loop cable complete as required. (Make : Morley Honeywell, Schrack, or equivalent) |
| 94 | Manual Call Points - Supply, Installation, Testing and Commissioning of addressable manual call points along with mounting back base complete with push button, enclosed in box with provision for cable or conduit coupling. The unit to be painted fire red outside, white inside. The unit shall be located near the exits/ staircase / strategic locations, should be wall mounted with break the galss/pull down cover type. The unit shall be addressable and communicate with main panel like other detectors. (Make : Morley Honeywell, Schrack, or equivalent) |
| 95 | Supply, Installation, Testing and Commissioning of Addressable intelligent type fault isolator module with LED indicator for isolating shorted, de-wired and loose circuits between two successive fault isolators with auto reset arrangement.(Make : Morley Honeywell, Schrack, or equivalent) |
| 96 | Response Indicators – Visual - Supply, Installation, Testing and Commissioning of visual indicators when the detector in that particular area/zone has been activated due to smoke of fire. The control room of the plant should be provided with separate visual alarm. (Make : Morley Honeywell, Schrack, or equivalent) |
| 97 | Response Indicator – Audio/Hooter - Supply, Installation, Testing and Commissioning of 1 Number of Hooter/ Siren for 1 km distance to be installed at the roof top of the plant.The alarm should be of horn cum strobe type and should be intelligent addressable with main panel. (Make : Morley Honeywell, Agni, Kheraj or equivalent) |
| 98 | Supply, Installation, Testing and Commissioning of Addressable Control Module. (Make : Morley Honeywell, Schrack,or equivalent) |
| 99 | Supply, Installation, Testing and Commissioning of Addressable Monitor Module. (Make : Morley Honeywell, Schrack,or equivalent) |
| 100 | Supply, Installation, Testing and Commissioning of LED base Emergency Exit signage with 3 hours battery backup etc. as required. (Make : ANG / Prolite / Autolite / MDS or equivalent). |
| 101 | Supply and Laying (Underground/on wall mounting/depending upon the location/path) along with proper protection of 2 Core x 1.5 Sqmm copper conductor FRLS armored red color cable along with clamping or on existing cable tray with clamping wherever required.The laying also includes the civil work wherever required. (Cable Make – Polycab or equivalent) |
| 102 | Part D - Automatic Sprinkler SystemWork under Part D may required to be carried out from the Approved Licensed Agencies of Haryana Fire Services Department, having license for that work. Party shall carry out design, engineering for the system, obtain approval from IOCL before carrying out the works as per BOQ & Scope of work of tender documents. |
| 103 | Supply, cutting, Welding, Installation, Testing & Commissioning of class ‘C’ heavy duty G Ipipe conforming to IS 1239 including fittings like internal threaded coupling suitable for sprinklers, elbows, bends, tees, flanges, tapers, half couplings, nuts bolts, gasket etc. fixing the pipe on the wall / ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint (after applying each primer as per specifications) of required shade of Fire Red complete as required. Item include providing required GI clamps/hooks/bolts & drilling required nos. holes in the structural support to fix the GI sprinkler as per design requirements. The item also includes fully welded 200 mm saddle/pad plate of same pipe in 1/4th perimeter at bottom over supports. Structural steel required for pipeline support or laying on wall / ceiling or columns etc. The connection/welding job of Sprinkler system with main hydrant line will also be part of this item. Contractor shall arrange boom lift & other equipments for ensuring safety during execution of this item. |
| 104 | 100NB |
| 105 | 65NB |
| 106 | 50NB |
| 107 | 40NB |
| 108 | 32NB |
| 109 | 25NB |
| 110 | Supply, cutting, laying GI pipe of 50 mm under Fire hydrant pipeline inlcuding tag welding, filling with concrete etc complete. |
| 111 | Supply, Installation,Testing, Commissioning of Hand Wheel Operated Gate Valves rising spindle type of following sizes on the pipeline including supply and fixing 3mm thk CAF gaskets, studs/ nuts, flanges, making flanges joint etc of approved make for the following sizes as per specifications and site instructions. |
