| 1 | 1 | Selection of site by means of electronic testing device or any other method to find out the availability of underground water inside the hospital premises for the guaranteed water discharge through the proposed bore well. Providing water logging test with electro-logging equipment and required machinery for ascertaining/ logging aquifers encountered in bore well and arranging and defining the water availability test giving test report of geo-hydrologist from govt. approved laboratories recommending water bearing zones, TDS of water etc., measuring of yield by V notch or other method after sinking of borewell and registration in respective department complete as directed by ESIC Engineer-in-charge. | BI01010001010000000000000515BI0100001113 | 1 | Nos |
|---|
| 2 | 2 | Boring/ drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. | BI01010001010000000000000515BI0100001155 | | |
|---|
| 3 | 2.01 | All types of soil 300 mm dia\n | BI01010001010000000000000515BI0100001115 | 50 | metre |
|---|
| 4 | 2.02 | Rocky strata including Boulders 300 mm dia\n | BI01010001010000000000000515BI0100001156 | 50 | metre |
|---|
| 5 | 3 | Supplying, assembling, lowering and fixing in vertical position in borewell, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. | BI01010001010000000000000515BI0100001157 | | |
|---|
| 6 | 3.01 | 150 mm nominal size dia | BI01010001010000000000000515BI01000011119 | 50 | metre |
|---|
| 7 | 3.02 | 200 mm nominal size dia | BI01010001010000000000000515BI0100001150 | 50 | metre |
|---|
| 8 | 4 | Supplying, assembling, lowering and fixing in vertical position in borewell strainer pipes with ribs,conforming to IS: 12818, including hire & labour charges, fittings &accessories etc. all complete, for all depths, as per direction of Engineer-in-charge: 150 mm dia | BI01010001010000000000000515BI0100001120 | 20 | metre |
|---|
| 9 | 5 | Supplying, assembling, lowering and fixing in vertical position in bore well UPVC column pipe for submerssible borewll pump safe pulling heavy duty pipe, conforming to IS: 12818, including labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 40 mm nominal size dia\n | BI01010001010000000000000515BI0100001121 | 50 | metre |
|---|
| 10 | 6 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge | BI01010001010000000000000515BI0100001122 | 10 | Cum |
|---|
| 11 | 7 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 200 mm dia | BI01010001010000000000000515BI0100001123 | 1 | Nos |
|---|
| 12 | 8 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 200 mm clamp | BI01010001010000000000000515BI0100001125 | 1 | Nos |
|---|
| 13 | 9 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). 200 mm dia | BI01010001010000000000000515BI0100001126 | 1 | Nos |
|---|
| 14 | 10 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. 65 mm nominal outer dia pipe | BI01010001010000000000000515BI0100001127 | 50 | metre |
|---|
| 15 | 11 | Three phase Submersible motor pump set (Texmo / Crompton Greaves/ Aquatic/ CRI/ V-Guar suitable for 100 mm bore well and above. 7.5 HP STAGE 40/ 50 with MCB controlled Submersible motor pump set control panel. The above rate inclusive of control panel and SITC complete in all respect as per the direction of Engineer-in-charge. | BI01010001010000000000000515BI0100001130 | | |
|---|
| 16 | 11.01 | Submersible moto pump | BI01010001010000000000000515BI0100001131 | 1 | Nos |
|---|
| 17 | 11.02 | Control Panel | BI01010001010000000000000515BI0100001114 | 1 | Nos |
|---|
| 18 | 12 | Providing & laying of 3 core 4mm2 flat submersible pump cable with copper wire of electrolyte grade conducror confirming to general specification as per IS 694latest edition fro submerssiblle pump to electric panel including water proofing cable joit as per requirementas per direction of engineer in charge | BI01010001010000000000000515BI0100001158 | | |
|---|
| 19 | 12.01 | TPN Switch | BI01010001010000000000000515BI0100001159 | 1 | Nos |
|---|
| 20 | 12.02 | Flat Cable | BI01010001010000000000000515BI0100001117 | 1 | 50 metre |
|---|
| 21 | 12.03 | Normal Cable | BI01010001010000000000000515BI0100001118 | 1 | 50 metre |
|---|
| 22 | 13 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer-in-charge. 50 mm nominal outer dia Pipes | BI01010001010000000000000515BI0100001119 | 50 | metre |
|---|