| 1 | 1 | SCHEDULE 'A' | | | |
|---|
| 2 | 2 | M & L for servicing of indoor unit of split type AC of 1.5/2.0/3.0 ton capacity of any make by air blowing, cleaning the filter in water and drying in sun, cleaning of drain tray and rectifying water leak, checking and tightening the electrical connection complete all as specified and directed. | | 275 | Job |
|---|
| 3 | 3 | M & L for servicing of outdoor unit of Split type AC of 1.5/2.0/3.0 ton capacity of any make by compressed air and water washing and oiling of oudoor fan motor, checking and tightening of all the electrical connections, nuts, bolts, washers complete all as specified and directed. | | 275 | Job |
|---|
| 4 | 4 | M & L for servicing of indoor unit of inverter type split AC of 1.0/1.5/2.0 ton capacity of any make by air blowing, cleaning the filter in water and drying in sun, cleaning of drain tray and rectifying water leak, checking and tightening the electrical connection complete all as specified and directed. | | 30 | Job |
|---|
| 5 | 5 | M & L for servicing of outdoor unit of inverter type split AC of 1.0/1.5/2.0 ton ton capacity of any make by compressed air and water washing and oiling of oudoor fan motor, checking and tightening of all the electrical connections, nuts, bolts, washers complete all as specified and directed. | | 30 | Job |
|---|
| 6 | 6 | M & L for preparation of old painted surface of outdoor unit of Split type AC of 1.5/2.0/3.0 ton capacity of any make and applying one coat of synthetic enamel paint in position complete all as specified and directed. | | 25 | Job |
|---|
| 7 | 7 | Supply and charge R-407 for central AC plant of 3x26 TR and Package type AC plant of 6x10 TR capacity after leak testing and rectification of leak complete all as specified and directed. | | 25 | Kg |
|---|
| 8 | 8 | Supply and charge R-410 for inverter type split type AC of 1.0/1.5/2.0 ton capacity after leak testing and rectification of leak complete all as specified and directed. | | 20 | Job |
|---|
| 9 | 9 | Supply and charge R22/R134a gas to refrigerator of 165 Ltrs to 250 Ltrs capacity after leak testing and rectification of leak complete all as specified and directed. | | 5 | Job |
|---|
| 10 | 10 | Supply and charge R22/R134a gas to refrigerator of 280 Ltrs to 430 Ltrs capacity after leak testing and rectification of leak complete all as specified and directed. | | 3 | Job |
|---|
| 11 | 11 | Supply and charge R22/R134a gas to water cooler of 40/80 Ltrs per hour capacity after leak testing and rectification of leak complete all as specified and directed. | | 5 | Job |
|---|
| 12 | 12 | Supply and charge R22/R134a gas to deep freezer of 205/405 Ltrs capacity after leak testing and rectification of leak complete all as specified and directed. | | 2 | Job |
|---|
| 13 | 13 | Supply and charge R22/R134a gas to window type AC of 1.5 Ton capacity after leak testing and rectification of leak complete all as specified and directed. | | 10 | Job |
|---|
| 14 | 14 | Supply and charge R22/R134a gas to split type AC of 1.5 Ton capacity after leak testing and rectification of leak complete all as specified and directed. | | 160 | Job |
|---|
| 15 | 15 | Supply and charge R22/R134a gas to split type AC of 2.0 Ton capacity after leak testing and rectification of leak complete all as specified and directed. | | 15 | Job |
|---|
| 16 | 16 | Supply and charge R22/R134a gas to split type AC of 3.0 Ton capacity after leak testing and rectification of leak complete all as specified and directed. | | 10 | Job |
|---|
| 17 | 17 | S & F of capillary & strainer suitable for refrigerator including taking down of any capacity and testing complete all as specified and directed. | | 5 | Job |
|---|
| 18 | 18 | S & F of capillary & strainer suitable for inverter type split AC and split type AC of of 1.0/1.5/2.0 ton capacity including taking down and testing complete all as specified and directed. | | 50 | Job |
|---|
| 19 | 19 | M & L for servicing of refrigerator of capacity 165 to 430 Ltrs by air blowing, cleaning of condensor coil, rubber beading & checking and tightening the electrical connection complete all as specified and directed. | | 15 | Job |
