| 1 | 1 | Excavation in trenches / foundation in soft / loose soil not exc. 1.5 metre wide and n'exc. 1.5 m deep for LT under ground cable / pole foundation and getting out including forming bottom surface to required level or slop, complete all as specified and directed by Engineer-in- Charge. | | 1455 | Cum |
|---|
| 2 | 2 | Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft / loose soil, complete all as specified and directed. | | 729 | Cum |
|---|
| 3 | 3 | Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed. | | 726 | Cum |
|---|
| 4 | 4 | Supply & spreading local sand obtained from ganga river in trenches for cable cushioning 8 cm under and 15 cm over the cable complete all as specified and directed. Note: Punned thickness shall be measured. | | 458 | Cum |
|---|
| 5 | 5 | Supplying and laid flat sub class 'B' bricks, old size, laid dry in trenches for the protection of U/G cable, complete all as specified and directed. | | 58000 | Per 1000 Nos |
|---|
| 6 | 6 | Supply and laying to wall or poles or fixing or passing through pipe, of 1100 volts grade heavy duty cable with XLPE insulated aluminium multistranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall PVC sheathed 6 sq. mm nominal cross section 2 core Including making good all distributed wall / flooring/tilling surfaces to match with existing specification complete all as specified and directed. Make: Gloster/Havells/ Paragon/ Grandlay/Finolex. \n | | 516 | RM |
|---|
| 7 | 7 | All as per srl item No 6 but cable of size 10 Sqmm 2 core. | | 176 | RM |
|---|
| 8 | 8 | All as per srl item No 6 but cable of size 25 Sqmm 2 core. | | 512 | RM |
|---|
| 9 | 9 | Supply laying , jointing, testing and commissioning of XLPE insulated, PVC sheathed, strip armoured heavy duty electric cable with aluminium conductor (stranded) working voltage upto 1100 volt confirming to IS 7098 Pt I in trenches, culvert, through pipe etc including connecting both end with proper size of aluminium lugs duly crimped with die press crimping device and cable gland complete all as specified and directed of the following sizes: Make: Gloster/Havells/ Paragon/ Grandlay/Finolex\n Note : 1.Cable laying and jointing are required to be carried out in short / long stretches as per site requirement\n2.Necessary excavation and earth work , sand cusioning, cable cover will be measured and paid separately. | | | |
|---|
| 10 | 9.01 | Size 16 sqmm, 4 core \n | | 2339 | RM |
|---|
| 11 | 9.02 | Size 25 sqmm, 3.5 core \n | | 2107 | RM |
|---|
| 12 | 9.03 | Size 35 sqmm, 3.5 core \n | | 1012 | RM |
|---|
| 13 | 9.04 | Size 50 sqmm, 3.5 core \n | | 968 | RM |
|---|
| 14 | 9.05 | Size 70 sqmm, 3.5 core \n | | 1464 | RM |
|---|
| 15 | 10 | Supply & laying in replacement of GI tubing of 50 mm bore dia , light grade conforming to IS 1239- Part-I and ISI marked in trenches, across the road, CI Pipe line, culvert etc of required length for cable protection complete all as specified and directed.Make: Jindal / Tata / Prakash Surya as approved by GE (I) | | 24 | RM |
|---|
| 16 | 11 | Supply & laying in replacement of GI tubing of 40 mm bore dia , light grade conforming to IS 1239- Part-I and ISI marked in trenches, across the road, CI Pipe line, culvert etc of required length for cable protection complete all as specified and directed.Make: Jindal / Tata / Prakash Surya as approved by GE (I) | | 140 | RM |
|---|
| 17 | 12 | Supply & fix of cable PVC insulated flexible aluminium conductor cable of size 1.5 Sqmm 3 core cut to pieces all as required for connetion with proper thimbles, drawn in existing/new GI or PVC pipe/in polefrom junction box to light fitting all as directed.Make: Gloster/Havells/ Paragon/ Grandlay/Finolex | | 699 | RM |
|---|
| 18 | 13 | Supply & fix rigid non-metallic PVC conduit of size 32 mm dia fixed on watch tower , exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Make of conduit : AKG/D-PLAST/FINOLEX/PLAZA | | 120 | RM |
