| 1 | 1 | Taking down carefully aluminium point wiring for (light, fan, socket or power) with all fittings and fixtures such as switches, ceiling roses, pendents, regulators, sockets, light fittings, etc, removing materials to taking credit and making good disturbed surfaces of walls, ceilings, etc complete all as specified and directed by Engineer-In Charge. | | 173 | Point |
|---|
| 2 | 2 | Taking down carefully old deteroirated fittings & fixtures such as bulk head fittings, FTL fittings,wall light fittings including making good to the disturbed surfaces complete all as specified and directed by Engineer-In Charge. | | 76 | Each |
|---|
| 3 | 3 | M&L for Concealed conduit point wiring complete with FRLS PVC insulated, unsheathed cable 1100 V grade conforming to IS-694, 1.5 sqmm (nominal area) multi-stranded with metalic rigid PVC conduit medium grade not less than 20mm dia (ISI marked ) and conduit accessories fixed on MS terminal boxes made out of 16 guage mild steel sheet with hold fast flushed to wall with, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc, including provision of FRLS PVC insulated, unsheathed multistranded copper conductor of size 1.0 sqmm as earth dolly complete all as specified and directed for the following :- (Make of cable: Havells ISI Marked. Make of PVC conduit : Sudhakar ISI Marked.) \n(a) One light/exhaust fan &ceiling fan point controlled by one, one-way switch & one switch and regulator | | 119 | Point |
|---|
| 4 | 4 | (b) One 3 pin socket outlet 5 Amps, 230 volts on independent board | | 14 | Point |
|---|
| 5 | 5 | (c) One 3 pin socket outlet 5 Amps, 230 volts on same board | | 14 | Point |
|---|
| 6 | 6 | All as per item No. 3 above but with 2.5 Sqmm cable for one 3 pin 5/15 Amps switch socket outlet on independent board with copper conductor of size 1.5 Sqmm as earth continuity conductor complete all as specified and directed by Engineer-In Charge. | | 26 | Point |
|---|
| 7 | 7 | S & F, Switch Piano, flush type, single pole, one way, 5 Amps, 240 Volt complete all as specified and directed by Engineer-In Charge. \nMake : Anchor / Havells/Legrand | | 147 | Each |
|---|
| 8 | 8 | S & F switch Piano, flush type, single pole, one- way, 15 Amps, flush type, universal ISI marked complete all as specified and directed by Engineer-In Charge. Make : Anchor / Havells/Legrand | | 26 | Each |
|---|
| 9 | 9 | S & F stepped type electronic fan regulator, flush type complete all as specified and directed by Engineer-In Charge .Make : Anchor / Havells/Legrand | | 27 | Each |
|---|
| 10 | 10 | Supply and fixing ceiling rose surface, 65x20mm size three terminals ISI marked complete all as specified and directed by Engineer-In Charge. Make : Anchor / Havells/Legrand | | 119 | Each |
|---|
| 11 | 11 | S & F Socket outlet 2 in 1, 5 Amps, flush type, multi purpose universal fixed on the same board complete all as specified and directed by Engineer-In Charge. Make : Anchor / Havells/Legrand | | 28 | Each |
|---|
| 12 | 12 | S & F socket out let, 2 in 1, 5 and 15 Amps, flush type, universal ISI marked complete all as specified and directed by Engineer-In Charge. Make : Anchor / Havells/Legrand | | 26 | Each |
|---|
| 13 | 13 | S&F Bell Ding-Dong AC, 230 Volts, single pole, complete all as specified and directed by Engineer-In-Charge. | | 10 | Each |
|---|
| 14 | 14 | S&F Bell push piano single pole one way flush type 5 Amps, complete all as specified and directed by Engineer-In-Charge. | | 10 | Each |
|---|
| 15 | 15 | Supply and fix surface mouting LED luminairies 1x 18 watts, 230 volts, wall/ceiling mounted type suitable for mirror fittings with all internal connections connector block with all accessories and connecting up with and including twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed by Engineer-In Charge. Make : CG/Philips/Havells. | | 67 | Each |
|---|
| 16 | 16 | Supply and fix ceiling fan 1200mm sweep, three blades(White Colour) 5 star rating with downrod and canopies but without regulator suitable for working on 230 volts, 50 Hz single phase supply including provision of 3 core twisted copper conductor cable of suitable guage from ceiling rose to connector of ceiling fan complete all as specified and as directed [ Note : Old Fans are handedover to MES Office ,quated rates deemend to be included in quated rates] Make : Havells ES-40 or its equivalent crompton /bajaj/usha/indigo/ortem. | | 6 | Each |
