| 1 | 1.01 | Withdrawing the Existing XLPE/A cable of the following sizes from wall and carrying to section store as per direction of E.I.C (a) 4 core 120 sq. mm. XLPE/A Alu. Cable | BI01010001010000000000000515BI0100001114 | 250 | Each |
|---|
| 2 | 2.01 | Supplying and fixing 415V, 200Amp TPN on load front operated Changeover switch with Sheet Steel\nenclosure on angle iron frame on wall with nuts\nbolts etc. (Make: L&T) | BI01010001010000000000000515BI0100001115 | 1 | Each |
|---|
| 3 | 3.01 | Fixing 415V, 250Amp TPN on load front\noperated Changeover switch with Sheet Steel\nenclosure on angle iron frame on wall with nuts\nbolts etc | BI01010001010000000000000515BI0100001116 | 1 | Each |
|---|
| 4 | 4.01 | Installation,Testing & commissioning of cubical type panel,compartmentalized floor mounted,indoor type dust and vermin proof powder coated panel panel board(1200X1000X200) and foundation should make extra height at about 0.60mt above ground level by Brick foundation work including plastering and neat cement finish.The FDB should be comprising with the following materials as per direction of E.I.C with carrying from Section Store to Radiotheraphy Panel . | BI01010001010000000000000515BI0100001117 | 1 | Job |
|---|
| 5 | 5.01 | Laying of one No. cable 4core 120 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed | BI01010001010000000000000515BI0100001118 | 220 | Mtr |
|---|
| 6 | 6.01 | Laying of cable 4 core 50 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting | BI01010001010000000000000515BI0100001119 | 30 | Mtr |
|---|
| 7 | 7.01 | Supply and Delivery of 1.1 K.V grade 4 core 120 sq. mm. XLPE/A Alu. Cable . As per choice of EIC | BI01010001010000000000000515BI0100001120 | 250 | Mtr |
|---|
| 8 | 8.01 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below\n4 core 120 sq. mm. XLPE/A Alu. Cable | BI01010001010000000000000515BI0100001122 | 20 | Each |
|---|
| 9 | 8.02 | 3.5 Core 35 Sqmm XLPE/A Alu Cable. | BI01010001010000000000000515BI0100001123 | 6 | Each |
|---|
| 10 | 9.01 | Finishing the end of following XLPE/PVC armoured cables by crimping method including the supply & fixing solderless socket (Dowels make), tapes anti corrosive paste & jointing material.\n 4 core 120 sq. mm. XLPE/A Alu. Cable | BI01010001010000000000000515BI0100001125 | 20 | Set |
|---|
| 11 | 9.02 | 3.5 Core 35 Sqmm XLPE/A Alu Cable. | BI01010001010000000000000515BI0100001126 | 6 | Set |
|---|
| 12 | 10.01 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR'(Precision make) incl. necy. fittings as required \nv) 4 x 16 sqmm + 2 x10 sqmm ECC (from VTPN to HTPN)as ECC | BI01010001010000000000000515BI0100001128 | 50 | Mtr |
|---|
| 13 | 11.01 | Supplying & fixing sheet metal (16 SWG) Iron Clad 415V, 4 bar Cu. Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991) \nii) 415V, 125A, 4 bar Cu. Busbar chambers[ Dimension of Cu. bars: 4 x 15x3mm; Dimension of Sheet Metal Box: 250x150mm(WxD)] | BI01010001010000000000000515BI0100001130 | 5 | Mtr |
|---|
| 14 | 12.01 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.\niv)10Sqmm | BI01010001010000000000000515BI0100001132 | 28 | Set |
|---|
| 15 | 12.02 | v)16Sqmm | BI01010001010000000000000515BI0100001133 | 30 | Set |
|---|
| 16 | 13.01 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level (By ISI-Medium GI pipe).incl excavation of soil of 2m3 as to GS. | BI01010001010000000000000515BI0100001134 | 2 | Each |
|---|
| 17 | 14.01 | Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. | BI01010001010000000000000515BI0100001135 | 40 | Mtr |
|---|