|---|
| 19 | 14 | Supply and fix of High power LED flood light fitting 120 Watt IP 66 Energy saving & environmental friendly long life versatile pressure die-cast aluminium IP65 with high power LEDs as light source and electronic driver incl electric connection with 1.5 Sqmm multistranded twin core alum cable PVC insulated complete all as spfd. Make : Havells cat part no JETAIRISFLS 120WLED757APNBLT G / Bajaj cat part no BJFL 120W LED I / Wipro Cat part No LF20-132-060-57-G2 / C&S cat part no ORION-3.0/120W LTEF120WHPLED or equivalent of Philips as approved by GE. | | 8 | Each |
|---|
| 20 | 15 | Supply and installation, connecting eclectically & commissioning in replacement of LT feeder pillar box outdoor type of size 0.90 x 0.60 x 0.50 Mtr size factory fabricated made out of MS sheet of thickness 3.15 mm front door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr embedded in PCC blocks of size 0.30x0.30x0.50 mtr- 04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 200 amps rated copper bus bar suitable for 3 phase 4 wire supply system duly drilled holes and making all cable connection with proper thimbles mounted on epoxy based post insulators and one MCCB 100 Amps 4 pole 415 Volt, 35/36 KA of Make of MCCB : Legrand/ Schneider/Havells/L&T complete all as required at site. | | 1 | Each |
|---|
| 21 | 16 | S&F of bus bar chamber with MCB SP 6 Amps-01 No outdoor type of size nearest to 400 x 380 x 190 mm made out of MS sheet 3mm thick with alum bus bar three phase & neutral each nearest to 320 x 20 x 6 mm of size fixed on insulators and fixing on steel pole with proper clamps, nuts , bolts & washers of required size and making connection of LT cables with thimbles, glands and making good the disturbed surfaces incl water proof PVC sticker like danger mark all as required at site. | | 60 | Each |
|---|
| 22 | 17 | M & L of existing unserviceable LT panel, Installation, commissioning and testing of new LT panel cubical type suitable for outdoor installation factory made CPRI approved of suitable size , dust & vermin proof fabricated out of 3.15 mm thick CRCA sheet duly powder coated with cable entry & exit with suitable size of glands, terminals & thimbles all as specified , duly mounted on angle iron frame fixed on RCC/PCC block fixed with grounded bolts & nuts and washers including suitable rating copper bus bar 250 Amps for 3 phase 4 wire mounted on epoxy based post insulators, power factor meter of make AE/Legrand/L&T, LED indicator lamp set type RYB of make AE/Legrand/L&T, MCB DP 32 Amp-08 and suitable for one incoming MCCB 160 Amps 4 pole, one No 100 amps 4 pole MCCB's, two Nos 63 Amps 4 pole MCCBs as outgoing, Digital ammeter & voltmeter and wiring with suitable size of PVC copper cable of Make : Havells/L&T/strip complete and making good all disturbed surfaces of floor/wall using RCC/PCC work as required at site complete all as required at site or directed by Engr-in-Charge. ( Note: 1. MCCBs will be measured and paid separately under respective items) | | 1 | Each |
|---|
| 23 | 18 | S&F in replacement of MCCB 4 Pole 415 Volts 3 phase 160 Amps 35/36 KA, thermal magnetic release S1 -01 No (incoming). Make : Legrand/Siemens / Schneider /L&T/ABB /Indo Asian | | 1 | Each |
|---|
| 24 | 19 | All as per item No 18 but MCCB 100 Amps 25 KA. | | 1 | Each |
|---|
| 25 | 20 | All as per item No 18 but MCCB 63 Amps 25 KA. | | 2 | Each |
|---|
| 26 | 21 | Supply, fixing, testing and comissioning of automatic street light switch of capacity 5 KW in single phase using nature switch for automatic switching of street lights based on LUX level of natural light. The sensor (nature switch) along with suitable power contactor, MCB and support terminals enclosed in pole / wall mounted enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC junction box (Make: Sintex) conforming to IP54, including mounting arrangement with suitable size of FI clamps 02 Nos with complete acessories as under complete all as specified and directed. \n(i) Contactor rating single phase, 25 Amp :\n(ii) MCB 40Amps (SP),10 KA, 240 volts:\n(iii) NATURESWITCH-01 \n[Make: HEALER (Model No. SWADEEP - 02EC5KW1P) or equivalent make of Hansel/HPL/Indo Asian] | | 2 | Each |