|---|
| 20 | 20 | M & L for servicing of water cooler of capacity 40/80 ltrs by air blowing, cleaning of condensor coil, checking and tightening the electrical connection complete all as specified and directed. | | 25 | Job |
|---|
| 21 | 21 | M & L for preparation of old painted surfaces of refrigerator of capacity 165 to 250 Ltrs by scrapping old paint, removing rust, making the surface even and smooth and applying two coats of synthetic enamel paint of approved colour by spray painting over a coat of red oxide primer complete all as specified and directed. | | 15 | Job |
|---|
| 22 | 22 | M & L for preparation of old painted surfaces of water cooler of capacity 40/80 Ltrs by scrapping old paint, removing rust, making the surface even and smooth and applying two coats of synthetic enamel paint of approved colour by spray painting over a coat of red oxide primer complete all as specified and directed. | | 25 | Job |
|---|
| 23 | 23 | S & F in repairs starting capacitor suitable for deep freezer/ water cooler/ refrigerator etc of approved make and testing complete all as specified and directed. | | 10 | Each |
|---|
| 24 | 24 | S & F in repairs running capacitor suitable for window/ split type AC of 1.0/1.5 / 2.0 ton capacity and testing complete all as specified and directed. | | 50 | Each |
|---|
| 25 | 25 | S & F in repairs running capacitor suitable for deep freezer/ water cooler and testing complete all as specified and directed. | | 25 | Each |
|---|
| 26 | 26 | S & F in repairs thermostat suitable for window type AC of 1.5 ton capacity and testing complete all as specified and directed. | | 40 | Each |
|---|
| 27 | 27 | S & F in repairs thermostat suitable for Deep Freezer of any capacity and testing complete all as specified and directed. | | 10 | Each |
|---|
| 28 | 28 | S & F in repairs thermostat suitable for water cooler of any capacity and testing complete all as specified and directed. | | 25 | Each |
|---|
| 29 | 29 | S & F in repairs thermostat suitable for refrigerator of any capacity and testing complete all as specified and directed. | | 15 | Each |
|---|
| 30 | 30 | S & F in repairs timer switch suitable for refrigerator of any capacity and testing complete all as specified and directed. | | 25 | Each |
|---|
| 31 | 31 | S & F in repairs bimetal switch for refrigerator of any capacity and testing complete all as specified and directed. | | 10 | Each Job |
|---|
| 32 | 32 | S & F in repairs over load protector suitable for Deep freezer/ refrigerator of any capacity and testing complete all as specified and directed. | | 10 | Job |
|---|
| 33 | 33 | S & F in repairs fan motor suitable for water cooler/deep freezer of any capacity and testing complete all as specified and directed. | | 10 | Job |
|---|
| 34 | 34 | S & F in repairs fan motor suitable for window type AC of 1.5 Ton capacity and testing complete all as specified and directed. | | 5 | Job |
|---|
| 35 | 35 | S & F in repairs fan motor suitable for outer unit of split type AC of 1.5/2.0/3.0 Ton capacity and testing complete all as specified and directed. | | 30 | Job |
|---|
| 36 | 36 | S & F in repairs fan motor suitable for outer unit of inverter type split AC of 1.0/1.5/2.0 ton capacity and testing complete all as specified and directed. | | 15 | Job |
|---|
| 37 | 37 | S & F in repairs fan motor suitable for inner unit of split type AC of 1.5/2.0/3.0 Ton capacity and testing complete all as specified and directed. | | 30 | Job |
|---|
| 38 | 38 | S & F in repairs fan motor suitable for inner unit of inverter type split AC of 1.0/1.5/2.0 ton capacity and testing complete all as specified and directed. | | 15 | Job |
|---|
| 39 | 39 | S & F in repairs swing motor suitable for split type AC of 1.5 /2.0/3.0 Ton capacity and testing complete all as specified and directed. | | 25 | Job |
|---|
| 40 | 40 | S & F in repairs swing motor suitable for inverter type split AC of 1.0/1.5/2.0 ton capacity and testing complete all as specified and directed. | | 10 | Job |
|---|
