| 1 | 1.01 | Laying of one No. cable above 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed | BI01010001010000000000000515BI0100001113 | 197 | Mtr |
|---|
| 2 | 2.01 | Supply and Delivery of 1.1 K.V grade 4 core 300 sq. mm. XLPE/A Alu. Cable . As per choice of EIC | BI01010001010000000000000515BI0100001115 | 197 | Mtr |
|---|
| 3 | 3.01 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required A) 80 mm dia | BI01010001010000000000000515BI0100001116 | 20 | Mtr |
|---|
| 4 | 4.01 | Supply & Delivery of 10 mtr Length steel tubular pole and painting depth 1.8 mtr havingthe following minimum specfication 410 SP 42 ,weight 144kg thickness of base plate 20mm bottom section length is 5.20mtr.Middle section length is 2.40 mtr. Bottom Dia 139.70mm ,middle dia 114.30mm,top dia 88.90mm ,bottom thickness 5.40mm thickness,middle thickness 4.50mm ,top thickness 3.25mm. Supply & Fixing circular shaped(4ft Dia) housing/Header on Existing S.T pole for holding of 6Nos LED Flood light made by 40mm G.I Pipe,centre cap of the circular header should be made by 100mm dia 300mm length M.S medium pipe as per direction of the E.I.C including Two coat alluminium painting of 9mtr pole ,header and loop box after two coat primer | BI01010001010000000000000515BI0100001119 | 1 | Each |
|---|
| 5 | 5.01 | Supply & Fixing circular shaped(4ft Dia) housing/Header on Existing S.T pole for holding of 6Nos LED Flood light made by 40mm G.I Pipe,centre cap of the circular header should be made by 100mm dia 300mm length M.S medium pipe as per direction of the E.I.C including Two coat alluminium painting of 9mtr pole ,header and loop box after two coat primer | BI01010001010000000000000515BI0100001121 | 1 | Each |
|---|
| 6 | 6.01 | Supply & Fixing LED Flood Light,cold temperature cool white, Nominal Voltage 240V AC, 50HZ,System Efficiency >80lm/W,with Gear integrated electronic Driver Protection IP 65/66,Class I (Make: Philips BVP120LED 72W) | BI01010001010000000000000515BI0100001124 | 4 | Each |
|---|
| 7 | 7.01 | Supplying & Fixing GI waterproof type looping cable box size 200x200x100 mm deep having 4 mm thick comprising of one 240 V 40 A DP Isolator(Legrand), 4 Nos 6Amp SPMCB(Legrand), one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint | BI01010001010000000000000515BI0100001131 | 1 | Each |
|---|
| 8 | 8.01 | Erection of single steel tubuler pole of length as given below with/without sole plate & cap etc. in CC foundation(Portion and dimension indicated below),having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal indicating CC (6 ;3;1)muffing 0.30 mtrs dia and0.30mts above ground level including 3mm thick neat cemented finish and GI earth bolt after makingdrillings holes etc on pole &carriage of pole upto 1.6km from store to work site including filling upto excavatied earth pit with shifted soil and ramming properly.Above 9.0 mtr size 0.6x0.6x 1.91 mtr. | BI01010001010000000000000515BI0100001135 | 2 | Each |
|---|
| 9 | 9.01 | Fixing outdoor type fluorescent/SV/MV light fitting on pole including S&F 40 mm dia x 1.68 mts. long GI Pipe (ISI-Medium) bracket with 40 mmx10 mm thick, MS clamp etc. and providing wiring with 2x1/1.40 PVC insulated and sheathed wire (single core) from loop box at the base of pole to light fiting through pole & bracket (without control switch) including making connections & painting . with GI Loop box | BI01010001010000000000000515BI0100001136 | 4 | Set |
|---|
| 10 | 10.01 | Supply & Erection of 80mm dia 2Mtr long GI(ISI-Medium) mini Pole with suitable size sole plate on the roof top of the building with necy.Drilling tapping and GI nut bolt for e/a and connecting wire entry hole incl making C.C muffing 2ft x2ftx 2.5ft in size by cement morter (6:3:1) incl neat cement finish(Without loopbox) as per direction of E.I.C | BI01010001010000000000000515BI0100001139 | 4 | Each |
|---|
| 11 | 11.01 | Supply, installation, testing of 240V; 90W LED type out door fitting on wall/ pipe pole and making necessary connection as per direction of E.I.C. ( Make: Crompton LSTP-90-CDL-1 ) the following fittigs installed by scaffolding arrangement as per direction | BI01010001010000000000000515BI0100001140 | 4 | Set |
|---|
| 12 | 12.01 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting | BI01010001010000000000000515BI0100001141 | 115 | RM |
|---|
| 13 | 13.01 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below\n2 core 10 Sq mm | BI01010001010000000000000515BI0100001143 | 10 | Each |
|---|
| 14 | 14.01 | Finishing the end of following XLPE/PVC armoured cables by crimping method including the supply & fixing solderless socket (Dowels make), tapes anti corrosive paste & jointing material.\n2 core 10 Sq mm | BI01010001010000000000000515BI0100001145 | 10 | Set |
|---|
| 15 | 15.01 | Supply &Installation ,commissiong of outdoor type dust and moisture proof feeder piller FDB made with 5mm top ms plate & 3mm in all sides having 1500mm x 1350mm x450 mm size both side door with cable alley with 5mm thick backite sheet base for fixing nylon base, kit kut etc incl 2 coats of synthetic enamel paint over one coat of R.O primer duely welded on 75 x40 x6mm MS channel (as foundation) frame. The foundation should make extra height at about 0.60mt above ground level and 0.45 mt below the ground by C.C foundation(4:2:1) work including plastering and neat cement finish.The FDB should be comprising with the following materials as per direction of E.I.C \nIncoming: A)415V ,630Amp TPNSFU MAIN Switch (L&T) With 3 nos Din type HRC fuse------------1 nos B) B))800A, 500V; 4bar copper busbar....... Outgoing: a)315 A rating 415V,TPN SFU with HRC fuse(Open Execution)....2Nos b)250A rating 415V,TPN SFU with HRC fuse(Open Execution).......3Nos f)LED indication lamp with fuse base &HRC fuse -----3Nos g)Danger Notice Board 6\"x8\"/20cm x30cm -------1No | BI01010001010000000000000515BI0100001146 | 1 | Job |
|---|
| 16 | 16.01 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S &F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below.A) By ISI-Medium GI pipe | BI01010001010000000000000515BI0100001148 | 4 | Set |
|---|
| 17 | 19.01 | Add 12% GST | BI01010001010000000000000515BI0100001184 | 1 | Item |
|---|
| 18 | 20.01 | Add 1% Labour Welfare Cess | BI01010001010000000000000515BI0100001185 | 1 | Item |
|---|