| 112 | 200 mm dia |
| 113 | 100 mm dia |
| 114 | Supply, installation, testing and comissiong of 25 mm dia automatic air release valve with isolation valve, all acesories as required. |
| 115 | Supply, Installation, testing & commissioning of butterfly valve of 100 mm dia confirming to IS 13095 PN 16complete with CAF gasket, GI bolts, nuts washers etc as required. |
| 116 | Supply, Installation, testing & commissioning of butterfly valve of 200 mm dia confirming to IS 13095 PN 16complete with CAF gasket, GI bolts, nuts washers etc as required. |
| 117 | Supply,Installation,Testing, Commissioning of Ball valves of 25 NB on the pipeline including Supply and fixing 3mm thk CAF gaskets, studs/ nuts etc of approved make for the following sizes as per specifications and site instructions. |
| 118 | Supply, Installation, testing & commissioning of Deluge valve of cast steel/iron body and brass/ bronze working parts complete with all accessories, water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box ball valves, MS pipe of reqd. size, flanges, orifice plate, gasket etc. of size 100 mm dia as reqd. (UL listed / FM approved ) |
| 119 | Supply, Installation, testing & commissioning of Control valve of cast steel/iron body and brass/ bronze working parts complete with all accessories, water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box ball valves, MS pipe of reqd. size, flanges, orifice plate, gasket etc. of size 100 mm dia as reqd. (UL listed / FM approved ) |
| 120 | Supply, installation, testing & commissioning of Flow Switch of size : 150 mm dia (UL listed / FM approved ) |
| 121 | Supply, installation, testing & commissioning of Swing type wall mounting Fire Hose Reel conforming to IS:884 consisting of Red colour Powder coated metallic drum, 20 mm dia inlet, 20 mm dia x 30 m long high pressure nylon braided Rubber Hose Pipe as per IS: 444 or Thermoplastic Hose Pipe as per IS: 12585 with isolating valve and Brass/Bronze nozzle with chrome plated and other required accessories complete in all respect with Nuts/bolts for mounting on wall. The make may be of HD Fire, NewAge, SBJ, Safegaurd etc. |
| 122 | Supply, Installation, testing & commissioning of medium velocity open type 15 mm size sprinklers of brass/bronze with chrome plated of standard design having K-64 & 120 deg pattern with other accessories as required. The sprinklers shall be UL listed or FM approved. Sprinkler to be fitted with Teflon Tape and must be leak proof/leak tight. Contractor shall arrange boom lift & other equipments for ensuring safety during execution of this item. The make may be of NewAge, HD Fire, Spraysafe, Tyco, Viking etcThe work shall be carried out ina warehouse at all heights upto 14 M. |
| 123 | Supply, Installation, testing & commissioning of 15 mm size pendent/upright type sprinklers of brass/bronze with chrome plated of standard design having K-80, Quartzoid bulb of rating680 C, Standard Response (SR) with other accessories as required. The sprinklers shall be UL listed or FM approved. Sprinkler to be fitted with Teflon Tape and must be leak proof/leak tight. Contractor shall arrange boom lift & other equipments for ensuring safety during execution of this item. The make may be of NewAge, HD Fire, Spraysafe, Tyco, Viking etc. The work shall be carried out ina warehouse at all heights upto 14 M. |
| 124 | Supply, Installation, testing & commissioning of UL approved S S Braided flexible drops 25 mm dia capable to with stand maximum working pressure of 175 psi with all fittings for making connection to sprinklers and with the branches.1.2 mtr length. |
| 125 | Supply, Installation, testing & commissioning of S.S. Rossate plates suiatble for below false ceiling sprinkler - for office/cabin area. |
| 126 | Supply, Fabrication, Erection, Installation, Welding and Painting of all the steel structures for pipeline support as per drawings or instruction of Engineering In-charge.Item include cleaning of surface and painting with two coat of red oxide primer and two coats of synthetic enamel paint. |
| 127 | Supply, installation, testing and commissioning of pressure gauge of 100 mm dia , 0-21 kg/sq.cm range with 15 mm dia stop cock valve, tubing etc as required. |