| 41 | 41 | S & F in repairs BLDC fan motor suitable for split type AC of 1.5/2.0 Ton capacity and testing complete all as specifed and directed. | | 25 | Each |
|---|
| 42 | 42 | S & F in repairs BLDC fan motor suitable for inverter type split AC of 1.0/1.5/2.0 ton capacity and testing complete all as specifed and directed. | | 10 | Each |
|---|
| 43 | 43 | M & L for rewinding of defective outdoor unit fan motor of split type AC of 1.0/1.5/2.0 ton capacity and testing complete all as specified and directed. | | 50 | Job |
|---|
| 44 | 44 | S & F in repairs electronic control PCB of approved make suitable for split type AC of 1.0/1.5/2.0 Ton capacity and testing complete all as specified and directed. | | 50 | Each |
|---|
| 45 | 45 | S & F in repairs electronic control PCB of approved make suitable for mega split, vertical split type AC of 3.0 ton capacity and testing complete all as specified and directed. | | 5 | Each |
|---|
| 46 | 46 | S & F in repairs electronic control PCB with panel of approved make suitable for 3.0 ton cassette type AC and testing complete all as specified and directed. | | 5 | Each |
|---|
| 47 | 47 | S & F in repairs electronic control PCB of approved make suitable for window type AC of 1.0/1.5/2.0 of any capacity and testing complete all as specified and directed. | | 10 | Each |
|---|
| 48 | 48 | S & F in repairs electronic control PCB of approved make suitable for refrigerator of any capacity and testing complete all as specified and directed. | | 10 | Each |
|---|
| 49 | 49 | S & F in repairs sensor / anti ice thermostat suitable for split type AC of any model and testing complete all as specified and directed. | | 12 | Each |
|---|
| 50 | 50 | S & F in repairs remote unit suitable for split type AC of any model and testing complete all as specified and directed. | | 15 | Each |
|---|
| 51 | 51 | S & F in repairs remote battery 1.5 Volts suitable for split type AC of any model and testing complete all as specified and directed. | | 15 | Set of 2 |
|---|
| 52 | 52 | S & F in repairs hermetically sealed compressor unit suitable for split type AC of 1.0/1.5/2.0 Ton capacity to operate on 230 volt AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 25 | Each |
|---|
| 53 | 53 | S & F in repairs hermetically sealed compressor unit suitable for inverter type split AC of 1.0/1.5/2.0 ton capacity to operate on 230 volt AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 5 | Each |
|---|
| 54 | 54 | S & F in repairs hermetically sealed compressor unit suitable for split type AC of 3.0 Ton capacity to operate on 425 volt 3 phase AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 5 | Each |
|---|
| 55 | 55 | S & F in repairs hermetically sealed compressor unit suitable for window type AC of 1.5 Ton capacity to operate on 230 volt AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 3 | Each |
|---|
| 56 | 56 | S & F in repairs hermetically sealed compressor unit suitable for water cooler of 40/80 & 80/120 Ltrs capacity to operate on 230 volt AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 5 | Each |
|---|
| 57 | 57 | S & F in repairs hermetically sealed compressor unit suitable for refrigerator of 165 to 250 Ltrs capacity to operate on 230 volt AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 5 | Each |
|---|
| 58 | 58 | S & F in repairs hermetically sealed compressor unit suitable for refrigerator of 280 to 430 Ltrs capacity to operate on 230 volt AC by removing unserviceable compressor after cutting the refrigerant lines, connecting back the suction & discharge refrigerant lines after replacement, vaccumising charging of refrigerant, testing and commissioning for smooth functioning complete all as specified & directed. | | 5 | Each |
|---|
| 59 | 59 | S & F in repairs float valve of 15 mm dia bore suitable for water cooler/ cooling tower etc complete all as specified & directed. | | 5 | Each |
|---|
| 60 | 60 | S & F in repairs push tap of 15 mm dia bore, CP, brass, suitable for water cooler of any capacity complete all as specified & directed. | | 10 | Each |
|---|