|---|
| 17 | 17 | Taking down carefully wooden/MS boxes of any size and any pattern complete with all enclosures/ components includung making good to the disturbed surfaces complete all as specified and directed by Engineer-In Charge. | | 11 | Each |
|---|
| 18 | 18 | S & F sheet metal enclosure for SPN DB 12 way double door, 240 volts with 200 Amps rated bus bar, IP-43 protection, shrouded neutral bar, bus bar, cement spill protector complete all as specified and directed by Engineer-In Charge. Make : L&T/Scheinder/Legrand/Havells | | 10 | Each |
|---|
| 19 | 19 | S & F sheet metal enclosure for TPN DB 4 way double door with 200 Amps rated bus bar, IP-43 protection, Shrouded neutral bar & bus bar, cement spill protector, 415 volts complete all as specified and directed by Engineer-In Charge. Make : Scheinder/Legrand/Havells/C&S. | | 1 | Each |
|---|
| 20 | 20 | S & F MCCB 4 Pole, 100 Amps with fixed thermal magnetic release up to breaking capacity 25 KA frame N2, 415 volts conforming to IS:13947-2 and IEC: 6047-2 complete all as specified and directed by Engineer-In Charge. Make : Scheinder/Legrand/Havells/C&S. | | 1 | Each |
|---|
| 21 | 21 | S & F MCB, 4 Pole Isolator, 415 V, 63 Amps, 'C' serie, complete all as specified and directed by Engineer-In Charge. Make : Scheinder/Legrand/Havells/C&S. | | 3 | Each |
|---|
| 22 | 22 | S & F SPN, Isolator, 240 V, 40 Amps, 'C' serie, complete all as specified and directed by Engineer-In Charge. Make : Scheinder/Legrand/Havells/C&S. | | 10 | Each |
|---|
| 23 | 23 | S & F MCB, SP, 240 V, 6 to 32 Amps, 'C' serie, complete all as specified and directed by Engineer-In Charge. Make : Scheinder/Legrand/Havells/C&S,L&T. | | 80 | Each |
|---|
| 24 | 24 | M&L for sub main wiring with two runs of single core 1100 volts grade, FRLS PVC, insulated, unsheathed, multistranded copper conductor cable of size 4.0 Sqmm, drawn through and including non-metallic rigid PVC conduit 20mm dia and conduit accessories including provision of one run of FRLS PVC insulated 2.5 Sqmm multistranded copper earth continuity conductor in concealed wiring including taking down old sub main wiring complete all as specified and directed. [NOTE: 2 runs of 4.0 Sqmm cable, 1 run of 1.5 Sqmm cable and 1 run of PVC conduit shall be measured as one unit length.] | | 120 | RM |
|---|
| 25 | 25 | Supply and fixing of domestic exhaust fan with louver AC single phase 230/240 Volts 300 mm sweep, 70 watts, 1380 RPM speed, 1600 cu.mtr/Min transair, fan and making good distrubed surfaces and also provide suitable wire mesh in outer side complete all as specified and directed by Engineer-In-Charge. .Make : havells- Ventil Air - DS or its equivalent crompton /BAJAJ | | 6 | Nos |
|---|
| 26 | 26 | Supply & Fixing BLDG security light/ street light 20 watt LED fitting complete driver and suitable 40mm or 50mm dia GI mast or bracket arms and service cable with street light control and wall fixing accessories complete all as specified and directed . | | 9 | Each |
|---|
| 27 | 27 | M & L Complete overhauling the window type A/C's up to capacity 1.5 to 2TR and servicing with electric blower caustic soda and soap water to parts like condenser ,evaporator,and checking all electrical connections including refilling of gas required at site and replaceing the petty spares as required at site for the effective operation of the A/C's, complete all as specified and directed by Engr-in-Charge. all as directed by Engr-in-Charge. | | 3 | Each Job |
|---|
| 28 | 28 | M & L Complete overhauling the Split type A/C's up to capacity 2TR and servicing with electric blower caustic soda and soap water to parts like condenser ,evaporator,and checking all electrical connections including refilling of gas required at site and replacing the petty spares as required at site for the effective operation of the A/C's, complete all as specified and directed by Engr-in-Charge. all as directed by Engr-in-Charge. | | 6 | Each Job |
|---|