|---|
| 27 | 22 | Supply and fix bus bar chambers factory febricated 400 mm long iron clad with 4 Nos 200 amp rated copper strips complete fixed flush wall and making good the disturbed wall surfaces to match with existing specification all as a required at site or directed. | | 7 | Each |
|---|
| 28 | 23 | M& L for Earthing complete with galvanised steel earth plate eletcrode of size 60x60cm x 6.0 mm thick electrode as buried directly in ground (earth pit not less than 2.25mtr below normal ground level connected to GI earth strip 32 mm x 6 mm thick by means of bolts nuts,check nuts and washers at complete etc all as shown in electrical plate No-3 of SSR part-1 connected to earthing test point all as specified or indicated including PCC pit in PCC(1:3:6) type CI cast iron frame 50mm thick pre cast RCC (1:1½ :3) nominal mix cover slab reinforced with 8mm dia mild steel bar including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc 50mtr and funnel with watering pipe light grade 20mm dia, wire mesh, GI protection pipe 40mm bore including testing complete all as specified and directed by Engineer-in-Charge. | | 3 | Each Job |
|---|
| 29 | 24 | S & F cable heat shrinkable outdoor terminal end joint, 1.1 KV grade, for suitable for XLPE 3.5 core LT cable of size 16 to 35 sqmm complete all as specified and directed.Make: Reychem/Dension/Birla 3 M | | 82 | Each |
|---|
| 30 | 25 | S & F cable heat shrinkable outdoor terminal end joint, 1.1 KV grade, for suitable for XLPE 3.5 core LT cable of size 50 to 95 sqmm complete all as specified and directed.Make: Reychem/Dension/Birla 3 M | | 16 | Each |
|---|
| 31 | 26 | Dismantling unserviceable insulators any type and taking down ACSR conductor, any size from HT/LT over head lines complete and remove from site all as specified and as directed by Engineer in charge. | | 23 | Qntl |
|---|
| 32 | 27 | Dismantling unsv insulators of any type complete and remove from site all as specified and as directed by Engineer in charge. . | | 391 | Each |
|---|
| 33 | 28 | Dismantling unsv cross-arms of M.S. channel or angle sections etc.and remove from site complete all as specified and as directed by Engineer in charge. . | | 9 | Qntl |
|---|
| 34 | 29 | Dismantling unserviceable stay assembly complete and remove from site all as specified and as directed by Engineer in charge. | | 4 | Each job |
|---|
| 35 | 30 | Dismantling unserviceable steel/PCC LT poles of any type complete and remove from site all as specified and directed by Engineer in charge. . | | 8 | Each job |
|---|
| 36 | 31 | S & F Mild steel cross arms, bracing, supports, clamps and back plates, fabricated from structural steel sections incuding nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated with a coat of red oxide primer, one under coat and one finshing coat of aluminium paint complete all as specified & directed by Engr-in Charge. | | 0.6 | Qntl |
|---|
| 37 | 32 | M & L for painting of steel pole (swan neck type or straight type) up to 9 mtr height with cross arms, clamp of any length and shape for LT overhead line / for street light with two coat of aluminium paint after scraping out old paint, cleaning and existing surface rust free, preparation of the existing surface, including marking pole numbers in a 20 cm dia yellow circle with number writting with black syenthic paint & painting strips in alternate from bottom to top with three strips of black syenthatic paint & two strips of yellow fluorescent paint (up to 1.5 mtr height) through out the circumference of pole (width of each strip shall be of 30 cm), complete all as specified and directed. | | 70 | Each job |
|---|