| 61 | 61 | M & L for repair of voltage stabilizer after removing the burnt out unserviceable winding, cleaning the slots, insulating properly and rewinding transformer of capacity 5 KVA, single phase, 230 V 50 Hz AC, including testing complete all as specified & directed. | | 15 | Job |
|---|
| 62 | 62 | M & L for repair of voltage stabilizer after removing the burnt out unserviceable winding, cleaning the slots, insulating properly and rewinding transformer of capacity 3/2/1/0.5 KVA, single phase, 230 V 50 Hz AC, including testing complete all as specified & directed. | | 10 | Job |
|---|
| 63 | 63 | S & F in repairs time delay relay /main relay unit of voltage stabilizer of capacity 5 KVA & 4KVA including testing complete all as specified and directed. | | 10 | Job |
|---|
| 64 | 64 | S & F in repairs time delay relay /main relay unit of voltage stabilizer of capacity 3 KVA, 2KVA, 1KVA & 0.5KVA including testing complete all as specified and directed. | | 10 | Job |
|---|
| 65 | 65 | S & F in repairs service valve for split type AC of 1/4\" size and testing complete all as specified and directed. | | 10 | Each |
|---|
| 66 | 66 | S & F in repairs service valve for split type AC of 1/2\" size and testing complete all as specified and directed. | | 10 | Each |
|---|
| 67 | 67 | S & F in repairs service valve for split type AC of 5/8\" size and testing complete all as specified and directed. | | 10 | Each |
|---|
| 68 | 68 | S & F in repairs condenser unit for split type AC of 1.5/2.0 ton capacity and testing complete all as specified and directed. | | 20 | Each |
|---|
| 69 | 69 | S & F in repairs condenser unit for inverter type split AC of 1.0/1.5/2.0 ton capacity and testing complete all as specified and directed. | | 15 | Each |
|---|
| 70 | 70 | S & F in repairs outer body kit for split type AC of 1.5/2.0 ton capacity including condensor coil and fan motor and testing complete all as specified and directed.\nNote: Condensor coil and fan motor shall be measured and paid separately. | | 20 | Each |
|---|
| 71 | 71 | S & F in repairs copper pipe 1/4\" and testing complete all as specified and directed. | | 25 | RM |
|---|
| 72 | 72 | S & F in repairs copper pipe 1/2\" and testing complete all as specified and directed. | | 25 | RM |
|---|
| 73 | 73 | S & F in repairs flair nut 1/4\" and testing complete all as specified and directed. | | 10 | Each |
|---|
| 74 | 74 | S & F in repairs flair nut 1/2\" and testing complete all as specified and directed. | | 10 | Each |
|---|
| 75 | 75 | S & F in repairs PVC drain pipe for split type AC of any capacity and testing complete all as specified and directed. | | 25 | RM |
|---|
| 76 | 76 | S & F in repairs of PC Board of indoor for inverter type split AC of 1.0/1.5/2.0 ton capacity and testing complete all as specified and directed. | | 10 | Each |
|---|
| 77 | 77 | S & F in repairs of PC Board of outdoor for inverter type split AC of 2.0/3.0 ton capacity and testing complete all as specified and directed. | | 10 | Each |
|---|
| 78 | 78 | Removing window type AC of 1.5 ton capacity by taking out from the existing location alongwith frame and shifting & fixing at new location cutting opening wall of required size topping up of gas and making good distrubed surface of wall opening by plastering and applying white wash including closing the old opening with brick work, making good distrubed surface, plastering and applying white wash complete all as specified and directed. | | 5 | Job |
|---|
| 79 | 79 | Removing split type AC of 1.5/2.0/3.0 ton capacity from existing location after pumping down gas and refixing at new location including provision of new copper pipes of required length and charging of gas in compressor after rectifying leak and rat cutting complete all as specified and directed. | | 20 | Job |
|---|
| 80 | 80 | S & F in repairs MS/GI bracket for fixing outer unit of Air conditioners of 1.5 /2.0 ton capacity complete all as specified and directed. | | 20 | Pair |
|---|
| 81 | 81 | Supply and replace Metal plug and socket with TPN / TP of MCB 40/32 Amps and steel enclosureall as specified and as directed | | 20 | Each |