| 29 | 29 | M & L for repair/replacement of desert coolers to spare parts like 3 speed motor, water pump and checking/replace all electrical connections/regulators & control switches including replace of suitable grass pads as required at site for the effective operation of the coolers, complete all as specified and directed by Engr-in-Charge. all as directed by Engr-in-Charge. | | 5 | Each Job |
|---|
| 30 | 30 | Over hauling the Geyser of 25 Ltrs cap of any make by dismantling the geyser by removing from its position by disconnecting electric connection in let& out let water supply connections detecting the lekage by removing the copper vessel and rectifying by soldering testing, refixing inposition including replacement of necessary indication lamps elements minor components etc. all as directed. Note: Heating element, will be measured and paid seperately. | | 5 | Each |
|---|
| 31 | 31 | S&F thermostat including rubber/PVC gasket tube set to a temparature not higher than the range of 70 suitable 25/50 Ltrs cap Geyser. | | 4 | Each |
|---|
| 32 | 32 | M&L complete servicing to Exhaust fans like winding connections and painting if required and cleaning of old one fixing on same locations all as specified directed by engineer in charge | | 20 | Each |
|---|
| 33 | 33 | Dismantling of floor, hearth or wall tilling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises complete. | | 97 | Sqm |
|---|
| 34 | 34 | M&L for Coloured printed Non Skid ceramic tiles 7 to 8 mm thick (square/rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match complete all as specified and as directed (colour & design approved by Engr -in-Charge). | | 80 | Sqm |
|---|
| 35 | 35 | M&L for Coloured printed Glazed ceramic tiles on vertical surface 350 x 250 x 7 mm/450 x 350 x 7 mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match the colour of tiles complete all as specified and as directed (colour & design approved by Engr -in-Charge). | | 17 | Sqm |
|---|
| 36 | 36 | M&l 25 mm thick PCC floor type B-1:2:4(20 mm graded crushed stone aggregated) laid as backing complete all as specified and directed | | 80 | Sqm |
|---|
| 37 | 37 | M&L for screed bed or bedding layer, 15 mm thick in cement morter (1: 6) for laying tile/Kota stone on floor surface complete. | | 80 | Sqm |
|---|
| 38 | 38 | M&L for 10 mm thick plastered surfaces in 1:4 cement mortar, to receiving tiles/kota stone on vertical surfaces as specified as directed. | | 17 | Sqm |
|---|
| 39 | 39 | Taking down cement or cement lime plaster of any description on brick/stone or concrete surfaces etc including raking out joints,hacking for key and scrubbing down with water upto 4 storeys building complete all as specified and directed by Engineer-in-Charge. | | 240 | Sqm |
|---|
| 40 | 40 | M&L for rendering CM (1:6) 15 mm thick on fair faces of brick work or concrete surfaces or for laying floor finishes even and smooth without using extra cement | | 120 | Sqm |
|---|
| 41 | 41 | M&L for rendering CM (1:3) 5 mm thick on ceiling, soffits etc of brick work or concrete surfaces surface even and smooth without using extra cement. | | 100 | Sqm |
|---|
| 42 | 42 | M&L for 15 mm thick rendering on fair faces of brick work or cement concrete surfaces in cement mortar 1:4, finished fair and even without using extra cement incl mixing of water proofing compound complete all as specified. (Note: Water Proofing compound shall be measured and paid for separately) | | 80 | Sqm |
|---|
| 43 | 43 | Supply only water proofing compound | | 21.6 | Kg |
|---|
| 44 | 44 | Demolition of Brickwork or stone/boulder masonry, built in cement mortar including all quoins, arches, pillars,etc, but excluding ashlarfacings, dressed stonework and precast concrete articles. | | 7 | Cum |
|---|
| 45 | 45 | M&L for brick work with subclass 'B' bricks, straight or curved on plan exc 6 M mean radius built in CM 1:6 all as specified. | | 7 | Cum |
|---|
| 46 | 46 | Dismantling Asbestos cement (corrugated, semicorrugated, etc.) sheets in roof coverings | | 127.6 | Sqm |
|---|
| 47 | 47 | Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified | | 116 | Sqm |
|---|
| 48 | 48 | Pre- painted galvatume aluminum zinc coating GI based plain steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified | | 11.6 | Sqm |
|---|