| 1 | 1 | Supply, fixing , testing & commissioning electric energy meter AC Single Phase, two Wire , tamper proof , static meter of class 1.0, 240V, 50Hz, 10A-60A capacity conforming to IS 13779 and relevant IEC standard and latest BIS standards with Optical & RS485 port with default and on demand display Instataneous data ( Cummulative KWH, Voltage, Current, Power factor & Frequency) and Daily Monthly Billing Data, Daily tamper Reports ( Such as Neutral Missing, Earth Leakage, Phase Reversal etc) with anti-tamper features as per IS 13779 , SMT based design , microprocessor & LED based circuitry, communication protocol as per IS 15959 with and including enclosure made from poly carbonatre for single phase energy meter wall mounted , single front , single door , fixed type , non compartmentalized for indoor / outdoor application with extra seal for wiring terminals complete all as specified and directed. \nNotes : (i). The rate quoted are deemed to be included cost of energy meter, all necessary E&M and civill work includibg T&P.\n(ii). All energy meter commissioning & execution to be done by original equipment manufacturer (OEM) engineer/technician.\n(iii). Warranty certificate,test certificate for a minimum of three years to be submitted after fixing of energy meter. The warranty of meter shall be irrespective of defect liability period and quoted rates shall be deemed to be included accordingly. The warranty of three year shall commence from actual date of completion.\n(iv) Old unserviceable energy meters retrived from site of any make /type/capacity shall be deposited to MES yard. Cost of the dismentaling, taking out including transporation deemed to be included in quoted rates.\n | | 817 | EACH JOB |
|---|
| 2 | 2 | Supply, fixing , testing & commissioning electric energy meter AC three phase, four Wire , tamper Proof , static meter of Class 1.0, 240V, 50Hz, 10A-60A capacity conforming to IS 13779 and relevant IEC standard and latest BIS standards with optical & RS485 port with default and on demand display Instataneous data ( cummulative KWH, Voltage, Current, Power factor & Frequency) and daily monthly billing data, daily tamper reports (such as neutral missing, earth leakage, phase reversal etc) with anti-tamper features as per IS 13779 , SMT based design , microprocessor & LED based circuitry, communication protocol as per IS15959 is acceptable with and including enclosure made from poly carbonatre for single phase energy meter wall mounted , single front , single door , fixed type , non compartmentalized for indoor / outdoor application with extra seal for wiring terminals including dismantling and taking out old unseviceable polycarboante/ metal enlcloser from site making good the disturded surfaces complete all as specified and directed. \nNotes : (i). The rate quoted are deemed to be included cost of energy meter, all necessary E&M and civill work includibg T&P.\n(ii). All energy meter commissioning & execution to be done by original equipment manufacturer (OEM) engineer/technician.\n(iii). Warranty certificate,test certificate for a minimum of three years to be submitted after fixing of energy meter. The warranty of meter shall be irrespective of defect liability period and quoted rates shall be deemed to be included accordingly. The warranty of three year shall commence from actual date of completion.\n(iv) Old unserviceable energy meters retrived from site of any make /type/capacity shall be deposited to MES yard. Cost of the dismentaling, taking out including transporation deemed to be included in quoted rates. | | 60 | EACH |
|---|
| 3 | 3 | M & L for sheet metal enclosure of CRCA sheet, wall mounted , single front , single door , fixed type , compartmentalized for outdoor application of size 600X600X450mm suitable for mounting two single/three phase energy meters with polycarbonate enclosure with and including MCCB TPN 63A 16kA, adjustable type as incomer and all incoming & outgoing cable shall be directly terminated on meter, outgoing cable shall be directly terminated on DBs, complete all as specified and directed. | | 2 | EACH |
|---|
| 4 | 4 | M & L for sheet metal enclosure of CRCA sheet, single front , single door , fixed type ,compartmentalized for outdoor application of size 900X900X 450mm suitable for mounting four single/three phase energy meters with polycarbonate enclosure with and including MCCB TPN 125A, 25kA adjustable type as incommer and all incoming & outgoing cable shall be directly terminated on meter, outgoing cable shall be directly terminated on DBs , complete all as specified and directed. | | 2 | EACH |
|---|
| 5 | 5 | M & L for sheet metal enclosure of CRCA sheet, single front , single door , fixed type, compartmentalized for outdoor application of size 1200X1200X 600mm suitable for mounting six single/three phase energy meters with polycarbonate enclosure with and including MCCB TPN 125A, 25kA adjustable type as incommer and all incoming & outgoing cable shall be directly terminated on meter, outgoing cable shall be directly terminated on DBs, complete all as specified and directed. | | 2 | EACH |
|---|
| 6 | 6 | Material and labour for sub main wiring with two single core, 6 sqmm, FRLS-H, 1100 volts grade, ISI marked, with multistranded, PVC insulated unsheathed copper conductor cable, drawn in and including rigid non metallic PVC conduit, medium grade, not less than 25 mm dia, ISI marked for housing cables, concealed in wall or ceiling including cutting chasing and making good, with accessories with and including one additional 6 sqmm, PVC insulated, stranded copper conductor, FRLS-H, green colour for earth continuity conductor connected to common earth dolly including taking down old unserviceable sub main wiring of any type and making good the disturbed surface complete all as specified and as directed.\nNote- Three runs of 6.0 sqmm cable and one run of concealed conduct shall be measured as one unit.\n | | 4500 | RUNNING METRE |
|---|
| 7 | 7 | Material and labour for sub main wiring with four single core, 10 sqmm, FRLS-H, 1100 volts grade, ISI marked, with multistranded, PVC insulated unsheathed copper conductor cable, drawn in and including rigid non metallic PVC conduit, medium grade, not less than 32 mm dia, ISI marked for housing cables, concealed in wall or ceiling including cutting chasing and making good, with accessories with and including one additional 10 sqmm, PVC insulated, stranded copper conductor, FRLS-H, green colour for earth continuity conductor connected to common earth dolly including taking down old unserviceable sub main wiring of any type and making good the disturbed surface complete all as specified and as directed.\nNote- Five runs of 10 sqmm cable and one run of concealed conduct shall be measured as one unit.\n | | 350 | RUNNING METRE |
|---|
| 8 | 8 | Note:- Amount of credit of Rs.30,500.00 for retrieved materials is mentioned in Schedule of Credit Page No. 17 of tender documents in pdf form which will be deducted offline while acceptance of tender. | | | |
|---|