|---|
| 82 | 82 | S & F in repairs metal plug and socket with MCB 20 Amps and steel enclosure complete all as specified and directed. | | 20 | Each |
|---|
| 83 | 83 | S & F in repairs MCB SP 5 to 30 Amps 230 Volts complete all as specified and directed. | | 20 | Each |
|---|
| 84 | 84 | Taking down existing submain wiring and M & L for submain wiring complete with two runs of 4 Sqmm and one run of 4 Sqmm earth continuity 1100 V grade PVC insulated unsheathed FR cable with single core multistranded ISI marked copper conductor (IS 694) drawn through and including non metallic rigid PVC caping and casing and accessories complete all as specified and directed. \nNote: One run of PVC casing and caping, two runs of 4 Sqmm cable and one run of earth wire shall be measured as one length. | | 200 | RM |
|---|
| 85 | 85 | S & F in repairs thermocool insulation for copper pipe for split type AC of any type and capacity complete all as specified and directed. | | 25 | Each |
|---|
| 86 | 86 | S & F in repairs fan blade of outdoor unit fan motor of split type AC of 1.0/1.5/2.0/3.0 ton capacity complete all as specified and directed. | | 25 | Each |
|---|
| 87 | 87 | Servicing / cleaning / AMC of water purifire 'CANT RO' or any type and capacity of existing make complete all as specified and as directed | | 10 | Each |
|---|
| 88 | 88 | Supply and replace of water filter for water cooler / purifire 'CANTT RO' or any type and capacity of existing make complete all as specified and as directed | | 10 | Each |
|---|
| 89 | 89 | Comprehensive Annual Maintenance Contract of the following AC Plants for 11 months through OEM :- | | 11 | Per Month |
|---|
| 90 | 89.01 | (a) Water Cooled Chiller AC Plants of capacity 26 Tr - 03 Nos Make - Voltas ( Location - HQ SAC) | | | |
|---|
| 91 | 89.02 | DETAIL OF AC PLANTS (i) Chiller Unit - 03 Nos (Machine Ser No ACWCD 5026 DPMN2X1P) (ii) Compressor - 09 Nos (Machine Ser No SZ18554 RC) (iii) Cooling tower with FRP Basin - 01 Set (RB - 9061) (iv) Monoblock pumpset 5 HP - 02 Nos , Make - Kirloskar KDS 520, 3 Phase. (v) 15 TR Double Sking AHU - 02 Nos (vi) 10 TR Double Skin AHU - 02 Nos (vii) Pump set 5 HP Make - KBL - 02 Nos DB 40/12, 3000 RPM. (viii) LT Panel Board Indoor type - 01 No | | | |
|---|
| 92 | 89.03 | (b) Air cooled package AC Plant of capacity 10 Tr - 06 Nos Make : Voltas (Location - HQ SAC Auditorium) | | | |
|---|
| 93 | 89.04 | DETAIL OF AC PLANTS (i) Indoor Unit - 06 Nos ( Manufacture Ser No D000031,D000032, D000025, D000026, D000024, D000027) (ii) Outdoor Unit - 06 Nos (Manufacture Ser Nos D001325/26, D001352/53, D001316/48, D001349/14, D001328/20, D001309/27 | | | |
|---|
| 94 | 89.05 | Scope of Works (i) To attend all the complaints/break down. (ii) Inspecting the plant and carry out preventive maintenance quarterly basis. (iii) To check the refrigeration system, compressor,controller, motor and starter and ensure healthy working condition of the equipment (iv) Checking the system for any leaks and rectification of leaks if found including refrigerant. (v) Taking the set of readings and evaluating to ensure satisfactory perforance for the plant. (vi) Checking the control system for operation and adjusting the settings. (vii) Checking the functioning of compressor and its accessories. | | | |
|---|
| 95 | 89.06 | (viii) Annual checking of compressor oil and changing if required. (ix) De-scaling of water cooled condenser once in a year (x) Replacement of refrigerant gas a a result of leak developed due to wear and tear. (xi) Repairing of compressor and motor at site as and when required. (xii) Checking the functioning of micrfoprocessor controller for its proper functioning and repair/replacement of the same if found necessary. | | | |
|---|
| 96 | 90 | Sub Total of Schedule 'A' | | | |
|---|
| 97 | 91 | SCHEDULE OF CREDIT | | | |
|---|
| 98 | 92 | Schedule of Credit (Minus) Rs. 38,691.00 B/F from Ser page No.112.\nNOTE: Bidder shall insert credit amount as rate Rs. 38,691.00 in Green field under Col-5. | | 1 | Nos |
|---|
| 99 | 93 | Sub Total of Schedule of Credit | | | |
|---|