Assistance In Carrying Out Miscellaneous Routine Works For Preventive Maintenance Of Different Substations Under 220Kv Oandm Division , Ptcul , Pantnagar , Electrical Items : , Assistance In Electrical Preventive Maintenance Of 220Kv Substation , Pantnagar Consisting Of 2X160 Mva ( 220/132Kv ) Transformers , 2X80 Mva ( 132/33Kv ) Transformers , 2X50 Mva ( 220/33Kv ) Transformers , 2X630 Kva ( 33/0 . 4Kv ) Transformers , 11 Nos . 220Kv Bays , 08 Nos . 132Kv Bays And 21 Nos . 33Kv Bays 132Kv Substation , Kichha Consisting Of 2X40 Mva ( 132/33Kv ) Transformers , 1X250 Kva ( 33/0 . 4Kv ) Transformers , 10 Nos . 132Kv Bays And 10 Nos . 33Kv Bays 132Kv Substation , Rudrapur Consisting Of 2X40 Mva ( 132/33Kv ) Transformers , 1X20 Mva ( 132/33Kv ) Transformer , 06 Nos . 132Kv Bays And 10 Nos . 33Kv Bays . ( I ) Routine Visual Checking Of Red Hot Points , Flashpoints , Burned Jumpers Etc . In 220Kv , 132Kv & 33Kv Switchyards . General Routine Maintenance Of Outdoor Equipments/Panels In 220Kv , 132Kv & 33Kv Switchyards I . E . Cbs , Isolators , Bus Bars , Cts , Pts/Cvts , Marshalling Kiosks Etc . Including Scheduled Cleaning , Lubrication , Tightening Of Connections/Jumpers , Replacement Of Minor Damaged Parts Of Equipments , Replacement Of Jumpers/Clamps/ Connectors Etc . ( Ii ) Routine Work On All Power And Station Transformers , Maintenance Of Their Cooling Fans , I . E . Oiling , Greasing , Cleaning Etc . Lt Electrical Connection , Cleaning Of Oil Collection Pits , Tightening Of Loose Connection , Replacing Silicagel , Provides Help In Oil Top Up As Per Direction Of Engineer In Charge . ( Iii ) Routine Checking Of Complete Length Of Control Cable And Power Cable Between Indoor Panels/Equipment And Outdoor Equipment/Kiosks/Panels , Cleaning Replacement Of Damaged/Burned Cable , Tightening And Replacement Of Damaged Terminals/ Connections/Lugs Etc . Referruling Whenever Required . ( Iv ) Routine Maintenance Of Battery Cells And Battery Chargers I . E . Daily Cleaning Of Battery Room And Battery Cells , Maintaining Fluid Level , Specific Gravity , Applying Of Petroleum Jelly Etc . Complete In All Respect . ( V ) Routine Maintenance Of Indoor Panels In Control Panels In Control Room And Plcc Room I . E . Control And Relay Panels . Acdb & Dcdb System , Indoor Transformers , Indoor & Outdoor Illumination System Etc . Including Scheduled Cleaning , Lubrication , Tightening Of Connection/Terminals , Replacement Of Minor Damaged Parts Of Panels , Tracing Of Circuit Etc . As Per Direction Of Engineer In Charge . ( Vi ) Any Other Routine Substation Electrical Maintenance Related Works Assigned By Engineer In Charge As And When Required . At 220Kv S/S , Pantnagar 01 No . Operation Signifies Deployment Of 02 Skilled And 04 Semi-Skilled Manpower For A Period Of 08 Hours . At 132Kv S/S , Kichha And 132Kv S/S , Rudrapur Signifies Deployment Of 01 Skilled And 02 Semi-Skilled Manpower For A Period Of 08 Hours . Total Operations At 220Kv S/S , Pantnagar:- 280 ( Rate Rs . 4313 . 20 Per Operation ) Total Operations At 132Kv S/S , Kichha:- 215 ( Rate Rs . 2156 . 60 Per Operation ) . Total Operations At 132Kv S/S , Rudrapur:- 207 ( Rate Rs . 2156 . 60 Per Operation ) . , Mccb 3Ph 415V/230V 65Amps Thermal Release 25A-50A , Ml6 Contractor 230V Ac ( 2No+2Nc ) Or Equilant