Assistance In Carrying Out Miscellaneous Routine Works For Preventive Maintenance Of Different Substations Under 220Kv Oandm Division , Ptcul , Haldwani , Electrical Items : , Assistance In Electrical Preventive Maintenance Of 220Kv Substation , Haldwani , 132Kv Substation , Kathgodam And 132Kv Substation , Bhowali By Carrying Out Following Miscellaneous Work On Routine Basis And With Round The Clock Availability Of Manpower . At 220Kv Substation , Haldwani:- 2X100 Mva ( 220 / 132Kv ) Transformers , 2X40 Mva ( 132 / 33Kv ) Transformers , 04 Nos . 220Kv Bays , 08 Nos . 132Kv Bays , 11 Nos . 33Kv Bays , 2X250 Kva ( 33 / . 44Kv ) Substation Transformer And 2X5 Mvar Capacitor Bank . At 132Kv Substation , Kathgodam:- 2X40 Mva ( 132 / 33Kv ) Transformers , 630Kva ( 33 / . 44Kv ) Substation Transformer , 06 Nos . 132Kv Bays And 07 Nos . 33Kv Bays . At 132Kv Substation , Bhowali:- 20 Mva ( 132 / 33Kv ) Transformer , 3X5 Mva Transformers , 2X250 Kva ( 33 / . 44Kv ) Substation Transformer , 05 Nos . 132Kv Bays , 08 Nos . 33Kv Bays And 2X2 . 5 Mvar Capacitor Bank . A ) Routine Visual Checking Of Red Hot Points , Flashpoints , Burned Jumpers Etc . In 220Kv , 132Kv & 33Kv Switchyards . General Routine Maintenance Of Outdoor Equipments / Panels In 220Kv , 132Kv & 33Kv Switchyards I . E . Cbs , Isolators , Bus Bars , Cts , Pts / Cvts , Marshalling Kiosks Etc . Including Scheduled Cleaning , Lubrication , Tightening Of Connections / Jumpers , Replacement Of Minor Damaged Parts Of Equipments , Replacement Of Jumpers / Clamps / Connectors Etc As Per Direction Of Engineer In Charge . B ) Routine Cleaning Of All Transformers , Maintenance Of Cooling Fans I . E . Oiling , Greasing , Cleaning Etc . , Lt Electrical Connections , Cleaning Of Oil Collection Pits , Tightening Of Loose Connections As Per Direction Of Engineer In Charge . C ) Routine Checking Of Complete Length Of Control Cables And Power Cables Between Indoor Panels / Equipments And Outdoor Equipments / Kiosks / Panels , Cleaning , Replacement Of Damaged / Burned Cables , Tightening & Replacement Of Damaged Terminals / Connections / Lugs Etc . Whenever Required . D ) Routine Maintenance Of Battery Cells And Battery Chargers I . E . Daily Cleaning Of Battery Room & Battery Cells , Maintaining Fluid Level , Specific Gravity , Applying Of Petroleum Jelly Etc . Complete In All Respect . E ) Routine Maintenance Of Indoor Panels In Control Room And Plcc Room I . E . Control & Relay Panels , Acdb & Dcdb System , Indoor Transformers , Indoor & Outdoor Illumination System Etc . Including Scheduled Cleaning , Lubrication , Tightening Of Connections / Terminals , Replacement Of Minor Damaged Parts Of Panels , Tracing Of Circuits Etc . As Per Direction Of Engineer In Charge . F ) Any Other Substation Electrical Maintenance Related Routine Works Assigned By Engineer Incharge As And When Required . At 220Kv S / S , Haldwani 01 No . Operation Signifies Deployment Of 02 Skilled And 04 Semi-Skilled Manpower For A Period Of 08 Hours . At 132Kv S / S , Kathgodam And 132Kv S / S , Bhowali Signifies Deployment Of 01 Skilled And 02 Semi-Skilled Manpower For A Period Of 08 Hours . Total Operations At 220Kv S / S , Haldwani:- 300 ( Rate Rs . 4028 . 00 Per Operation ) Total Operations At 132Kv S / S , Kathgodam:- 300 ( Rate Rs . 2014 . 00 Per Operation ) . Total Operations At 132Kv S / S , Bhowali:- 300 ( Rate Rs . 2014 Per Operation ) . , Mccb 3Ph 415V / 230V 65Amps Thermal Release 25A-50A , Ml6 Contractor 230V Ac ( 2No+2Nc ) Or Equilant